Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-12-10 Cont ID  
Sent By pvalenti Date 2020-12-10 Time 09:12 Rev Time 0.00
Received By pvalenti Date 2020-12-10 Time 09:12 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-08-21 Cont ID  
Sent By rmcphers Date 2020-08-21 Time 09:05 Rev Time 0.00
Received By rmcphers Date 2020-08-21 Time 09:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-07-22 Cont ID  
Sent By rmcphers Date 2020-07-22 Time 08:32 Rev Time 0.00
Received By rmcphers Date 2020-07-22 Time 08:10 Sent To  
Notes
2020-07-22 08:31:55MINI SPLIT AC
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SEPARATE EACH DRAWING OR DOCUMENT IN
 PROJECTDOX TO STAND ALONE IN ITS OWN FOLDER. YOU HAVE
 GARAGE DOOR SPECS. WHICH SHOULD NOT BE IN THE FOLDER AT
 ALL.
 2) THE ENGINEERING FOR THE AC STAND STATES THAT YOU
 NEED A SEPARATE SIGNED AND SEALED SITE SPECIFIC DESIGN
 PRESSURE CALCULATIONS (SEE "DESIGN NOTES ON THE
 PROVIDED ENGINEERING) FROM AN ARCHITECT OR ENGINEER AND
 A SIGNED AND SEALED DRAWING SHOWING THE SIZE OF THE
 UNIT TO MEET WHAT THE STAND IS INTENDED FOR (SEE
 GENERAL NOTE NUMBER 4 ON THE PROVIDED ENGINEERING). FBC
 1609
  
 FYI = SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO
 BE DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL
 SIGNATURE - PLEASE DROP OFF (CITY HALL DROP BOX) THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS ALONG
 WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE REASON
 FOR SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN REVIEW
 REQUEST FORM CAN BE OBTAINED BY E MAILING [email protected]
 AND ASKING FOR THE FORM. (AT THIS TIME DROP BOX ITEMS
 MAY TAKE 2 TO 3 WEEKS TO PROCESS, TO SEND TO PLAN
 REVIEW - DUE TO LIMITED STAFF INSIDE THE BUILDING
 DEPT.)
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-12-10 Cont ID  
Sent By pvalenti Date 2020-12-10 Time 09:12 Rev Time 0.00
Received By pvalenti Date 2020-12-09 Time 16:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-08-21 Cont ID  
Sent By rmcphers Date 2020-08-21 Time 09:22 Rev Time 0.00
Received By rmcphers Date 2020-08-06 Time 16:49 Sent To  
Notes
2020-08-10 16:50:5208/10/2020 UPLOADED TO PROJECTDOX INFORMATION THAT WAS
 RESUBMITTED BY THE CONTRACTOR VIA DROP BOX. BASICALLY
 IT WAS THE SAME THAT WAS ORIGINALLY SUBMITTED. I JUST
 UPLOADED EACH DOCUMENT INDIVIDUALLY. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-07-22 Cont ID  
Sent By rmcphers Date 2020-07-22 Time 08:33 Rev Time 0.00
Received By rmcphers Date 2020-06-08 Time 10:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2020-12-10 Cont ID  
Sent By hmoser Date 2020-12-10 Time 09:11 Rev Time 0.00
Received By hmoser Date 2020-12-10 Time 09:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-08-12 Cont ID  
Sent By medwards Date 2020-08-12 Time 07:33 Rev Time 0.00
Received By medwards Date 2020-08-12 Time 07:22 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-07-16 Cont ID  
Sent By medwards Date 2020-07-16 Time 08:03 Rev Time 0.00
Received By medwards Date 2020-07-16 Time 07:12 Sent To  
Notes
2020-07-16 08:03:571ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20050832
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS M1.1 ARE VERY BLURRY AND NOT READABLE PLEASE
 UPLOAD A CLEAR READABLE SHEET.
  
 2) THIS PROJECT MUST HAVE A BUILDING PERMIT WITH A
 BUILDING REVIEW AND INSPECTIONS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-12-10 Cont ID  
Sent By hmoser Date 2020-12-10 Time 09:11 Rev Time 0.00
Received By hmoser Date 2020-12-10 Time 09:03 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-08-12 Cont ID  
Sent By medwards Date 2020-08-12 Time 07:35 Rev Time 0.00
Received By medwards Date 2020-08-12 Time 07:35 Sent To  
Notes
2020-08-12 07:34:48THE BRACKET STAND DRAWINGS MUST HAVE THE ORIGINAL
 DESIGNERS DIGITAL SIGNATURE AND STAMP.
2020-08-11 07:42:28PLEASE SEE 1 ST CYCLE SIGNATURE REVIEW COMMENTS.
 DESIGNER OF DRAWINGS MUST PRINT AND SIGN THEIR NAME ON
 THE DRAWINGS.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
2020-08-10 16:54:1708/10/2020 UPLOADED TO PROJECTDOX INFORMATION THAT WAS
 RESUBMITTED BY THE CONTRACTOR VIA DROP BOX. BASICALLY
 IT WAS THE SAME THAT WAS ORIGINALLY SUBMITTED. I JUST
 UPLOADED EACH DOCUMENT INDIVIDUALLY. JG.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-07-16 Cont ID  
Sent By medwards Date 2020-07-16 Time 08:04 Rev Time 0.00
Received By medwards Date 2020-07-16 Time 08:04 Sent To  
Notes
2020-07-16 08:05:26DESIGNER MUST SIGN AND SEAL THE DRAWINGS. FBC FS
 471.025
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728