Plan Review Details - Permit 20050763
Plan Review Stops For Permit 20050763
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2020-06-16 Cont ID  
Sent By rmcphers Date 2020-06-16 Time 11:25 Rev Time 0.00
Received By rmcphers Date 2020-06-16 Time 11:25 Sent To  
Notes
2020-06-16 11:26:07PERMIT IS FOR ELECTRICAL UPGRADE (CHANGE OF OCCUPANCY
 CLASSIFICATION PERMIT - 20060761)

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-07-17 Cont ID  
Sent By jleahy Date 2020-07-17 Time 16:44 Rev Time 0.00
Received By jleahy Date 2020-07-17 Time 16:40 Sent To  
Notes
2020-07-17 16:49:28ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) SHOW LOCATION ON BUILDING OF ALL SERVICE DISCONNECTS
 230.72
  
 2) SUBMIT A LOAD CALCULATION DONE IN ACCORDANCE WITH
 ARTICLE 220 OF THE NEC
  
 3) VALUE JUST OF THE SERVICE IS LOW FOR INDUSTRY
 STANDARDS. PLEASE ADJUST THE VALUE ACCORDING TO
 INDUSTRY STANDARDS. (2450)
  
 4) SHOW LOCATION OF PANEL IN BUILDING.
  
 5) SUBMIT A PANEL SCHEDULE FOR NEW PANEL IN BUILDING
 215.5
  
 6) PLAN NEEDS TO BE SIGNED BY ENGINEER OR CONTRACTOR
 WHO IS RESPONSIBLE FOR THE PLANS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-06-12 Cont ID  
Sent By jleahy Date 2020-06-12 Time 14:00 Rev Time 0.00
Received By jleahy Date 2020-06-12 Time 13:55 Sent To  
Notes
2020-06-12 16:03:20NO PLANS OR PERMIT FOR A BREWERY SUBMITTED TO CITY.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-07-28 Cont ID  
Sent By shill Date 2020-07-28 Time 07:56 Rev Time 0.00
Received By shill Date 2020-06-29 Time 08:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-06-24 Cont ID  
Sent By shill Date 2020-06-24 Time 16:20 Rev Time 0.00
Received By shill Date 2020-05-28 Time 14:20 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-07-17 Cont ID  
Sent By jleahy Date 2020-07-17 Time 16:49 Rev Time 0.00
Received By jleahy Date 2020-07-17 Time 16:49 Sent To  
Notes
2020-07-17 16:50:13SEE FIRST REVIEW COMMENTS FOR SIGNATURE. JLEAHY

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-06-24 Cont ID  
Sent By shill Date 2020-06-24 Time 16:19 Rev Time 0.00
Received By shill Date 2020-06-24 Time 16:19 Sent To  
Notes
2020-06-24 16:20:26PAGES NOT APPLICABLE TO ELECTRICAL WORK WERE SUBMITTED;
 PLEASE CONTACT [email protected] TO HAVE THEM
 REMOVED
  

Review Stop Z ZONING
Rev No 2 Status F Date 2020-07-24 Cont ID  
Sent By awooten Date 2020-07-24 Time   Rev Time 0.00
Received By awooten Date 2020-07-24 Time   Sent To  
Notes
2020-07-24 11:37:12***********ZONING REVIEW************
  
 PER CHAPTER 6 - ALCOHOLIC BEVERAGES SEC. 6-2
 (D)(E)(1)A., AT LEAST 65 PERCENT OF THE SQUARE FOOTAGE
 OF THE FACILITY (INCLUSIVE OF OUTDOOR SEATING
 FACILITIES) SHALL BE DEDICATED TO THE BREWERY FUNCTION
 INCLUDING, BUT NOT LIMITED TO, BREW HOUSE, BOILING AND
 WATER TREATMENT AREAS, BOTTLING AND KEGGING LINES, MALT
 MILLING AND STORAGE, FERMENTATION TANKS, CONDITION
 TANKS AND SERVING TANKS.
  
 *****SHOW ALL EQUIPMENT AND AREA DEDICATED TO THE
 BREWERY FUNCTION ON FLOOR PLAN, INCLUDING, BUT NOT
 LIMITED TO, BREW HOUSE, BOILING AND WATER TREATMENT
 AREAS, BOTTLING AND KEGGING LINES, MALT MILLING AND
 STORAGE, FERMENTATION TANKS, CONDITION TANKS AND
 SERVING TANKS.****
  
 ALANA WOOTEN
 PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2020-06-18 Cont ID  
Sent By awooten Date 2020-06-18 Time   Rev Time 0.00
Received By awooten Date 2020-06-18 Time   Sent To  
Notes
2020-06-18 11:10:32***********************ZONING REVIEW
 FAILED**********************************
  
 THE SUBJECT PROPERTY IS ZONED INDUSTRIAL, SO THERE IS
 NO MAXIMUM SQUARE FOOTAGE RESTRICTION.
  
 THE OTHER REQUIREMENTS BELOW MUST BE MET ALONG WITH A
 BUSINESS TAX LICENSE FROM THE CITY.
  
 PLEASE PROVIDE A WRITTEN STATEMENT RESPONDING TO THE
 REQUIREMENTS LISTED BELOW FROM THE CITY'S ZONING AND
 LAND DEVELOPMENT REGULATIONS AND A FLOOR PLAN SHOWING
 THE REQUIRED CALCULATIONS.
  
 (6.1)
 BREWPUB/MICROBREWERY/MICRO-DISTILLERY/MICRO-WINERY
 (PXR: SEE ITEM 12.1, TABLE IX-I).
  
 A. ADDITIONAL APPLICATION REQUIREMENTS.
  
 1. A WRITTEN STATEMENT THAT THE PROPOSED FACILITY WILL
 COMPLY WITH ALL APPLICABLE STATE LAWS AND REGULATIONS.
  
 2. THE ADDITIONAL STANDARDS FOR THIS USE SHALL NOT
 APPLY TO BONA FIDE RESTAURANTS DERIVING MORE THAN 51
 PERCENT OF SALES FROM FOOD AND SERVING MANUFACTURES
 ALCOHOLIC BEVERAGES FOR ON-SITE CONSUMPTION ONLY AND
 WITH NO DISTRIBUTION.
  
 3. A FLOOR PLAN DEPICTING COMPLIANCE WITH ADDITIONAL
 STANDARD 2 SHALL BE SUBMITTED AS PART OF THE
 CERTIFICATE OF USE APPLICATION.
  
 B. ADDITIONAL STANDARDS.
  
 1. THE MAXIMUM SIZE OF A BUILDING CONTAINING A BREWPUB,
 MICROBREWERY, MICRO-DISTILLERY, OR MICRO-WINERY USE
 SHALL NOT EXCEED 3,000 SQUARE FEET IN THE NORTHWOOD
 MIXED-USE DISTRICT (NMUD) OR 5,000 SQUARE FEET IN THE
 GENERAL COMMERCIAL (GC) ZONING DISTRICT. THERE SHALL BE
 NO LIMIT FOR A FACILITY LOCATED WITHIN THE INDUSTRIAL
 (IND) ZONING DISTRICT.
  
 2. THIS USE SHALL BE PERMITTED ONLY IN CONJUNCTION WITH
 A RESTAURANT, BAR, TASTING ROOM OR RETAIL SERVICE. A
 MAXIMUM OF 75 PERCENT OF THE SQUARE FOOTAGE OF THE
 FACILITY (INCLUSIVE OF OUTDOOR SEATING FACILITIES)
 SHALL BE DEDICATED TO THE BREWERY FUNCTION INCLUDING,
 BUT NOT LIMITED TO, BREW HOUSE, BOILING AND WATER
 TREATMENT AREAS, BOTTLING AND KEGGING LINES, MALT
 MILLING AND STORAGE, FERMENTATION TANKS, CONDITION
 TANKS AND SERVING TANKS. THIS STANDARD SHALL NOT APPLY
 TO PROPERTIES LOCATED WITHIN THE INDUSTRIAL (I) ZONING
 DISTRICT).
  
 3. EXCEPT FOR LOADING AND UNLOADING, ALL ACTIVITIES
 SHALL OCCUR WITHIN A BUILDING. DELIVERY ACCESS AND
 LOADING BAYS SHALL NOT FACE TOWARD ANY STREET,
 EXCLUDING ALLEYS. DELIVERY ACCESS AND LOADING BAYS
 FACING AN ADJACENT RESIDENTIAL USE, OR RESIDENTIAL
 ZONING DISTRICT, SHALL HAVE THE DOORS CLOSED AT ALL
 TIMES, EXCEPT DURING THE MOVEMENT OF RAW MATERIALS,
 OTHER SUPPLIES AND FINISHED PRODUCTS INTO AND OUT OF
 THE BUILDING.
  
 4. ALL NEW FACILITIES, WHETHER IN AN EXISTING BUILDING
 OR NEW BUILDING SHALL PROVIDE ON-SITE LOADING IN
 ACCORDANCE WITH ZLDR SECTION 94-485(P), TABLE XV-4. FOR
 NEW FACILITIES LOCATING WITHIN AN EXISTING BUILDING,
 WITH NO CHANGE IN BUILDING FOOTPRINT, IF A FUNCTIONAL
 ALLEY EXISTS ADJACENT TO THE FACILITY, FACILITIES MAY
 USE THE ALLEY TO ACCOUNT FOR ONE OF THE REQUIRED
 ON-SITE LOADING SPACES.
  
 5. ALL MECHANICAL EQUIPMENT VISIBLE FROM THE STREET
 (EXCLUDING ALLEYS), WITH AN ADJACENT RESIDENTIAL USE OR
 WITHIN A RESIDENTIAL ZONING DISTRICT, SHALL BE SCREENED
 USING ARCHITECTURAL FEATURES CONSISTENT WITH THE
 PRINCIPAL STRUCTURE.
  
 6. NO OUTDOOR STORAGE SHALL BE ALLOWED. THIS
 PROHIBITION INCLUDES USE OF PORTABLE STORAGE UNITS,
 CARGO CONTAINERS, AND TRACTOR TRAILERS.
  
 7. OUTDOOR SEATING AREAS OR AREAS OF PATRON
 CONGREGATION SHALL BE PROHIBITED WHEN THE PROPERTY
 DIRECTLY ABUTS A RESIDENTIAL ZONING DISTRICT.
  
 8. DRIVE-THROUGH FACILITIES ARE PROHIBITED.
  
 ADDITIONAL COMMENTS MAY FOLLOW FURTHER REVIEW.
  
 ALANA WOOTEN
 PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]