Plan Review Details - Permit 20050798
Plan Review Stops For Permit 20050798
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-06-11 Cont ID  
Sent By ppetty Date 2020-06-11 Time 08:13 Rev Time 0.00
Received By ppetty Date 2020-06-11 Time 08:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-06-05 Cont ID  
Sent By ppetty Date 2020-06-05 Time 10:20 Rev Time 0.00
Received By ppetty Date 2020-06-05 Time 10:20 Sent To  
Notes
2020-06-05 10:21:24PLEASE SEE F/D NOTE

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-06-10 Cont ID  
Sent By pleduc Date 2020-06-10 Time   Rev Time 0.00
Received By pleduc Date 2020-06-10 Time 15:12 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-06-01 Cont ID  
Sent By pleduc Date 2020-06-01 Time   Rev Time 0.00
Received By pleduc Date 2020-06-01 Time 09:53 Sent To  
Notes
2020-06-01 09:53:47THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
  
 1) THE SUBMITTED PALN DOES NOT INDICATE SMOKE
 ALARMS(SA) OUTSIDE OF THE SLEEPING AREAS OF THE TWO
 BEDROOMS.
  
 PER NFPA 101, CH 32 NEW RESIDENTIAL BOARD AND CARE
 OCCUPANCIES
  
 32.3.3.4.7 SMOKE ALARMS. APPROVED SMOKE ALARMS SHALL BE
 INSTALLED IN ACCORDANCE WITH 9.6.2.10 INSIDE EVERY
 SLEEPING ROOM,
 OUTSIDE EVERY SLEEPING AREA IN THE IMMEDIATE VICINITY
 OF THE
 BEDROOMS, AND ON ALL LEVELS WITHIN A RESIDENT UNIT.
  
 PLEASE REVIEW AND CORRECT OF JUSTIFY WITH SPECIFIC
 INFORMATION AND CODE REFERENCES.
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-06-11 Cont ID  
Sent By ppetty Date 2020-06-11 Time 08:13 Rev Time 0.00
Received By ppetty Date 2020-06-10 Time 14:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-06-05 Cont ID  
Sent By ppetty Date 2020-06-05 Time 10:26 Rev Time 0.00
Received By ppetty Date 2020-05-29 Time 11:17 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2020-06-11 Cont ID  
Sent By ppetty Date 2020-06-11 Time 08:13 Rev Time 0.00
Received By ppetty Date 2020-06-11 Time 08:14 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2020-06-05 Cont ID  
Sent By ppetty Date 2020-06-05 Time 10:26 Rev Time 0.00
Received By ppetty Date 2020-06-05 Time 10:26 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved