Plan Review Details - Permit 20050899
| Plan Review Stops For Permit 20050899 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2020-08-19 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-08-19 |
Time |
14:16 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-08-19 |
Time |
14:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2020-06-16 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-06-16 |
Time |
10:56 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-06-16 |
Time |
10:37 |
Sent To |
|
|
| Notes |
| 2020-06-16 11:00:48 | PARKING LOT LIGHTING | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PLEASE PROVIDE SIGNED AND SEALED LIGHT POLE DETAILS | | | SHOWING ATTACHMENT TO FOUNDATION AND THE WIND DESIGN | | | PARAMETERS USED TO COMPLY WITH FBC 1609. SIGNED AND | | | SEALED DOCUMENTS OR DRAWINGS NEED TO BE ELECTRONICALLY | | | SIGNED AND SEALED TO BE USED IN ELECTRONIC PLAN REVIEW. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2020-09-10 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-09-10 |
Time |
08:15 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-09-10 |
Time |
08:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2020-08-12 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2020-08-12 |
Time |
22:13 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2020-08-12 |
Time |
21:21 |
Sent To |
|
|
| Notes |
| 2020-08-12 22:13:54 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. VALUE STILL LOW. PROVIDE SIGNED CONTRACT BY BOTH | | | OWNER AND CONTRACTOR TO INCLUDE ALL MATERIALS AND | | | LABOR. FBC 109.3 | | | | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | CODES IN EFFECT: | | | | | | IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN | | | PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE | | | 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A | | | COMPLETED RESUBMITTAL FORM, VIA EMAIL TO | | | [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT | | | NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE | | | RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: | | | | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | | UILDING-PERMIT-FORMS | | | | | | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2017 6TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | FRANK GIAQUINTO III | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | [email protected] | | | CELL: 561-657-1653 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2020-06-12 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-06-12 |
Time |
13:50 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-06-12 |
Time |
13:31 |
Sent To |
|
|
| Notes |
| 2020-06-12 13:54:13 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | | 5TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, | | | PART VIII ELECTRICAL | | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) VALUE FOR PERMIT SHOWN IS LOW FOR THIS TYPE OF | | | INSTALLATION. (11,000) LABOR AND MATERIALS? | | | | | | 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF | | | THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF | | | BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS, | | | MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE | | | UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE | | | DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED, | | | QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS | | | (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE | | | BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION | | | OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT | | | VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, | | | MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK, | | | ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS, | | | OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. | | | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED | | | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES | | | (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY | | | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT | | | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. | | | | | | 2) PLEASE INDICATE NUMBER OF EACH FIXTURE BEING USED | | | AND WHICH POLE FOR WHICH FIXTURES. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2020-09-10 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-09-10 |
Time |
08:15 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-08-28 |
Time |
13:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2020-08-19 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-08-19 |
Time |
14:17 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-07-27 |
Time |
10:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2020-06-17 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2020-06-17 |
Time |
09:46 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2020-05-28 |
Time |
14:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2020-08-19 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-08-19 |
Time |
14:16 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-08-19 |
Time |
14:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2020-06-16 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-06-16 |
Time |
11:00 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-06-16 |
Time |
11:00 |
Sent To |
|
|
| Notes |
| 2020-06-16 11:01:18 | SEE BUILDING PLAN REVIEW |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2020-08-17 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2020-08-17 |
Time |
16:51 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2020-08-17 |
Time |
16:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2020-06-17 |
|
|
Cont ID |
|
| Sent By |
avann |
Date |
2020-06-17 |
Time |
09:46 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2020-06-17 |
Time |
09:46 |
Sent To |
|
|
| Notes |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |