| 2020-06-02 13:18:50 | BUILDING REVIEW COMMENTS: |
| | |
| | W.P.B. PERMIT: 20050937 |
| | REVIEWED: JUNE 2, 2020 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER PX4191 |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK |
| | BELOW) |
| | HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ |
| | BUILDING-PERMIT-FORMS |
| | FBC[B] = FBC BUILDING |
| | FBC[EXISTING] = FBC EXISTING BUILDING |
| | FBC[A] = FBC ACCESSIBILITY |
| | FBC[E] = FBC ENERGY CONSERVATION |
| | |
| | 1) 1816.1 FBC[B] TERMITE PROTECTION. TERMITE PROTECTION |
| | SHALL BE PROVIDED BY REGISTERED TERMITICIDES, INCLUDING |
| | SOIL APPLIED PESTICIDES, BAITING SYSTEMS, AND |
| | PESTICIDES APPLIED TO WOOD, OR OTHER APPROVED METHODS |
| | OF TERMITE PROTECTION LABELED FOR USE AS A PREVENTATIVE |
| | TREATMENT TO NEW CONSTRUCTION. SEE SECTION 202, |
| | ?REGISTERED TERMITICIDE.? UPON COMPLETION OF THE |
| | APPLICATION OF THE TERMITE PROTECTIVE TREATMENT, A |
| | CERTIFICATE OF COMPLIANCE SHALL BE ISSUED TO THE |
| | BUILDING DEPARTMENT BY THE LICENSED PEST CONTROL |
| | COMPANY THAT CONTAINS THE FOLLOWING STATEMENT: ?THE |
| | BUILDING HAS RECEIVED A COMPLETE TREATMENT FOR THE |
| | PREVENTION OF SUBTERRANEAN TERMITES. TREATMENT IS IN |
| | ACCORDANCE WITH RULES AND LAWS ESTABLISHED BY THE |
| | FLORIDA DEPARTMENT OF AGRICULTURE AND CONSUMER |
| | SERVICES.? |
| | - ADD NOTES TO SHOW COMPLIANCE WITH 1816.1 FBC[B] |
| | TERMITE PROTECTION. |
| | |
| | 2) 1203.4 UNDER-FLOOR VENTILATION. THE SPACE BETWEEN |
| | THE BOTTOM OF THE FLOOR JOISTS AND THE EARTH UNDER ANY |
| | BUILDING EXCEPT SPACES OCCUPIED BY BASEMENTS OR CELLARS |
| | SHALL BE PROVIDED WITH VENTILATION OPENINGS THROUGH |
| | FOUNDATION WALLS OR EXTERIOR WALLS. SUCH OPENINGS SHALL |
| | BE PLACED SO AS TO PROVIDE CROSS VENTILATION OF THE |
| | UNDER-FLOOR SPACE. |
| | |
| | 3) 1203.4.1 OPENINGS FOR UNDER-FLOOR VENTILATION. THE |
| | NET AREA OF VENTILATION OPENINGS SHALL BE NOT LESS THAN |
| | 1 SQUARE FOOT FOR EACH 150 SQUARE FEET (0.67 M2 FOR |
| | EACH 100 M2) OF CRAWL-SPACE AREA. VENTILATION OPENINGS |
| | SHALL BE COVERED FOR THEIR HEIGHT AND WIDTH WITH ANY OF |
| | THE FOLLOWING MATERIALS, PROVIDED THAT THE LEAST |
| | DIMENSION OF THE COVERING SHALL BE NOT GREATER THAN 1/4 |
| | INCH (6.4 MM): |
| | - PLEASE PROVIDE THE CALCULATION, SIZE AND AMOUNT OF |
| | VENTS. |
| | |
| | 4) 1609.4.3 FBC(B) EXPOSURE CATEGORIES. THIS SITE WOULD |
| | BE EXPOSURE "C" SINCE IT DOESN?T MEET THE CRITERIA FOR |
| | EXPOSURE B OR D. IF YOU USE A MORE STRINGENT CATEGORY |
| | NOW WE WILL USE IT FOR ALL WINDOW AND DOOR CALCULATIONS |
| | AND A HIGHER PRESUURE THAN NEEDED WILL BE APPLIED. |
| | -PLEASE ADJUST TO CATEGORY C OR STATE THAT YOU WOULD |
| | LIKE TO EXCEED CODE MINIMUM. |
| | |
| | PROVISOS: |
| | DEFERRED SUBMITTALS- |
| | COMPONENT AND CLADDING WITH INTERIOR BUILD-OUT |
| | SEPARATE PERMITS REQUIRED FOR- |
| | INTERIOR BUILD-OUT, LIGHT POLES/SITE LIGHTING, FIRE |
| | ALARM, LOW VOLTAGE, ACCESS, LANDSCAPING, IRRIGATION, |
| | PARKING LOT. |
| | CONSTRUCTION HOURS - 7AM TO 7PM MON-FRI, 8AM TO 8PM |
| | SAT-SUN |
| | - PROVISOS WILL BE ADDED TO THE PLANS PRIOR TO |
| | ISSUANCE. IF YOU SEE SOME THAT DON'T APPLY PLEASE |
| | INDICATE IN YOUR COMMENT RESPONSE AND I WILL ADJUST. |
| | |
| | NOTES: |
| | |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| | [email protected] |
| | |
| | |
| | |