Plan Review Details - Permit 20050834
Plan Review Stops For Permit 20050834
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status N Date 2020-06-16 Cont ID  
Sent By jwitmer Date 2020-06-16 Time 11:00 Rev Time 0.00
Received By jwitmer Date 2020-06-16 Time 10:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-08-10 Cont ID  
Sent By jwitmer Date 2020-08-10 Time 07:58 Rev Time 0.00
Received By jwitmer Date 2020-08-10 Time 07:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-07-24 Cont ID  
Sent By jwitmer Date 2020-07-24 Time 15:58 Rev Time 0.00
Received By jwitmer Date 2020-07-24 Time 15:45 Sent To  
Notes
2020-07-24 15:58:41PLANS WILL BE STAMPED APPROVED ONCE THERE IS A DIGITAL
 SIGNATURE FOR EACH PAGE OF PLANS.
 ARCHITECT DIGITAL SIGNING & SEALING PLANS. 61G1-16.005
 PROCEDURES FOR DIGITALLY SIGNING AND SEALING AND FOR
 ELECTRONICALLY TRANSMITTING PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS.
 (1) INFORMATION STORED IN ELECTRONIC FILES REPRESENTING
 PLANS, SPECIFICATIONS, PLATS, REPORTS, OR OTHER
 DOCUMENTS WHICH MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 481, F.S., SHALL BE SIGNED, DATED AND SEALED BY
 THE ARCHITECT OR INTERIOR DESIGNER IN RESPONSIBLE
 CHARGE.
 (A) A SCANNED IMAGE OF AN ORIGINAL SIGNATURE SHALL NOT
 BE USED IN LIEU OF A DIGITAL OR ELECTRONIC SIGNATURE.
 (B) THE DATE THAT THE ELECTRONIC SIGNATURE FILE WAS
 CREATED OR THE DIGITAL SIGNATURE WAS PLACED INTO THE
 DOCUMENT MUST APPEAR ON THE DOCUMENT IN THE SAME MANNER
 AS DATE IS REQUIRED TO BE APPLIED WHEN A LICENSEE USES
 THE MANUAL SEALING PROCEDURE SET OUT IN RULE
 61G1-16.003, F.A.C.
 (2) AN ARCHITECT OR INTERIOR DESIGNER UTILIZING A
 DIGITAL SIGNATURE TO SEAL CONSTRUCTION DOCUMENTS SHALL
 ASSURE THAT THE DIGITAL SIGNATURE IS:
 (A) UNIQUE TO THE PERSON USING IT;
 (B) CAPABLE OF VERIFICATION;
 (C) UNDER THE SOLE CONTROL OF THE PERSON USING IT; AND
 (D) LINKED TO A DOCUMENT IN SUCH A MANNER THAT THE
 ELECTRONIC SIGNATURE IS INVALIDATED IF ANY DATA IN THE
 DOCUMENT ARE CHANGED.
 (3) EACH ELECTRONICALLY SIGNED FILE SHALL HAVE AN
 AUTHENTICATION CODE DEFINED AS A MESSAGE DIGEST
 DESCRIBED IN FEDERAL INFORMATION PROCESSING STANDARD
 PUBLICATION 180-4 ?SECURE HASH STANDARD,? MARCH 2012,
 WHICH IS HEREBY ADOPTED AND INCORPORATED BY REFERENCE
 BY THE BOARD AND CAN BE OBTAINED FROM HTTP://WWW.FLRULE
 S.ORG/GATEWAY/REFERENCE.ASP?NO=REF-01340 OR THE
 INTERNET WEBSITE: HTTP://CSRC.NIST.GOV/PUBLICATIONS/FIP
 S/FIPS180-4/FIPS-180-4.PDF.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-06-16 Cont ID  
Sent By jwitmer Date 2020-06-16 Time 11:01 Rev Time 0.00
Received By jwitmer Date 2020-06-16 Time 10:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-08-11 Cont ID  
Sent By jleahy Date 2020-08-11 Time 12:49 Rev Time 0.00
Received By jleahy Date 2020-08-10 Time 17:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-08-02 Cont ID  
Sent By jleahy Date 2020-08-02 Time 14:32 Rev Time 0.00
Received By jleahy Date 2020-08-02 Time 14:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-07-02 Cont ID  
Sent By jleahy Date 2020-07-02 Time 15:01 Rev Time 0.00
Received By jleahy Date 2020-07-02 Time 15:01 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2020-08-05 Cont ID  
Sent By pleduc Date 2020-08-05 Time   Rev Time 0.00
Received By pleduc Date 2020-08-05 Time 10:00 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-07-22 Cont ID  
Sent By pleduc Date 2020-07-22 Time   Rev Time 0.00
Received By pleduc Date 2020-07-22 Time 10:34 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-06-01 Cont ID  
Sent By fstal Date 2020-06-01 Time   Rev Time  
Received By fstal Date 2020-06-01 Time   Sent To  
Notes
2020-06-01 17:15:32DIGITAL FIRE REVIEW PASS.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-08-11 Cont ID  
Sent By jleahy Date 2020-08-11 Time 12:49 Rev Time 0.00
Received By jleahy Date 2020-08-04 Time 11:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-08-03 Cont ID  
Sent By lmarchan Date 2020-08-03 Time 14:22 Rev Time 0.00
Received By lmarchan Date 2020-07-21 Time 15:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-07-07 Cont ID  
Sent By lmarchan Date 2020-07-07 Time 10:50 Rev Time 0.00
Received By lmarchan Date 2020-05-29 Time 09:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2020-08-08 Cont ID  
Sent By medwards Date 2020-08-08 Time 08:26 Rev Time 0.00
Received By medwards Date 2020-08-08 Time 08:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-07-30 Cont ID  
Sent By medwards Date 2020-07-30 Time 16:22 Rev Time 0.00
Received By medwards Date 2020-07-30 Time 10:42 Sent To  
Notes
2020-07-30 10:45:00ACCORDING TO SCOPE OF WORK THE ONLY MECHANICAL WORK
 INCLUDED IN THIS PROJECT IS FURNISHING AND INSTALLATION
 OF PANASONIC BATH EXHAUST FANS.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-07-07 Cont ID  
Sent By medwards Date 2020-07-07 Time 10:38 Rev Time 0.00
Received By medwards Date 2020-07-07 Time 09:52 Sent To  
Notes
2020-07-07 10:39:35PLEASE PROVIDE MECHANICAL DEMO AND NEW WORK DRAWINGS.
 COULD NOT DO A REVIEW AT THIS TIME. FBC FS 107.2.1
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2020-08-05 Cont ID  
Sent By lcrespo Date 2020-08-05 Time 09:27 Rev Time 0.00
Received By lcrespo Date 2020-08-05 Time 09:27 Sent To  
Notes
2020-08-05 09:28:1808/05/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL,
 CONTRACTORS OR THEIR REPRESENTATIVES FROM THE
 RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEW
 AVAILABLE FROM 6:30 AM TO 7:30 / 2:00 PM TO 5:00 PM
 EMAIL: [email protected] CELL: 561-701-6437
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-08-03 Cont ID  
Sent By lcrespo Date 2020-08-03 Time 13:50 Rev Time 0.00
Received By lcrespo Date 2020-08-03 Time 13:50 Sent To  
Notes
2020-08-03 13:50:3708/03/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL,
 CONTRACTORS OR THEIR REPRESENTATIVES FROM THE
 RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEW
 AVAILABLE FROM 6:30 AM TO 7:30 / 2:00 PM TO 5:00 PM
 EMAIL: [email protected] CELL: 561-701-6437
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-07-02 Cont ID  
Sent By tklarge Date 2020-07-02 Time 14:36 Rev Time 0.00
Received By tklarge Date 2020-07-01 Time 10:35 Sent To  
Notes
2020-07-02 14:36:491) NONE OF THE PLUMBING FIXTURES IN BATH #2 CAN BE
 REMOVED. THIS BATHROOM HAS BEEN DESIGNED TO COMPLY WITH
 THE FEDRAL FAIR HOUSING ACT AND FLORIDA FAIR HOUSING
 ACT DESIGN REQUIREMENTS FOR A SPECIFICATION "B"
 BATHROOM WHEN THE BUILDING WAS ORIGINALLY CONSTRUCTED.
 REVISE THE PLANS TO SHOW THE PLUMBING TO REMAIN AS IS
 WITH NO CHANGES.
 2) SUBMIT A SANITARY AND WATER RISER DIAGRAM FOR
 CHANGES BEING MADE TO THE PLUMBING SYSTEM. WPB AMEND.
 TO FBC SEC. 107.3.5.1.3.
 3) NEW SHOWER VALVE SHALL COMPLY WITH FBC-PLUMBING
 SEC.424.3.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-08-10 Cont ID  
Sent By jwitmer Date 2020-08-10 Time 07:58 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-07-24 Cont ID  
Sent By jwitmer Date 2020-07-24 Time 15:56 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2020-07-24 15:56:14ARCHITECT DIGITAL SIGNING & SEALING PLANS. 61G1-16.005
 PROCEDURES FOR DIGITALLY SIGNING AND SEALING AND FOR
 ELECTRONICALLY TRANSMITTING PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS.
 (1) INFORMATION STORED IN ELECTRONIC FILES REPRESENTING
 PLANS, SPECIFICATIONS, PLATS, REPORTS, OR OTHER
 DOCUMENTS WHICH MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 481, F.S., SHALL BE SIGNED, DATED AND SEALED BY
 THE ARCHITECT OR INTERIOR DESIGNER IN RESPONSIBLE
 CHARGE.
 (A) A SCANNED IMAGE OF AN ORIGINAL SIGNATURE SHALL NOT
 BE USED IN LIEU OF A DIGITAL OR ELECTRONIC SIGNATURE.
 (B) THE DATE THAT THE ELECTRONIC SIGNATURE FILE WAS
 CREATED OR THE DIGITAL SIGNATURE WAS PLACED INTO THE
 DOCUMENT MUST APPEAR ON THE DOCUMENT IN THE SAME MANNER
 AS DATE IS REQUIRED TO BE APPLIED WHEN A LICENSEE USES
 THE MANUAL SEALING PROCEDURE SET OUT IN RULE
 61G1-16.003, F.A.C.
 (2) AN ARCHITECT OR INTERIOR DESIGNER UTILIZING A
 DIGITAL SIGNATURE TO SEAL CONSTRUCTION DOCUMENTS SHALL
 ASSURE THAT THE DIGITAL SIGNATURE IS:
 (A) UNIQUE TO THE PERSON USING IT;
 (B) CAPABLE OF VERIFICATION;
 (C) UNDER THE SOLE CONTROL OF THE PERSON USING IT; AND
 (D) LINKED TO A DOCUMENT IN SUCH A MANNER THAT THE
 ELECTRONIC SIGNATURE IS INVALIDATED IF ANY DATA IN THE
 DOCUMENT ARE CHANGED.
 (3) EACH ELECTRONICALLY SIGNED FILE SHALL HAVE AN
 AUTHENTICATION CODE DEFINED AS A MESSAGE DIGEST
 DESCRIBED IN FEDERAL INFORMATION PROCESSING STANDARD
 PUBLICATION 180-4 ?SECURE HASH STANDARD,? MARCH 2012,
 WHICH IS HEREBY ADOPTED AND INCORPORATED BY REFERENCE
 BY THE BOARD AND CAN BE OBTAINED FROM HTTP://WWW.FLRULE
 S.ORG/GATEWAY/REFERENCE.ASP?NO=REF-01340 OR THE
 INTERNET WEBSITE: HTTP://CSRC.NIST.GOV/PUBLICATIONS/FIP
 S/FIPS180-4/FIPS-180-4.PDF.
  
 J. WITMER 7/24/2020

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-07-07 Cont ID  
Sent By medwards Date 2020-07-07 Time 10:46 Rev Time 0.00
Received By medwards Date 2020-07-07 Time 10:39 Sent To  
Notes
2020-07-07 10:48:23ALL SHEETS IN TIS PACKAGE NEED TO BE DIGITALLY SIGNED
 AND SEAL BY THE DESIGNER. FS 471.025
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  