Plan Review Details - Permit 20060009
Plan Review Stops For Permit 20060009
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2020-07-27 Cont ID  
Sent By jwitmer Date 2020-07-27 Time 11:13 Rev Time 0.00
Received By jwitmer Date 2020-07-27 Time 10:59 Sent To  
Notes
2020-07-27 11:11:26PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
 19120504
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-07-05 Cont ID  
Sent By jwitmer Date 2020-07-05 Time 20:16 Rev Time 0.00
Received By jwitmer Date 2020-07-05 Time 19:29 Sent To  
Notes
2020-07-05 20:16:11PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
 19120504
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-08-13 Cont ID  
Sent By shill Date 2020-08-13 Time 10:42 Rev Time 0.00
Received By shill Date 2020-08-13 Time 10:42 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-07-27 Cont ID  
Sent By jwitmer Date 2020-07-27 Time 11:13 Rev Time 0.00
Received By jwitmer Date 2020-07-27 Time 10:59 Sent To  
Notes
2020-07-27 11:06:33WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20060009
 ADD: 2600 N. MILITARY TRL. KEISER UNIVERSITY DORMS
 CONT: RACE CONSTRUCTION
 TEL: 561-632-3371
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE:MON. JULY 27TH/ 2020
 ACTION: DENIED
  
 4X FEE / NOTICE!!!!! FLORIDA STATUTE 553.80(2)(B)
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
 NO CHANGE IN PLANS, NO BUILDING RESPONSE LETTER IN
 REGARDS TO ACCESSIBILITY.
  
  
 1) THE SUBMITTED SKETCH DOES NOT MEET THE REQUIREMENT
 OF DRAFTSMAN QUALITY PLANS. 107.2.1.3. QUALITY OF
 PLANS. BUILDING PLANS SHALL BE DRAWN TO A 1/8TH INCH
 SCALE ON SUBSTANTIAL PAPER OR OTHER ACCEPTABLE MEDIUM.
 THE BUILDING OFFICIAL MAY ESTABLISH THROUGH DEPARTMENT
 POLICY OTHER STANDARDS FOR THE PLANS AND SPECIFICATIONS
 IN ORDER TO PROVIDE CONFORMITY TO ITS RECORD RETENTION
 PROGRAM. THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM
 SIZE, SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED
 TO RECORD MANAGEMENT. ELECTRONIC MEDIA MUST BE
 COMPATIBLE WITH THE ARCHIVE REQUIREMENTS OF FLORIDA
 STATUTES.
  
 2A) 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION 107.2.1.
 CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT CLARITY TO
 INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. THE SUBMITTED SKETCH DOES NOT PROVIDE
 DIMENSIONS OF THE DORM, BATHROOMS AND SHOWER
 ENCLOSURES. THE PLANS DO NOT SHOW CURBS NOR PAN
 DETAILS.
  
  
 2B) CERTIFICATION BY CONTRACTOR. 107.3.4.3
 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE EXCEPTION
 TO ENGINEERED PLANS UNDER 471.003(H) ELECTRICAL/
 PLUMBING/ MECHANICAL, 481.229(1)(C) (BUILDING) REQUIRES
 THE CONTRACTOR FOR THAT TRADE THAT WILL BE LICENSED IN
 THAT TRADE, WILL ALSO BE THE CONTRACTOR THAT DESIGNS
 THE SYSTEM UNDER THAT TRADE. THE CONTRACTOR (QUALIFIER)
 THAT CREATED / DRAWN THE SET OF PLANS WILL NEED TO
 IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE
 PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR
 THE TRADE YOU ARE LICENSED IN AND PLANS DRAWN. FOR EACH
 TRADE THE CONTRACTOR RESPONSIBLE FOR THE DESIGN UNDER
 THE TRADE LICENSED IN MUST PRINT THEIR NAME, SIGN THEIR
 NAME AND LICENSE NUMBER, NOTE THESE PLANS APPEAR TO BE
 DRAWN BY ONE INDUVIAL, THEY WOULD HAVE TO BE LICENSED
 AS A BUILDING, ELECTRICAL AND PLUMBING CONTRACTOR TO
 SUBMIT ALL THESE TRADES UNDER ONE SHEET.
  
  
 3) PLEASE ALSO REVIEW THE 2017EXISTING BUILDING CODE
 806.1 ACCESSIBILITY CODE. THIS SECTION REFERS YOU BACK
 TO THE 2017 FBC-ACCESSIBILITY CODE.
 SECTION 224.7 HOUSING AT A PLACE OF EDUCATION.
 TRANSIENT LODGING GUEST ROOMS IN SECTION 224 AND 806
 SHALL APPLY. THE TERM SLEEPING ROOM IS INTENDED TO BE
 INTERCHANGEABLE WITH THE TERM GUEST ROOMS AS IT IS USED
 IN THE TRANSIENT LODGING STANDARDS.
  
 3A) 2017 ACC. CODE SECTION 224.1.1 WHERE GUEST ROOMS
 ARE ALTERED THE REQUIREMENTS OF 224 SHALL APPLY ONLY TO
 THE GUEST ROOMS BEING ALTERED OR ADDED UNTIL THE NUMBER
 OF GUEST ROOMS COMPLIES WITH THE MINIMUM NUMBER
 REQUIRED FOR NEW CONSTRUCTION.
  
 3B) PLEASE REVIEW IN THE 2017 FBC-ACCESSIBILITY CODE
 TABLE 224.2 & SECTION224.6.3 A MINIMUM OF ONE BATHROOM
 WILL NEED TO MEET THE REQUIREMENTS FOR AN ACCESSIBLE
 BATHROOM ALL ELEMENTS OF THE RESTROOM, LAV, TOILET AND
 SHOWER AND ACCESSORIES WILL NEED TO MEET ALL OF THE
 REQUIREMENTS FOUND IN CHAPTER 6 OF THE ACCESSIBILITY
 BOOK.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-07-07 Cont ID  
Sent By jwitmer Date 2020-07-05 Time 20:15 Rev Time 0.00
Received By jwitmer Date 2020-07-05 Time 19:28 Sent To  
Notes
2020-07-05 20:14:25WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20060009
 ADD: 2600 N. MILITARY TRL. KEISER UNIVERSITY DORMS
 CONT: RACE CONSTRUCTION
 TEL: 561-632-3371
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SUN. JULY 06TH/ 2020
 ACTION: DENIED
  
 1) THE SUBMITTED SKETCH DOES NOT MEET THE REQUIREMENT
 OF DRAFTSMAN QUALITY PLANS. 107.2.1.3. QUALITY OF
 PLANS. BUILDING PLANS SHALL BE DRAWN TO A 1/8TH INCH
 SCALE ON SUBSTANTIAL PAPER OR OTHER ACCEPTABLE MEDIUM.
 THE BUILDING OFFICIAL MAY ESTABLISH THROUGH DEPARTMENT
 POLICY OTHER STANDARDS FOR THE PLANS AND SPECIFICATIONS
 IN ORDER TO PROVIDE CONFORMITY TO ITS RECORD RETENTION
 PROGRAM. THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM
 SIZE, SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED
 TO RECORD MANAGEMENT. ELECTRONIC MEDIA MUST BE
 COMPATIBLE WITH THE ARCHIVE REQUIREMENTS OF FLORIDA
 STATUTES.
  
 2A) 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION 107.2.1.
 CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT CLARITY TO
 INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. THE SUBMITTED SKETCH DOES NOT PROVIDE
 DIMENSIONS OF THE DORM, BATHROOMS AND SHOWER
 ENCLOSURES. THE PLANS DO NOT SHOW CURBS NOR PAN
 DETAILS.
  
  
 2B) CERTIFICATION BY CONTRACTOR. 107.3.4.3
 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE EXCEPTION
 TO ENGINEERED PLANS UNDER 471.003(H) ELECTRICAL/
 PLUMBING/ MECHANICAL, 481.229(1)(C) (BUILDING) REQUIRES
 THE CONTRACTOR FOR THAT TRADE THAT WILL BE LICENSED IN
 THAT TRADE, WILL ALSO BE THE CONTRACTOR THAT DESIGNS
 THE SYSTEM UNDER THAT TRADE. THE CONTRACTOR (QUALIFIER)
 THAT CREATED / DRAWN THE SET OF PLANS WILL NEED TO
 IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE
 PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR
 THE TRADE YOU ARE LICENSED IN AND PLANS DRAWN. FOR EACH
 TRADE THE CONTRACTOR RESPONSIBLE FOR THE DESIGN UNDER
 THE TRADE LICENSED IN MUST PRINT THEIR NAME, SIGN THEIR
 NAME AND LICENSE NUMBER, NOTE THESE PLANS APPEAR TO BE
 DRAWN BY ONE INDUVIAL, THEY WOULD HAVE TO BE LICENSED
 AS A BUILDING, ELECTRICAL AND PLUMBING CONTRACTOR TO
 SUBMIT ALL THESE TRADES UNDER ONE SHEET.
  
  
 3) PLEASE ALSO REVIEW THE 2017EXISTING BUILDING CODE
 806.1 ACCESSIBILITY CODE. THIS SECTION REFERS YOU BACK
 TO THE 2017 FBC-ACCESSIBILITY CODE.
 SECTION 224.7 HOUSING AT A PLACE OF EDUCATION.
 TRANSIENT LODGING GUEST ROOMS IN SECTION 224 AND 806
 SHALL APPLY. THE TERM SLEEPING ROOM IS INTENDED TO BE
 INTERCHANGEABLE WITH THE TERM GUEST ROOMS AS IT IS USED
 IN THE TRANSIENT LODGING STANDARDS.
  
 3A) 2017 ACC. CODE SECTION 224.1.1 WHERE GUEST ROOMS
 ARE ALTERED THE REQUIREMENTS OF 224 SHALL APPLY ONLY TO
 THE GUEST ROOMS BEING ALTERED OR ADDED UNTIL THE NUMBER
 OF GUEST ROOMS COMPLIES WITH THE MINIMUM NUMBER
 REQUIRED FOR NEW CONSTRUCTION.
  
 3B) PLEASE REVIEW IN THE 2017 FBC-ACCESSIBILITY CODE
 TABLE 224.2 & SECTION224.6.3 A MINIMUM OF ONE BATHROOM
 WILL NEED TO MEET THE REQUIREMENTS FOR AN ACCESSIBLE
 BATHROOM ALL ELEMENTS OF THE RESTROOM, LAV, TOILET AND
 SHOWER AND ACCESSORIES WILL NEED TO MEET ALL OF THE
 REQUIREMENTS FOUND IN CHAPTER 6 OF THE ACCESSIBILITY
 BOOK.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2020-07-16 Cont ID  
Sent By jleahy Date 2020-07-16 Time 14:25 Rev Time 0.00
Received By jleahy Date 2020-07-16 Time 14:25 Sent To  
Notes
2020-07-16 14:25:58NO ELECTRICAL WORK INVOLVED JLEAHY

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-07-24 Cont ID  
Sent By pleduc Date 2020-07-24 Time   Rev Time 0.00
Received By pleduc Date 2020-07-24 Time 10:01 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-06-12 Cont ID  
Sent By pleduc Date 2020-06-12 Time   Rev Time 0.00
Received By pleduc Date 2020-06-12 Time 13:49 Sent To  
Notes
2020-06-12 16:10:13THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THE ADDRESS IS THE GENERAL ADDRESS OF THE
 UNIVERSITY.
  
 PLEASE PROVIDE THE ADDRESS AND/OR NAME OF THE
 APPLICABLE DORM AND ENSURE IT IS ON THE PLAN SHEET.
  
  
 2) THE APPLICATION STATES 18 BATHROOMS & 18 SHOWERS.
  
 DOES THESE NUMBERS ACCOUNT FOR ALL/EVERY ROOM ION THE
 APPLICABLE DORM?
  
 IF NOT, THE INDIVIDUAL ROOM NUMBERS NEED TO BE LISTED
 ON THE APPLICATION AND THE PLAN SHEET.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-08-18 Cont ID  
Sent By shill Date 2020-08-18 Time 13:15 Rev Time 0.00
Received By shill Date 2020-07-23 Time 15:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-07-16 Cont ID  
Sent By jleahy Date 2020-07-16 Time 14:26 Rev Time 0.00
Received By jleahy Date 2020-06-11 Time 14:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-08-13 Cont ID  
Sent By jesmith Date 2020-08-13 Time 11:18 Rev Time 0.00
Received By jesmith Date 2020-08-13 Time 08:44 Sent To  
Notes
2020-08-13 11:18:44PLUMBING COMMENTS: APPROVED
 NORMAL MAINTENANCE
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
  
 20060009 2600 N MILITARY TRL
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-07-15 Cont ID  
Sent By jesmith Date 2020-07-15 Time 11:17 Rev Time 0.00
Received By jesmith Date 2020-07-15 Time 09:10 Sent To  
Notes
2020-07-15 11:17:16CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20060009 2600 N MILITARY TRL
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 1. PER WPB FBC 107.2.1, PROVIDE PLAN COMPLYING WITH WPB
 FBC 107.2.1.3 (QUALITY OF PLANS) SIGNED AND STAMPED BY
 THE DESIGN PROFESSIONAL IN ACCORDANCE WITH WPB FBC
 107.1 SHOWING THE FULL SCOPE OF THE WORK INCLUDING BUT
 NOT LIMITED TO THE FOLLOWING:
  
 A. FLOOR PLAN SHOWING ALL IMPACTED DORM ROOMS. INDICATE
 GROUND FLOOR AND/OR ELEVATED FLOOR.
 B. DIMENSIONS OF THE DORM, BATHROOMS AND SHOWER
 ENCLOSURES
 C. DETAIL FOR SHOWER PAN (INCLUDE TYPE OF MATERIAL),
 CURB AND DRAIN COMPLYING WITH SHOWING COMPLIANCE WITH
 FBC PL SECTION 417.
 E. SPECIFICATION FOR SHOWER VALVE SHOWING COMPLIANCE
 WITH FBC PL 424.3. WHERE A HAND HELD SHOWER IS
 REQUIRED, COMPLY WITH FBC PL 424.2
 F. LOCATION OF EXISTING SERVICE SINK OR PROVIDE NEW
 SERVICE SINK TO SHOW COMPLIANCE WITH FBC PL TABLE 403.1
 G. PROVIDE ALL CLEAR FLOOR SPACES AND TURNING SPACES
 FOR ACCESSIBLE PLUMBING FIXTURES IN ACCORDANCE WITH FBC
 ACC SECTIONS 304 AND 305
 H. PROVIDE DETAILS FOR ACCESSIBLE FIXTURES SHOWING
 COMPLIANCE WITH FBC ACC CHAPTER 6.
 I. PER FBC ACC 806.2.4, PROVIDE AT LEAST ONE BATHROOM
 THAT IS PROVIDED AS PART OF A GUEST ROOM AND COMPLIES
 WITH 603. NO FEWER THAN ONE WATER CLOSET, ONE LAVATORY,
 AND ONE BATHTUB OR SHOWER SHALL COMPLY WITH APPLICABLE
 REQUIREMENTS OF 603 THROUGH 610. IN ADDITION, REQUIRED
 ROLL-IN SHOWER COMPARTMENTS SHALL COMPLY WITH 608.2.2
 OR 608.2.3. TOILET AND BATHING FIXTURES REQUIRED TO
 COMPLY WITH 603 THROUGH 610 SHALL BE PERMITTED TO BE
 LOCATED IN MORE THAN ONE TOILET OR BATHING AREA,
 PROVIDED THAT TRAVEL BETWEEN FIXTURES DOES NOT REQUIRE
 TRAVEL BETWEEN OTHER PARTS OF THE GUEST ROOM.
 J. PER FBC ACC 806.2.4.1, IF VANITY COUNTER TOP SPACE
 IS PROVIDED IN NON-ACCESSIBLE GUEST TOILET OR BATHING
 ROOMS, COMPARABLE VANITY COUNTER TOP SPACE, IN TERMS OF
 SIZE AND PROXIMITY TO THE LAVATORY, SHALL ALSO BE
 PROVIDED IN ACCESSIBLE GUEST TOILET OR BATHING ROOMS.
 K. PER FBC ACC 806.4, PLEASE NOTE THIS SECTION DOES NOT
 RELIEVE THE OWNER OF THE RESPONSIBILITY OF PROVIDING
 ACCESSIBLE ROOMS IN CONFORMANCE WITH SECTION 224 AND
 806 OF THIS CODE. IN ALL BUILDINGS, STRUCTURES AND
 FACILITIESLICENSED AS A HOTEL, MOTEL OR RESORT
 CONDOMINIUM PURSUANT TO CHAPTER 509, F.S., A NUMBER OF
 ROOMS EQUALING AT LEAST 5 PERCENT OF THE GUEST ROOMS
 MINUS THE TOTAL NUMBER OF REQUIRED (ACCESSIBLE) ROOMS
 REQUIRED BY TABLE 224.2 SHALL PROVIDE THE FOLLOWING
 ADDITIONAL SPECIAL ACCESSIBILITY FEATURES:
 (I) GRAB RAILS IN BATHROOMS AND TOILET ROOMS WHICH
 COMPLY WITH SECTION 604.5.
 (II) ALL BEDS IN DESIGNED ACCESSIBLE GUEST ROOMS SHALL
 BE OPEN-FRAME TYPE THAT ALLOWS THE PASSAGE OF LIFT
 DEVICES.
 (III) WATER CLOSETS THAT COMPLY WITH SECTION 604.4.
  
 2A. PER WPB FBC 107.1,ALL PLANS TO BE SIGNED AND SEALED
 BY THE DESIGNER IN ACCORDANCE WITH FAC AND FS. DESIGNER
 TO PROVIDE DIGITAL SIGNATURE IN ACCORDANC WITH FAC AND
 FS OR SHALL PROVIDE SIGNED AND SEALED PAPER DOCUMENT
 PRIOR TO PERMIT ISSUANCE.CALL 561-805-6724 FOR
 ADDITIONAL INFORMATION
 2B. SEE WPB FBC 107.3.4.3 CERTIFICATION BY CONTRACTOR.
 PLEASE NOTE THE EXCEPTION TO ENGINEERED PLANS UNDER
 471.003(H) ELECTRICAL/ PLUMBING/ MECHANICAL,
 481.229(1)(C) (BUILDING) REQUIRES THE CONTRACTOR FOR
 THAT TRADE THAT WILL BE LICENSED IN THAT TRADE, WILL
 ALSO BE THE CONTRACTOR THAT DESIGNS THE SYSTEM UNDER
 THAT TRADE. THE CONTRACTOR (QUALIFIER) THAT CREATED /
 DRAWN THE SET OF PLANS WILL NEED TO IDENTIFY THEMSELVES
 AS THE AUTHOR OF THE PLANS. PLEASE PRINT YOUR NAME,
 SIGN YOUR NAME AND LICENSE NUMBER FOR THE TRADE YOU ARE
 LICENSED IN AND PLANS DRAWN. FOR EACH TRADE THE
 CONTRACTOR RESPONSIBLE FOR THE DESIGN UNDER THE TRADE
 LICENSED IN MUST PRINT THEIR NAME, SIGN THEIR NAME AND
 LICENSE NUMBER, NOTE THESE PLANS APPEAR TO BE DRAWN BY
 ONE INDIVIDUAL, THEY WOULD HAVE TO BE LICENSED AS A
 BUILDING, ELECTRICAL AND PLUMBING CONTRACTOR TO SUBMIT
 ALL THESE TRADES UNDER ONE SHEET.
  
 A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT
 THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A
 RESPONSE NARRATIVE ADDRESSING THE PLUMBING COMMENTS
 FROM THE FIRST REVIEW.
  
 END OF COMMENTS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20060009 2600 N MILITARY TRL
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-08-13 Cont ID  
Sent By shill Date 2020-08-13 Time 10:52 Rev Time 0.00
Received By shill Date 2020-08-13 Time 10:52 Sent To  
Notes
2020-08-13 11:03:11PROVISO - SUBMIT A SIGNED & SEALED ORIGINAL PLAN TO THE
 BUILDING DIVISION, EITHER DROP OFF BOX OR MAIL TO:
  
 BUILDING DIVISION 1ST FLOOR
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST
 WEST PALM BEACH, FL 33401
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-07-05 Cont ID  
Sent By jwitmer Date 2020-07-05 Time 20:22 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2020-07-05 20:22:23CERTIFICATION BY CONTRACTOR.
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT
 WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE
 CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE.
 THE CONTRACTOR (QUALIFIER) THAT CREATED / DRAWN THE SET
 OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR
 OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME
 AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN
 AND PLANS DRAWN. FOR EACH TRADE THE CONTRACTOR
 RESPONSIBLE FOR THE DESIGN UNDER THE TRADE LICENSED IN
 MUST PRINT THEIR NAME, SIGN THEIR NAME AND LICENSE
 NUMBER, NOTE THESE PLANS APPEAR TO BE DRAWN BY ONE
 INDUVIAL, THEY WOULD HAVE TO BE LICENSED AS A BUILDING,
 ELECTRICAL AND PLUMBING CONTRACTOR TO SUBMIT ALL THESE
 TRADES UNDER ONE SHEET.
  