| 2020-07-07 18:54:45 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PLAN MUST BE DIIGITALLY SIGNED BY ENGINEER OR SIGNED |
| | BY THE ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE |
| | CORRECTION. FS 471.003(2)(H); 471.025; WPB FBC 107.1 |
| | |
| | 2. NO VALUE SHOWN ON PERMIT APP. |
| | |
| | 3. SATISFY ZONING COMMENTS. |
| | |
| | 4. DISCONNECT MUST BE WITHIN SIGHT OF SIGN 600.6A1 NEC |
| | |
| | 5. PROVIDE EXTERIOR LIGHTING CONTROLS AS SPECIFIED IN |
| | THE FBC ENERGY CONSERVATION. FBC EC C405.2.5 |
| | EXTERIOR LIGHTING FOR BUILDING FACADE OR LANDSCAPE, |
| | MUST HAVE CONTROLS AUTOMATICALLY SET TO SHUT OFF |
| | LIGHTING PROGRAMMED FROM DAWN/DUSK. ALL TIME SWITCHES |
| | MUST HAVE MINIMUM 10HR BATTERY BACKUP. |
| | |
| | A PHOTOCELL AND TIMECLOCK AS SHOWN ON PLAN DOES NOT |
| | SUFFICE. IF ALL SIGNS ARE BEING CONTROLLED FROM A |
| | BUILDING MANAGMENT SYSTEM, A BLUE BIRD LIGHTING CONTROL |
| | CONTACTOR FOR EXAMPLE, ANNOTATE THAT ON THE PLAN. |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN |
| | PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE |
| | 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A |
| | COMPLETED RESUBMITTAL FORM, VIA EMAIL TO |
| | [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT |
| | NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE |
| | RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: |
| | |
| | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| | UILDING-PERMIT-FORMS |
| | |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |