| 2020-06-08 15:02:10 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20050552 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) ON THE APPLICATION IT INDICATES THAT YOU ARE |
| | INSTALLING AN ENTIRELY NEW GAS SYSTEM AT THIS |
| | RESIDENCE. PLEASE REMOVE THE WORD EXISTING FROM THE GAS |
| | LINE PIPING RISER DIAGRAM. FBC FS 107.2.1 |
| | |
| | 2) PLEASE PROVIDE A DRAWING WITH THE SHUT OFFS, UNION |
| | FITTINGS, DRIP LEGS, VENTING OF INDOOR REGULATORS. |
| | PLEASE SHOW THAT EACH HAVE A WAY OF ACCESSING EACH. FBC |
| | FS 107.2.1 |
| | |
| | 3) IS ANY OF THIS NEW PIPING SYSTEM INSTALLED INDOORS |
| | UNDERGROUND? FBC RES G2415.14 |
| | |
| | 4) PLEASE PROVIDE SPECS ON THE GENERATOR AND FLEXIBLE |
| | GAS LINE CONNECTING THE GENERATOR TO THE GAS LINE. FBC |
| | FS 107.2.1 |
| | |
| | 5) THIS APPEARS TO BE A 2PSI SYSTEM WITH MP REGULATORS |
| | ALONG THE PIPING SYSTEM TO REDUCE PRESSURE TO EACH |
| | APPLIANCE. PLEASE PROVIDE THE LONGEST LENGTH TO THE |
| | MOST REMOTE APPLIANCE (WHICH APPEARS TO BE THE NEW |
| | TANKLESS WATER HEATER) ON THE 2LB SYSTEM. PLEASE ALSO |
| | SHOW WHERE THE PIPING MATERIAL CHANGES FROM PE TO GALV. |
| | GOING TO THE WATER HEATER. FBC FS 107.2.1 |
| | |
| | 6) PLEASE SHOW THE REGULATOR LOCATION FOR THE WATER |
| | HEATER. FBC RES G2421.1 |
| | |
| | 7) PLEASE SHOW DISTANCE FROM THE METER TO THE ?? JOINT |
| | FOR THE EXISTING PE FOR THE INTERIOR. FBC FS 107.2.1 |
| | |
| | 8) PLEASE PROVIDE THE CONCRETE SLAB DETAIL DRAWING AND |
| | THE TIE DOWN SYSTEM FOR THE GENERATOR. FBC FS 107.2.1 |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | |