Plan Review Details - Permit 20050830
Plan Review Stops For Permit 20050830
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-09-28 Cont ID  
Sent By jgomez Date 2020-09-28 Time 13:24 Rev Time 0.00
Received By jgomez Date 2020-09-28 Time 11:05 Sent To  
Notes
2020-09-28 13:18:54BUILDING REVIEW APPROVED WITH PROVISO:
  
 1-PROVIDE EXTERIOR DOORS PRODUCT APPROVAL FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-08-24 Cont ID  
Sent By jgomez Date 2020-08-24 Time 17:05 Rev Time 0.00
Received By jgomez Date 2020-08-24 Time 17:05 Sent To  
Notes
2020-08-24 17:40:26RESIDENTIAL (R3) SECOND BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- PLANS SUBMITTED NOW NEED TO HAVE THE NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN AS
 REQUIRED BY-SEC. 107.2.1 CITY AMENDMENTS.
  
 2- OK.
  
 3- PROVIDE COMPLETE FRAMING DETAIL/SPECIFICATIONS FOR
 THE DOUBLE DOOR. SPECIFY ALL FRAMING MEMBERS AND ALL
 CONNECTORS. SEC. R301.2.1 FBC-RESIDENTIAL AND SEC.
 107.3.5.3 CITY AMENDMENTS.
  
 RESPONSE:
 NO DETAIL WAS PROVIDED. NOTE: THIS DETAIL IS IMPORTANT
 BECAUSE THE DOUBLE DOORS ARE GOING TO BE RESTING ON
 THIS FRAME IN ORDER TO RESIST THE WIND LOADS.
 COORDINATE WITH COMMENT #6 BELOW REGARDING THE DOORS
 DETAILS.
  
 4- WALL SECTION ON SHEET 2.0:
 A) OK
  
 B) CONNECTOR TP6X SPECIFIED TO CONNECT THE 2X4 STUDS AT
 TOP AND BOTTOM IS NOT CLEAR. PROVIDE CLEAR
 SPECIFICATIONS OF THE STRUCTURAL CONNECTOR. SPECIFY
 MANUFACTURER AND SPECIFIC PUBLISHED CONNECTOR. SEC.
 R301.2.1 FBC-RESIDENTIAL AND SEC. 107.2.1 CITY
 AMENDMENTS.
  
 RESPONSE:
 CONNECTOR WAS REMOVED. NOW THERE ARE NO SPECIFICATIONS
 FOR THE ATTACHMENT OF THE STUDS AT TOP AND BOTTOM.
 PROVIDE INFORMATION.
  
 C) OK.
  
 5- OK
  
 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) DOUBLE DOORS AS SHOWN ON PLANS.
  
 RESPONSE:
 (PLYWOOD DOORS OK PER ROBERT BROWN. E-MAIL DATED
 06/23/2020 IF COMPLETE INFORMATION IS PROVIDED).
 DOOR DETAIL ON SHEET 2.0 WAS REVIEWED WITH ROBERT BROWN
 AND IS MISSING THE FOLLOWING INFORMATION (SEC. 107.2.1
 CITY AMENDMENTS):
 (A) NEED TO SPECIFY TYPE OF PLYWOOD TO BE USED TO AVOID
 DECAY WHEN EXPOSED TO THE WEATHER.
 (B) NEED TO PROVIDE DETAILS SHOWING HOW ARE THE PLYWOOD
 EDGES PROTECTED TO AVOID DELAMINATING AND DECAYING.
 SEC. R317.1 FBC-RESIDENTIAL.
 (C) NEED TO SPECIFY DOORS LOCKING AND LATCHING
 HARDWARE.
  
  
 B) OK
  
 7-OK
  
 8- OK.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-06-11 Cont ID  
Sent By jgomez Date 2020-06-11 Time 12:13 Rev Time 0.00
Received By jgomez Date 2020-06-11 Time 10:34 Sent To  
Notes
2020-06-11 12:14:43RESIDENTIAL (R3) BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- PLANS SUBMITTED HAVE A PRINT OF THE ARCHITECT'S
 DIGITAL SIGNATURE. NEED ORIGINAL SIGNATURE. PROVIDE
 PLANS WITH ORIGINAL SEAL AND SIGNATURE OR ARCHITECT TO
 SUBMIT PLANS ELECTRONICALLY WITH DIGITAL SIGNATURE AS
 REQUIRED BY 61G1-16.005 FAC.
  
 ARCHITECTS
 61G1-16.005 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING AND FOR ELECTRONICALLY TRANSMITTING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 2- PROVIDE ROOF FRAMING PLAN. SPECIFY ALL ROOFING
 MEMBERS SIZES, SPACING AND CONNECTORS. SEC. R301.2.1
 FBC-RESIDENTIAL AND SEC. 107.3.5.3 CITY AMENDMENTS.
  
 3- PROVIDE COMPLETE FRAMING DETAIL/SPECIFICATIONS FOR
 THE DOUBLE DOOR. SPECIFY ALL FRAMING MEMBERS AND ALL
 CONNECTORS. SEC. R301.2.1 FBC-RESIDENTIAL AND SEC.
 107.3.5.3 CITY AMENDMENTS.
  
 4- WALL SECTION ON SHEET 2.0:
 A)PROVIDE DETAIL/SPECS FOR THE DRIP EDGE AS REQUIRED BY
 SEC. R905.2.8.5 FBC-RESIDENTIAL.
  
 B) CONNECTOR TP6X SPECIFIED TO CONNECT THE 2X4 STUDS AT
 TOP AND BOTTOM IS NOT CLEAR. PROVIDE CLEAR
 SPECIFICATIONS OF THE STRUCTURAL CONNECTOR. SPECIFY
 MANUFACTURER AND SPECIFIC PUBLISHED CONNECTOR. SEC.
 R301.2.1 FBC-RESIDENTIAL AND SEC. 107.2.1 CITY
 AMENDMENTS.
  
 C)SPECIFY HOW MUCH EMBEDMENT IS REQUIRED FOR THE 3/8"
 ZINC PLATED WEDGE ANCHORS SPECIFIED IN THE WALL SECTION
 TO FASTEN THE 2X4 BOTTOM PLATE.
 SEC. R301.2.1 FBC-RESIDENTIAL AND SEC. 107.3.5.3 CITY
 AMENDMENTS.
  
 5- PLANS SPECIFY 3:12 ROOF PITCH. NEED TO SPECIFY TWO
 LAYERS OF UNDERLAYMENT AS REQUIRED BY SEC. R905.2.2
 FBC-RESIDENTIAL.
  
 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) DOUBLE DOORS AS SHOWN ON PLANS. (OK PER ROBERT
 BROWN. E-MAIL DATED 06/23/2020)
  
 B) ROOF SHINGLES.
  
 7-DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 8- VALUATION DECLARED IN THE PERMIT APPLICATION IS LOW.
 VALUATION TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S
 OVERHEAD AND PROFIT AND DESIGN PROFESSIONAL FEES AS
 REQUIRED BY SEC. 109.3 CITY AMENDMENTS. UPDATE
 VALUATION TO INCLUDE ALL COSTS OR PROVIDE COPY OF
 SIGNED CONTRACTS INCLUDING DESIGN PROFESSIONAL FEES.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By kalexand Date 2020-09-30 Time 13:58 Rev Time 0.00
Received By lmarchan Date 2020-09-25 Time 14:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-08-24 Cont ID  
Sent By jgomez Date 2020-08-24 Time 17:40 Rev Time 0.00
Received By jgomez Date 2020-07-18 Time 15:31 Sent To I
Notes
2020-07-18 09:07:14ROUTED TO ZONING BIN

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-06-11 Cont ID  
Sent By jgomez Date 2020-06-11 Time 12:14 Rev Time 0.00
Received By jgomez Date 2020-05-30 Time 08:22 Sent To I
Notes
2020-06-10 14:56:38ROUTED TO BLDG <$5K
2020-05-30 08:23:00ROUTED TO ZONING BIN

Review Stop Z ZONING
Rev No 3 Status P Date 2020-09-30 Cont ID  
Sent By kalexand Date 2020-09-30 Time 13:56 Rev Time 0.00
Received By kalexand Date 2020-09-30 Time 13:56 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2020-08-11 Cont ID  
Sent By kalexand Date 2020-08-11 Time 16:42 Rev Time 0.00
Received By kalexand Date 2020-08-11 Time 16:42 Sent To I
Notes
2020-08-11 16:59:14ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW:
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. OVERHANG PROJECTS TOO FAR INTO SETBACK; SHOULD BE
 2.9 FT. FROM PROPERTY LINE.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD
 LIKE TO RESUBMIT ELECTRONICALLY, EMAIL
 [email protected] AND REQUEST TO HAVE YOUR
 PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOG
 IN INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL.
 PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU
 ARE FINISHED UPLOADING.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 KIZZI ALEXANDRE, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1442
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By kalexand Date 2020-06-05 Time   Rev Time  
Received By   Date 2020-06-05 Time   Sent To I
Notes
2020-06-05 09:13:30ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 6/5/20
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. SHED OVERHANG ENCHROACHES TOO FAR INTO REQUIRED
 SETBACK. PER SEC 94 305(B)(2) OVERHANGS SHALL NOT
 EXTEND FARTHER THAN 3FT INTO REQUIRED STEBACKS.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 IF THE FORM IS TEMPORARILY UNAVAILABLE, PLEASE REQUEST
 THAT IT BE SENT TO YOU BY EMAILING [email protected]
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 KIZZI ALEXANDRE, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1442
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved