Plan Review Details - Permit 20050766
Plan Review Stops For Permit 20050766
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2020-07-30 Cont ID  
Sent By shill Date 2020-07-30 Time 12:28 Rev Time 0.00
Received By shill Date 2020-07-30 Time 12:28 Sent To  
Notes
2020-07-30 12:28:36PROVISO: CONTRACTOR TO PROVIDE LETTER

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-06-09 Cont ID  
Sent By pvalenti Date 2020-06-09 Time 07:54 Rev Time 0.00
Received By pvalenti Date 2020-06-08 Time 10:55 Sent To  
Notes
2020-06-09 07:56:18 
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 ASBESTOS REVIEW DENIED:
  
 ASBESTOS REQUIREMENTS:
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-07-20 Cont ID  
Sent By pvalenti Date 2020-07-20 Time 11:45 Rev Time 0.00
Received By pvalenti Date 2020-07-20 Time 11:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-06-09 Cont ID  
Sent By pvalenti Date 2020-06-09 Time 15:48 Rev Time 0.00
Received By pvalenti Date 2020-06-08 Time 10:54 Sent To  
Notes
2020-06-09 16:18:30PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 BUILDING REVIEW DENIED:
  
 FBC B 107.2.1, ON PAGE A0.01, ADD THE SECTION FROM THE
 EXISTING BUILDING CODE THAT YOU ARE REFERENCING
 (EXAMPLE: ALTERATION LEVEL 1, 2, OR 3).
 THIS WILL HELP TO ADDRESS CONCERNS OF POTENTIAL CODE
 VIOLATIONS SUCH AS: FBC B 1016.2 EGRESS THROUGH
 INTERVENING SPACES.
  
 FBC B 107, PLEASE ADDRESS THE CONCERN OF ELEVATOR
 LOBBIES IN EXISTING HIGH RISE CONSTRUCTION AS IT
 APPEARS THAT A DOOR MAY BE REQUIRED SEPARATING THE
 CENTER CORRIDOR FROM THE ELEVATOR LOBBY.
 (THIS ISSUE HAS COME UP UNDER PRIOR PERMITS FROM OTHER
 FLOORS WITHIN THIS BUILDING, PER CHIEF PLANS EXAMINER
 S. HILL)
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-07-17 Cont ID  
Sent By jleahy Date 2020-07-17 Time 08:02 Rev Time 0.00
Received By jleahy Date 2020-07-16 Time 16:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-06-05 Cont ID  
Sent By jleahy Date 2020-06-05 Time 17:09 Rev Time 0.00
Received By jleahy Date 2020-06-05 Time 16:59 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-07-16 Cont ID  
Sent By pleduc Date 2020-07-16 Time   Rev Time 0.00
Received By pleduc Date 2020-07-16 Time 11:20 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-05-29 Cont ID  
Sent By pleduc Date 2020-05-29 Time   Rev Time 0.00
Received By pleduc Date 2020-05-29 Time 10:56 Sent To  
Notes
2020-05-29 11:13:50THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET A 1.11 - WITHIN THE LAB ROOM THERE ARE TWO
 HOODS INDICATED THAT ARE NOT ON THE MECHANICAL PLAN
 SHEETS.
  
 WHAT IS THE FUNCTION OF THESE HOODS AND DO THEY HAVE
 ANY VENTING/EXHAUSTED RELEATED FEATURES TO THEM?
  
 PLEASE PROVIDE DETAILS/SPEC SHEETS AND ADD THEM TO THE
 MECHANICAL PLANS IF APPLICABLE.
  
  
  
 2) SHEET AO.14 - WITHIN THE DOOR SCHEDULE UNDER
 HARDWARE GROUP THERE ARE INDICATIONS OF TBD & N/A.
  
 ON REVIEW OF THE BACK UP INFORMATION LABORATORY SUMMARY
 THERE IS INDICATIONS OF: "LABORATORY FACILITIES
 (SECONDARY BARRIERS) # 1 LABORATORY DOORS SHOULD BE
 SELF-CLOSING AND HAVE LOCKS IN ACCORDANCE WITH THE
 COMPNAY PLOICIES."
  
 THERE ARE NO INDICATIONS OF SELF-CLOSERS WITHIN THE
 DOOR SCHEDULE.
  
 THERE ARE NO INDICATIONS OF DOO & LOCKS/LATCHING
 HARDWARE.
  
 PER NFPA 101 CH 7, MEANS OF EGRESS
  
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM
 THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED.
 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY
 TO DOOR
 LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER EXPOSURE TO
 ELEVATED
 TEMPERATURE IN ACCORDANCE WITH THE LISTING, BASED ON
 LABORATORY
 FIRE TEST PROCEDURES.
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A
 TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM
 THE EGRESS
 SIDE.
  
 PLEASE ENSURE COMPLIANCE.
  
  
  
 3) ELECTRICAL SHEETS - FOR INFOMATIONAL PURPOSES ONLY
  
 THERE ARE NO INDICATIONS OF ACCESS CONTROL WITHIN THE
 PORJECT.
  
 SHOULD ACCESS CONTROL BE CONSIDERED, IT SHALL BE
 SUBMITTED UNDER SEPARATE PERMIT AND SHOP DRAWINGS.
  
 PROVIDE AND APPLICABLE NOTE OF ACKNOWLEDGEMENT.
  
 PLEASE ENSURE COMPLINACE IF PROPOSED.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-07-21 Cont ID  
Sent By jesmith Date 2020-07-21 Time 11:16 Rev Time 0.00
Received By jesmith Date 2020-07-21 Time 11:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-06-11 Cont ID  
Sent By lmarchan Date 2020-06-11 Time 08:10 Rev Time 0.00
Received By lmarchan Date 2020-05-28 Time 13:43 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2020-06-09 Cont ID  
Sent By pvalenti Date 2020-06-09 Time 08:07 Rev Time 0.00
Received By pvalenti Date 2020-06-08 Time 10:54 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-07-18 Cont ID  
Sent By medwards Date 2020-07-18 Time 14:30 Rev Time 0.00
Received By medwards Date 2020-07-18 Time 14:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-06-10 Cont ID  
Sent By medwards Date 2020-06-10 Time 17:42 Rev Time 0.00
Received By medwards Date 2020-06-05 Time 08:21 Sent To  
Notes
2020-06-10 17:43:451ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20050766
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE BIO SAFETY PDF DOCUMENT IS A BLANK PAGE, PLEASE
 UPLOAD DOCUMENT. FBC FS 107.2.1
  
 2) SHEET M0.1: PLEASE PROVIDE OUTDOOR AIR CALCULATIONS
 INCLUDING THE SYSTEM VENTILATION EFFICIENCY. FBC
 M403.3.1.1.2.3.2
  
 3) PLEASE PROVIDE ENERGY CODE CALCULATIONS. FBC EC
 C403.2
  
 4) PLEASE PROVIDE A LIST OF HAZARDOUS MATERIALS WITH
 QUANTITIES OF EACH STORED FOR THIS FACILITY. FBC FS
 107.2.1
  
 5) PLEASE PROVIDE SPEC SHEETS FOR ALL EQUIPMENT USED IN
 THESE AREAS. FBC FS 107.2.1
  
 6) ACCORDING TO THE A SHEETS THESE WALLS HAVE A FIRE
 RATING OF 1 HR. PLEASE SHOW ALL DUCT WORK PASSING
 THROUGH THESE WALLS ARE PROTECTED WITH THE REQUIRED FD.
 FBC M 607.5
  
 7) PLEASE SHOW HOW AHU-1 IS PROVIDING VENTILATION FOR
 THE AREA. SHOW DUCT WORK ON THE DRAWING. FBC FS 107.2.1
  
 8) PLEASE SHOW HOW THE HOODS LOCATED IN THE LABS ARE
 EXHAUSTING THE AIR AND SHOW THE EXHAUST TERMINATION
 LOCATION. FBC FS 107.2.1
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-07-21 Cont ID  
Sent By jesmith Date 2020-07-21 Time 11:15 Rev Time 0.00
Received By jesmith Date 2020-07-21 Time 11:03 Sent To  
Notes
2020-07-21 11:15:1220050766 625 N FLAGLER DR # 625
  
 PLUMBING COMMENTS: APPROVED
  
 EXISTING DRINKING FOUNTAIN TO REMAIN AS IS; SEE A0.02
 AND A1.11
  
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-06-09 Cont ID  
Sent By shill Date 2020-06-09 Time 12:30 Rev Time 0.00
Received By shill Date 2020-06-09 Time 08:31 Sent To  
Notes
2020-06-09 12:30:43CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20050766 625 N FLAGLER DR # 625
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1. PER WPB FBC 107.2.1, PROVIDE ON PLANS THE
 LOCATION(S) OF MINIMUM PLUMBING FACILITIES FOR THE
 BUSINESS OCCUPANCY PER FBC PL 403.1, TABLE 403.1 AS
 FOLLOW:
 A. FBC PL 410.3 REQUIRES NO FEWER THAN TWO DRINKING
 FOUNTAINS. ONE DRINKING FOUNTAIN SHALL COMPLY WITH THE
 REQUIREMENTS FOR PEOPLE WHO USE A WHEELCHAIR AND ONE
 DRINKING FOUNTAIN SHALL COMPLY WITH THE REQUIREMENTS
 FOR STANDING PERSONS. A SINGLE DRINKING FOUNTAIN WITH
 TWO SEPARATE SPOUTS THAT COMPLIES WITH THE REQUIREMENTS
 FOR PEOPLE WHO USE A WHEELCHAIR AND STANDING PERSONS
 SHALL BE PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE
 DRINKING FOUNTAINS. COMPLY WITH FBC ACC 211.2 AND
 SECTION 602.
 B. ONE (1) SERVICE SINK
  
 2. THE BSL-2 RESEARCH LABORATORY SUMMARY SUBMITTED IN
 SUPPORTING DOCUMENTS CALL OUT AN AUTOCLAVE. PER WPB FBC
 107.2.1, PROVIDE MANUFACTURER?S
 SPECIFICATION/INSTALLATION MANUAL SHOWING COMPLIANCE
 WITH FBC PL 422.9 AND SHOW LOCATION ON THE PLANS.
 3. THE BSL-2 RESEARCH LABORATORY SUMMARY SUBMITTED IN
 SUPPORTING DOCUMENTS CALL OUT AND SHOW TWO (2)
 EMERGENCY EYEWASH STATIONS. PER WPB FBC 107.2.1,
 PROVIDE MANUFACTURER?S SPECIFICATION/INSTALLATION
 MANUAL SHOWING COMPLIANCE WITH FBC PL 411.1 AND SHOW
 LOCATIONS ON THE PLANS.
  
 A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT
 THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A
 RESPONSE NARRATIVE ADDRESSING THE PLUMBING COMMENTS
 FROM THE FIRST REVIEW.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE SIGNED AND SEALED BY THE DESIGNER AS
 REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20050766 625 N FLAGLER DR # 625
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-07-20 Cont ID  
Sent By pvalenti Date 2020-07-20 Time 11:43 Rev Time 0.00
Received By pvalenti Date 2020-07-20 Time 11:39 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-06-09 Cont ID  
Sent By pvalenti Date 2020-06-09 Time 08:22 Rev Time 0.00
Received By pvalenti Date 2020-06-08 Time 10:55 Sent To  
Notes
***NONE***