Plan Review Details - Permit 20050946
Plan Review Stops For Permit 20050946
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-07-07 Cont ID  
Sent By jleahy Date 2020-07-07 Time 16:27 Rev Time 0.00
Received By jleahy Date 2020-07-07 Time 16:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-06-22 Cont ID  
Sent By jleahy Date 2020-06-22 Time 17:03 Rev Time 0.00
Received By jleahy Date 2020-06-22 Time 16:16 Sent To  
Notes
2020-06-22 17:04:35ELECTRICAL PASS PENDING ON FIRE COMMRENTS RESOLUTION.
 JLEAHY

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-06-29 Cont ID  
Sent By pleduc Date 2020-06-29 Time   Rev Time 0.00
Received By pleduc Date 2020-06-29 Time 10:25 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-06-04 Cont ID  
Sent By pleduc Date 2020-06-04 Time   Rev Time 0.00
Received By pleduc Date 2020-06-04 Time 13:48 Sent To  
Notes
2020-06-04 14:25:52THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THERE ARE NO PRODUCT SPEC SHEETS TO VERIFY
 CALCULATIONS
  
 PER NFPA 72, CH 7
  
 7.2* MINIMUM REQUIRED DOCUMENTATION.
  
 (5) EQUIPMENT TECHNICAL DATA SHEETS
 (6) MANUFACTURERS PUBLISHED INSTRUCTIONS, INCLUDING
 OPERATION
 AND MAINTENANCE INSTRUCTIONS
  
 PLEASE PROVIDE.
  
  
 2) THERE IS NO INDICATION OF LIVE VOICE ANNOUNCEMENT.
  
 PER NFPA 101, CH 13
  
 13.3.4.3.3 OCCUPANT NOTIFICATION SHALL BE BY MEANS OF
 VOICE
 ANNOUNCEMENTS IN ACCORDANCE WITH 9.6.3.9 INITIATED BY
 THE PERSON
 IN THE CONSTANTLY ATTENDED RECEIVING STATION.
  
 13.3.4.3.6 THE ANNOUNCEMENT SHALL BE PERMITTED TO BE
 MADE VIA A
 VOICE COMMUNICATION OR PUBLIC ADDRESS SYSTEM IN
 ACCORDANCE WITH
 9.6.3.9.2.
 13.3.4.3.7 WHERE THE AUTHORITY HAVING JURISDICTION
 DETERMINES THAT
 A CONSTANTLY ATTENDED RECEIVING STATION IS IMPRACTICAL,
 AUTOMATICALLY TRANSMITTED EVACUATION OR RELOCATION
 INSTRUCTIONS
 SHALL BE PROVIDED IN ACCORDANCE WITH NFPA 72, NATIONAL
 FIRE
 ALARM AND SIGNALING CODE.
  
 PER NFPA 101 CH 9
  
 9.6.3.9 AUTOMATICALLY TRANSMITTED OR LIVE VOICE
 EVACUATION OR
 RELOCATION INSTRUCTIONS SHALL BE PERMITTED TO BE USED
 TO NOTIFY
 OCCUPANTS AND SHALL COMPLY WITH EITHER 9.6.3.9.1 OR
 9.6.3.9.2.
 9.6.3.9.1 AUTOMATICALLY TRANSMITTED OR LIVE VOICE
 EVACUATION OR
 RELOCATION INSTRUCTIONS SHALL BE IN ACCORDANCE WITH
 NFPA 72,
 NATIONAL FIRE ALARM AND SIGNALING CODE.
 9.6.3.9.2* WHERE PERMITTED BY CHAPTERS 11 THROUGH 43,
 AUTOMATICALLY TRANSMITTED OR LIVE VOICE ANNOUNCEMENTS
 SHALL BE
 PERMITTED TO BE MADE VIA A VOICE COMMUNICATION OR
 PUBLIC
 ADDRESS SYSTEM THAT COMPLIES WITH ALL OF THE FOLLOWING:
 (1) OCCUPANT NOTIFICATION, EITHER LIVE OR RECORDED,
 SHALL BE
 INITIATED AT A CONSTANTLY ATTENDED RECEIVING STATION BY
 PERSONNEL TRAINED TO RESPOND TO AN EMERGENCY.
 (2) AN APPROVED SECONDARY POWER SUPPLY SHALL BE
 PROVIDED FOR
 OTHER THAN EXISTING, PREVIOUSLY APPROVED SYSTEMS.
 (3) THE SYSTEM SHALL BE AUDIBLE ABOVE THE EXPECTED
 AMBIENT
 NOISE LEVEL.
 (4) EMERGENCY ANNOUNCEMENTS SHALL TAKE PRECEDENCE OVER
 ANY
 OTHER USE.
  
 PER NFPA 72 CH 24
  
 24.3 GENERAL.
 24.3.1* INTELLIGIBLE VOICE MESSAGES. EMERGENCY
 COMMUNICATIONS
 SYSTEMS SHALL BE CAPABLE OF THE REPRODUCTION OF
 PRERECORDED,
 SYNTHESIZED, OR LIVE (E.G., MICROPHONE, TELEPHONE
 HANDSET, AND RADIO) MESSAGES WITH VOICE INTELLIGIBILITY
 IN ACCORDANCE
 WITH CHAPTER 18.
  
 24.3.2 MICROPHONE USE.
 24.3.2.1* ALL USERS OF SYSTEMS THAT HAVE MICROPHONES
 FOR LIVE
 VOICE ANNOUNCEMENTS SHALL BE PROVIDED WITH POSTED
 INSTRUCTIONS
 FOR USING THE MICROPHONE.
  
 PLEASE PROVIDE DETAILS
  
  
 THE FOLLOWING TWO COMMENTS 3) & 4) ARE INTENDED TO
 EDUCATE AND REDUCE THE POSSIBLITIY OF UNNECESSARY FALSE
 ALARM AND NONREQUIRED DEVICES.
  
 HOWEVER, IF THE EOR OF THIS OCCUPANCY IS PROVIDING
 THESE DEVICES AS PART OF A LIFE SAFETY ELVALUATION,
 PLEASE PROVIDE THAT ELVALUATION FOR CONSIDERATION.
 PLEASE CONTACT MY OFFICE TO DISCUSS AND OR COORDINATE
 AGRREMENTS WITH THE PROPSED PROTECTION.
  
 PER NFPA 101 CH 13
  
 13.4.1.4 LIFE SAFETY BUILDING SYSTEMS DOCUMENT. THE AHJ
 SHALL BE PROVIDED WITH A LIFE SAFETY BUILDING SYSTEMS
 DOCUMENT
 PROVIDING THE INFORMATION REQUIRED IN 13.4.1.4.2
 THROUGH
 13.4.1.4.4.
 13.4.1.4.1 RESERVED.
 13.4.1.4.2 LIFE SAFETY NARRATIVE. A LIFE SAFETY
 NARRATIVE SHALL BE
 PROVIDED DESCRIBING THE FOLLOWING:
 (1) BUILDING OCCUPANCY, CONSTRUCTION TYPE, AND INTENDED
 USES
 AND EVENTS
 (2) BUILDING AREA AND POPULATION CAPACITY OF THE
 PROPOSED
 FACILITY
 (3) PRINCIPAL FIRE AND LIFE SAFETY FEATURES/STRATEGIES
 FOR THE
 BUILDING, INCLUDING ? AS APPLICABLE ? THE FOLLOWING:
 (A) EGRESS
 (B) ACCESS CONTROL
 (C) FIRE BARRIERS, SMOKE BARRIERS, AND SMOKE PARTITIONS
 (D) FIRE SUPPRESSION SYSTEMS
 (E) SMOKE CONTROL/PROTECTION
 ( F) FIRE DETECTION AND ALARM
 (G) PA SYSTEM
 (H) EMERGENCY ELEVATOR OPERATION
 (I) EMERGENCY POWER AND LIGHTING
 (J) PROVISIONS FOR PATRONS WITH DISABILITIES
 (K) FIRE DEPARTMENT ACCESS
 (L) FIRE/EMERGENCY COMMAND CENTER
 (4) EXTERIOR CONSTRUCTION DESIGN PARAMETERS
 USED/APPLIED
 13.4.1.4.3 LIFE SAFETY FLOOR PLANS. LIFE SAFETY FLOOR
 PLANS OF EACH
 LEVEL SHALL BE PROVIDED ? AS APPLICABLE ? WITH THE
 FOLLOWING:
 (1) OCCUPANT LOAD, EXIT LOCATION, EGRESS CAPACITY, MAIN
 ENTRANCE/EXIT, HORIZONTAL EXITS, TRAVEL DISTANCE, AND
 EXIT
 DISCHARGE
 (2) FIRE BARRIERS, SMOKE BARRIERS, AND SMOKE PARTITIONS
 (3) AREAS OF SMOKE-PROTECTED ASSEMBLY OCCUPANCY
 (4) SEPARATE SMOKE-PROTECTED AREAS OR ZONES
 (5) AREAS OF OTHER OCCUPANCY TYPE AND SEPARATIONS
 (6) UNPROTECTED VERTICAL OPENINGS
 (7) EVENT PLANS FOR EACH ANTICIPATED TYPE OF EVENT
 DEPICTING THE
 FOLLOWING:
 (A) SEATING CONFIGURATION
 (B) EXHIBIT BOOTH LAYOUT
 (C) STAGE LOCATION
 (D) OCCUPANT LOAD, EGRESS CAPACITY REQUIRED, EXITS
 PROVIDED,
 AND TRAVEL DISTANCE
 (E) ANY FLOOR OR STAGE USE RESTRICTIONS
 (F) PLAN AND/OR SECTION DRAWING INDICATING AREAS WHERE
 THE
 ROOF CONSTRUCTION IS MORE THAN 50 FT (15 M) ABOVE FLOOR
 LEVEL AND AREAS WHERE SPRINKLER PROTECTION IS OMITTED
 (G) AREAS OF REFUGE ? INTERIOR AND EXTERIOR
  
  
  
 3) THERE ARE INDICATION OF NUMEROUS PULL STATIONS AT
 EACH EXIT. PULL STATIONS LOCATIONS MAY BE
 REDUCED/ELIMINATED PER NFPA 101, CH 13 AND CH 9
  
 CH 13
  
 13.3.4.2 INITIATION.
 13.3.4.2.1 INITIATION OF THE REQUIRED FIRE ALARM SYSTEM
 SHALL BE BY
 BOTH OF THE FOLLOWING MEANS, AND THE SYSTEM SHALL BE
 PROVIDED
 WITH AN EMERGENCY POWER SOURCE:
 (1) MANUAL MEANS IN ACCORDANCE WITH 9.6.2.1(1), UNLESS
 OTHERWISE PERMITTED BY ONE OF THE FOLLOWING:
 (A) THE REQUIREMENT OF 13.3.4.2.1(1) SHALL NOT APPLY
 WHERE
 INITIATION IS BY MEANS OF AN APPROVED AUTOMATIC FIRE
 DETECTION SYSTEM IN ACCORDANCE WITH 9.6.2.1(2) THAT
 PROVIDES FIRE DETECTION THROUGHOUT THE BUILDING.
 (B) THE REQUIREMENT OF 13.3.4.2.1(1) SHALL NOT APPLY
 WHERE
 INITIATION IS BY MEANS OF AN APPROVED AUTOMATIC
 SPRINKLER SYSTEM IN ACCORDANCE WITH 9.6.2.1(3) THAT
 PROVIDES FIRE DETECTION AND PROTECTION THROUGHOUT THE
 BUILDING.
 (2) WHERE AUTOMATIC SPRINKLERS ARE PROVIDED, INITIATION
 OF THE
 FIRE ALARM SYSTEM BY SPRINKLER SYSTEM WATERFLOW, EVEN
 WHERE
 MANUAL FIRE ALARM BOXES ARE PROVIDED IN ACCORDANCE WITH
 13.3.4.2.1(1)
 13.3.4.2.2 THE INITIATING DEVICE SHALL BE CAPABLE OF
 TRANSMITTING AN
 ALARM TO A RECEIVING STATION, LOCATED WITHIN THE
 BUILDING, THAT IS
 CONSTANTLY ATTENDED WHEN THE ASSEMBLY OCCUPANCY IS
 OCCUPIED.
  
 CH 9
  
 9.6.2.6* FOR FIRE ALARM SYSTEMS USING AUTOMATIC FIRE
 DETECTION OR
 WATERFLOW DETECTION DEVICES TO INITIATE THE FIRE ALARM
 SYSTEM IN
 ACCORDANCE WITH CHAPTERS 11 THROUGH 43, NOT LESS THAN
 ONE MANUAL
 FIRE ALARM BOX, LOCATED AS REQUIRED BY THE AUTHORITY
 HAVING
 JURISDICTION, SHALL BE PROVIDED TO INITIATE A FIRE
 ALARM SIGNAL.
  
 APPENDIX NARATIVE
  
 A.9.6.2.6 THE MANUAL FIRE ALARM BOX REQUIRED BY 9.6.2.6
 IS INTENDED
 TO PROVIDE A MEANS TO MANUALLY ACTIVATE THE FIRE ALARM
 SYSTEM WHEN THE AUTOMATIC FIRE DETECTION SYSTEM OR
 WATERFLOW DEVICES
 ARE OUT OF SERVICE DUE TO MAINTENANCE OR TESTING, OR
 WHERE
 HUMAN DISCOVERY OF THE FIRE PRECEDES AUTOMATIC
 SPRINKLER SYSTEM
 OR AUTOMATIC DETECTION SYSTEM ACTIVATION. WHERE THE
 FIRE ALARM
 SYSTEM IS CONNECTED TO A MONITORING FACILITY, THE
 MANUAL FIRE
 ALARM BOX REQUIRED BY 9.6.2.6 SHOULD BE CONNECTED TO A
 SEPARATE
 CIRCUIT THAT IS NOT PLACED ?ON TEST? WHEN THE DETECTION
 OR SPRINKLER
 SYSTEM IS PLACED ON TEST. THE MANUAL FIRE ALARM BOX
 SHOULD BE
 LOCATED IN AN AREA THAT IS ACCESSIBLE TO OCCUPANTS OF
 THE BUILDING
 AND SHOULD NOT BE LOCKED.
  
 UNLESS THE ONWER IS REQUIRIENG THEM THROUGHTOUT THE
 PREMISIES AS INDICATED, PULL STATIONS MAY BE ELIMINATED
 EXCEPT FOR THE TWO PULL STATIONS ON SHEET FA 06 AT THE
 NORTH/SOUTH 4 DOOR EXITS AND OUTSIDE THE FACP ROOM,
 SHEET FA 03.
  
  
  
 4) THERE ARE INDICATIONS OF SMOKE DETECTION THROUGHOUT
 THE OCCUPANCY. PER NFPA 13, A TOTAL SMOKE DETECTION
 SYSTEM IS NOT REQUIRED AND UNLESS THE SD ARE TIED INTO
 A SMOKE CONTROL/EVACUATION SYSTEM OR MECHANICAL
 SHUTDOWN, THE SD'S IN AREAS WITH SPRINKLERS IS NOT
 REQUIRED.
  
  
 CH 13
  
 13.3.4.2.3* IN ASSEMBLY OCCUPANCIES WITH OCCUPANT LOADS
 OF MORE
 THAN 300, AUTOMATIC DETECTION SHALL BE PROVIDED IN ALL
 HAZARDOUS
 AREAS THAT ARE NOT NORMALLY OCCUPIED, UNLESS SUCH AREAS
 ARE
 PROTECTED THROUGHOUT BY AN APPROVED AUTOMATIC SPRINKLER
 SYSTEM
 IN ACCORDANCE WITH SECTION 9.7
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-07-10 Cont ID  
Sent By lmarchan Date 2020-07-10 Time 13:11 Rev Time 0.00
Received By lmarchan Date 2020-06-24 Time 16:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-06-22 Cont ID  
Sent By jleahy Date 2020-06-22 Time 17:53 Rev Time 0.00
Received By jleahy Date 2020-06-03 Time 09:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-07-14 Cont ID  
Sent By medwards Date 2020-07-10 Time 12:19 Rev Time 0.00
Received By medwards Date 2020-07-14 Time 07:15 Sent To  
Notes
2020-07-14 07:16:46INFORMATION WAS PROVIDED ON 07/13/2020. PROJECT
 APPROVED.
2020-07-10 12:20:282ND REVIEW FBC-2017 MECHANICAL
 PERMIT-20050946
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVE INFORMATION THAT THE DUCT SMOKE
 DETECTORS SPECKED OUT FOR THIS PROJECT ARE APPROVED BY
 UL 268A AND THE SMOKE DETECTORS ARE APPROVED BY UL 268.
 FBC M 606.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-06-17 Cont ID  
Sent By medwards Date 2020-06-17 Time 07:29 Rev Time 0.00
Received By medwards Date 2020-06-17 Time 07:06 Sent To  
Notes
2020-06-17 07:31:24SEE FIRE REVIEWERS COMMENTS: PLEASE PROVIDE SPEC SHEETS
 FOR THE NEW EQUIPMENT.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-07-10 Cont ID  
Sent By medwards Date 2020-07-10 Time 12:28 Rev Time 0.00
Received By medwards Date 2020-07-10 Time 12:20 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-06-17 Cont ID  
Sent By medwards Date 2020-06-17 Time 07:40 Rev Time 0.00
Received By medwards Date 2020-06-17 Time 07:32 Sent To  
Notes
***NONE***