Plan Review Details - Permit 20051001
Plan Review Stops For Permit 20051001
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-07-23 Cont ID  
Sent By pvalenti Date 2020-07-23 Time 13:17 Rev Time 0.00
Received By pvalenti Date 2020-07-23 Time 13:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-06-09 Cont ID  
Sent By rmcdouga Date 2020-06-09 Time 15:20 Rev Time 0.00
Received By rmcdouga Date 2020-06-09 Time 15:20 Sent To  
Notes
2020-06-09 15:21:13PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) ONLY PART OF THE GENERATOR PAD DRAWING WAS UPLOADED.
 THE ENTIRE DOCUMENT IS REQUIRED. FBC 107

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-06-19 Cont ID  
Sent By jleahy Date 2020-06-19 Time 14:25 Rev Time 0.00
Received By jleahy Date 2020-06-19 Time 08:03 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2020-06-25 Cont ID  
Sent By tklarge Date 2020-06-25 Time 07:51 Rev Time 0.00
Received By tklarge Date 2020-06-25 Time 07:51 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-06-17 Cont ID  
Sent By medwards Date 2020-06-17 Time 15:32 Rev Time 0.00
Received By medwards Date 2020-06-17 Time 14:29 Sent To  
Notes
2020-06-17 15:33:281ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20051001
  
 CODES IN EFFECT:
  
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE ADD THE VALUE OF THIS PROJECT TO THE GAS SUB
 PERMIT. FBC FS 107.2.1
  
 2) INTERIOR IS EXISTING LOW PRESSURE SYSTEM, THE METER
 IS GOING TO BE UPGRADED TO A 2PSI SYSTEM. WHERE IS THE
 MP REGULATOR FOR THE INTERIOR PIPING SYSTEM MAKING IT A
 LOW PRESSURE SYSTEM? FBC FS 107.2.1
  
 3) HOW IS THE ?? PE PIPING CONNECTING TO THE GENERATOR?
 IF A HOSE IS TO BE USED FOR THIS CONNECTION, PLEASE
 PROVIDE SPEC SHEETS FOR THIS HOSE. PLEASE IDENTIFY
 WHICH HOSE IS TO BE USED ALONG WITH THE PRESSURE DROP.
 FBC FS 107.2.1
  
 4) PROVIDE A DETAIL DRAWING OF THE NEW METER WITH THE
 2PSI REGULATOR AND THE PIPING TO THE BRANCHES TO THE
 GENERATOR, THE FUTURE POOL AND THE EXISTING HOUSE LOW
 PRESSURE SYSTEM. PLEASE SHOW PIPE SIZES, REGULATOR AND
 FITTINGS . FBC FS 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-07-23 Cont ID  
Sent By pvalenti Date 2020-07-23 Time 13:19 Rev Time 0.00
Received By pvalenti Date 2020-07-23 Time 10:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-06-19 Cont ID  
Sent By jleahy Date 2020-06-19 Time 14:25 Rev Time 0.00
Received By jleahy Date 2020-06-01 Time 15:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-06-17 Cont ID  
Sent By medwards Date 2020-06-17 Time 15:33 Rev Time 0.00
Received By medwards Date 2020-06-17 Time 15:33 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-07-23 Cont ID  
Sent By pvalenti Date 2020-07-23 Time 13:17 Rev Time 0.00
Received By pvalenti Date 2020-07-23 Time 13:17 Sent To  
Notes
2020-07-23 13:18:50PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 SIGNATURE REVIEW APPROVED BY PAPER ORIGINALS.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-06-09 Cont ID  
Sent By rmcdouga Date 2020-06-09 Time 15:21 Rev Time 0.00
Received By rmcdouga Date 2020-06-09 Time 15:21 Sent To  
Notes
2020-06-09 15:23:02THE GENERATOR PAD ENGINEERING IS REQUIRED TO HAVE THE
 ENGINEER'S DIGITAL SIGNATURE, FS 471 & FAC 61G15

Review Stop Z ZONING
Rev No 1 Status P Date 2020-06-05 Cont ID  
Sent By rthermid Date 2020-06-05 Time   Rev Time  
Received By rthermid Date 2020-06-05 Time   Sent To I
Notes
***NONE***