| 2020-07-23 09:08:55 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20050961 |
| | ADD: 1617 N. FLAGLER DR. SUITE: 7A |
| | CONT: ATHENS CONSTRUCTION |
| | TEL: 561-602-2255 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: THURS. JULY 23RD/ 2020 |
| | ACTION: DENIED |
| | |
| | 1) 2ND REVIEW ON SHEET A1 THE DESIGNER OF RECORD QUOTED |
| | CODE SECTIONS RATHER THAN PROVIDE DOCUMENTATION |
| | CONFIRMING THE CODE REQUIREMENT WAS MET. |
| | |
| | 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION 107.2.1. |
| | W.P.B. ADMINISTRATIVE CODE/2017 DRAWINGS & |
| | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO |
| | THE TECHNICAL CODES " THE CODE SHALL NOT BE CITED AS A |
| | WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS |
| | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | |
| | 1ST ROUND OF COMMENTS.SHEET A1 & A2 INDICATE NEW TILE |
| | IN THE SHOWERS BUT THE PLAN IS SILENT AS TO WHAT TYPE |
| | OF BACKER BOARD THE WALL SHOWER TILE WILL BE ADHERED |
| | TOO? PLEASE SHOW COMPLIANCE WITH THE: |
| | 2017 FBC-B 2509.2 BASE FOR TILE. MATERIALS USED AS A |
| | BASE FOR WALL TILE IN TUB AND SHOWER AREAS AND WALLS |
| | AND CEILING PANELS IN SHOWER AREAS SHALL BE OF |
| | MATERIALS LISTED IN TABLE 2509.2 AND INSTALLED IN |
| | ACCORDANCE WITH MANUFACTURER?S RECOMMENDATIONS. WATER |
| | RESISTANT GYPSUM BACKING BOARD SHALL BE USED AS A BASE |
| | FOR TILE IN WATER CLOSET COMPARTMENT WALLS WHEN |
| | INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C840 AND |
| | THE MANUFACTURE?S RECOMMENDATIONS. |
| | |
| | 2) 2ND REVIEW ON SHEET A1 THE DESIGNER OF RECORD QUOTED |
| | CODE SECTIONS RATHER THAN PROVIDE DOCUMENTATION |
| | CONFIRMING THE CODE REQUIREMENT WAS MET. |
| | |
| | 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION 107.2.1. |
| | W.P.B. ADMINISTRATIVE CODE/2017 DRAWINGS & |
| | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO |
| | THE TECHNICAL CODES " THE CODE SHALL NOT BE CITED AS A |
| | WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS |
| | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | |
| | 1ST ROUND OF COMMENTS. |
| | FLOOR INSULATION (FBC-B 2017). FOR TILE, STONE, MARBLE, |
| | VINYL AND WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND |
| | UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING |
| | STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH |
| | OF THE STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/ |
| | NO DROPPED CEILING: |
| | PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: |
| | |
| | TYPE I AND II BUILDINGS |
| | 2A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 2B) FBC-B 2017 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | 2C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2. |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | |