| 2020-07-27 11:06:33 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20060009 |
| | ADD: 2600 N. MILITARY TRL. KEISER UNIVERSITY DORMS |
| | CONT: RACE CONSTRUCTION |
| | TEL: 561-632-3371 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE:MON. JULY 27TH/ 2020 |
| | ACTION: DENIED |
| | |
| | 4X FEE / NOTICE!!!!! FLORIDA STATUTE 553.80(2)(B) |
| | WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? |
| | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. |
| | |
| | NO CHANGE IN PLANS, NO BUILDING RESPONSE LETTER IN |
| | REGARDS TO ACCESSIBILITY. |
| | |
| | |
| | 1) THE SUBMITTED SKETCH DOES NOT MEET THE REQUIREMENT |
| | OF DRAFTSMAN QUALITY PLANS. 107.2.1.3. QUALITY OF |
| | PLANS. BUILDING PLANS SHALL BE DRAWN TO A 1/8TH INCH |
| | SCALE ON SUBSTANTIAL PAPER OR OTHER ACCEPTABLE MEDIUM. |
| | THE BUILDING OFFICIAL MAY ESTABLISH THROUGH DEPARTMENT |
| | POLICY OTHER STANDARDS FOR THE PLANS AND SPECIFICATIONS |
| | IN ORDER TO PROVIDE CONFORMITY TO ITS RECORD RETENTION |
| | PROGRAM. THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM |
| | SIZE, SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED |
| | TO RECORD MANAGEMENT. ELECTRONIC MEDIA MUST BE |
| | COMPATIBLE WITH THE ARCHIVE REQUIREMENTS OF FLORIDA |
| | STATUTES. |
| | |
| | 2A) 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION 107.2.1. |
| | CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT CLARITY TO |
| | INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| | OFFICIAL. THE SUBMITTED SKETCH DOES NOT PROVIDE |
| | DIMENSIONS OF THE DORM, BATHROOMS AND SHOWER |
| | ENCLOSURES. THE PLANS DO NOT SHOW CURBS NOR PAN |
| | DETAILS. |
| | |
| | |
| | 2B) CERTIFICATION BY CONTRACTOR. 107.3.4.3 |
| | CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE EXCEPTION |
| | TO ENGINEERED PLANS UNDER 471.003(H) ELECTRICAL/ |
| | PLUMBING/ MECHANICAL, 481.229(1)(C) (BUILDING) REQUIRES |
| | THE CONTRACTOR FOR THAT TRADE THAT WILL BE LICENSED IN |
| | THAT TRADE, WILL ALSO BE THE CONTRACTOR THAT DESIGNS |
| | THE SYSTEM UNDER THAT TRADE. THE CONTRACTOR (QUALIFIER) |
| | THAT CREATED / DRAWN THE SET OF PLANS WILL NEED TO |
| | IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE |
| | PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR |
| | THE TRADE YOU ARE LICENSED IN AND PLANS DRAWN. FOR EACH |
| | TRADE THE CONTRACTOR RESPONSIBLE FOR THE DESIGN UNDER |
| | THE TRADE LICENSED IN MUST PRINT THEIR NAME, SIGN THEIR |
| | NAME AND LICENSE NUMBER, NOTE THESE PLANS APPEAR TO BE |
| | DRAWN BY ONE INDUVIAL, THEY WOULD HAVE TO BE LICENSED |
| | AS A BUILDING, ELECTRICAL AND PLUMBING CONTRACTOR TO |
| | SUBMIT ALL THESE TRADES UNDER ONE SHEET. |
| | |
| | |
| | 3) PLEASE ALSO REVIEW THE 2017EXISTING BUILDING CODE |
| | 806.1 ACCESSIBILITY CODE. THIS SECTION REFERS YOU BACK |
| | TO THE 2017 FBC-ACCESSIBILITY CODE. |
| | SECTION 224.7 HOUSING AT A PLACE OF EDUCATION. |
| | TRANSIENT LODGING GUEST ROOMS IN SECTION 224 AND 806 |
| | SHALL APPLY. THE TERM SLEEPING ROOM IS INTENDED TO BE |
| | INTERCHANGEABLE WITH THE TERM GUEST ROOMS AS IT IS USED |
| | IN THE TRANSIENT LODGING STANDARDS. |
| | |
| | 3A) 2017 ACC. CODE SECTION 224.1.1 WHERE GUEST ROOMS |
| | ARE ALTERED THE REQUIREMENTS OF 224 SHALL APPLY ONLY TO |
| | THE GUEST ROOMS BEING ALTERED OR ADDED UNTIL THE NUMBER |
| | OF GUEST ROOMS COMPLIES WITH THE MINIMUM NUMBER |
| | REQUIRED FOR NEW CONSTRUCTION. |
| | |
| | 3B) PLEASE REVIEW IN THE 2017 FBC-ACCESSIBILITY CODE |
| | TABLE 224.2 & SECTION224.6.3 A MINIMUM OF ONE BATHROOM |
| | WILL NEED TO MEET THE REQUIREMENTS FOR AN ACCESSIBLE |
| | BATHROOM ALL ELEMENTS OF THE RESTROOM, LAV, TOILET AND |
| | SHOWER AND ACCESSORIES WILL NEED TO MEET ALL OF THE |
| | REQUIREMENTS FOUND IN CHAPTER 6 OF THE ACCESSIBILITY |
| | BOOK. |
| | |
| | 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |