Plan Review Details - Permit 20050672
| Plan Review Stops For Permit 20050672 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2020-08-31 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2020-08-31 |
Time |
09:01 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2020-08-31 |
Time |
08:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2020-07-22 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2020-07-22 |
Time |
11:57 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2020-07-22 |
Time |
11:13 |
Sent To |
|
|
| Notes |
| 2020-07-22 11:52:03 | 2017 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 20050672 | | | ADD: 1320 ALPHA ST. | | | CONT: GEN-X-CONSTRUCTION | | | TEL: 561-963-4490 | | | E-MAIL: [email protected] | | | | | | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 2ND REVIEW | | | DATE: WED. JULY 22ND/2020 | | | ACTION: DENIED | | | | | | 1) SEMI-COMPLIED. SHEET A8.02 DOES SHOW THE SLAB REPAIR | | | AND SHEET A8.01 SHOWS THE ONE HOUR FIRE RATING FOR | | | BETWEEN UNITS WITH FIRE X DRYWALL BUT THERE IS NO | | | MENTION IN THIS DETAIL HOW COMPLIANCE IS TO BE MET IN | | | THE SHOWER WHERE YOU WILL ALSO NEED TO SHOW COMPLIANCE | | | WITH SECTION: 2509.2 BASE FOR TILE IN THE 2017 FBC-B. | | | MATERIALS USED AS A BASE FOR WALL TILE IN TUB AND | | | SHOWER AREAS AND WALLS AND CEILING PANELS IN SHOWER | | | AREAS SHALL BE OF MATERIALS LISTED IN TABLE 2509.2 AND | | | INSTALLED IN ACCORDANCE WITH MANUFACTURER?S | | | RECOMMENDATIONS. WATER RESISTANT GYPSUM BACKING BOARD | | | SHALL BE USED AS A BASE FOR TILE IN WATER CLOSET | | | COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE WITH | | | GA-216 OR ASTM C840 AND THE MANUFACTURER'S | | | RECOMMENDATIONS. | | | | | | 2) SEMI- COMPLIED SEE COMMENT # 1. PLEASE PROVIDE IN | | | THE FLOOR PLAN, THE R2 UNITS THAT ARE BACK TO BACK AND | | | HAVE REPLACEMENT PLUMBING IN THESE WALLS. SHOW HOW | | | CONFORMANCE WITH THE 1 HOUR FIRE SEPARATION (FIRE | | | PARTITIONS) REQUIRED BY SECTION708.1 AND 420 FBC-B AND | | | IN CONFORMANCE WITH THE FIRE RESISTANCE RATING OF | | | 708.3. | | | . | | | 3) COMPLIED. PLUMBING THAT IS WITHIN THE 1 HOUR TENANT | | | SEPARATION WALL AND EXTENDS THROUGH THE WALL MEMBRANE | | | WILL NEED TO PROVIDE COMPLIANCE WITH 714.3.2 COMPLYING | | | WITH 714.3.1.2 THROUGH- PENETRATION FIRESTOP SYSTEM. | | | | | | 4) COMPLIED. IT IS UNKNOWN IF THIS IS A MULTIPLE STORY | | | APARTMENT COMPLEX, THIS INFORMATION WAS NOT GIVEN. IF | | | SO COMPLIANCE WITH 714.4 HORIZONTAL ASSEMBLIES AND | | | 714.4.1 THROUGH PENETRATIONS AND 714.4.1.2. HORIZONTAL | | | THROUGH-PENETRATIONS FIRESTOP ASSEMBLIES WILL NEED TO | | | SHOW COMPLIANCE. | | | | | | 5) COMPLIED. THE BUILDING PLANS WILL NEED TO COMPLY | | | WITH THE, 107.2.1.3. QUALITY OF PLANS. BUILDING PLANS | | | SHALL BE DRAWN TO A 1/8TH INCH SCALE ON SUBSTANTIAL | | | PAPER OR OTHER ACCEPTABLE MEDIUM. THE BUILDING OFFICIAL | | | MAY ESTABLISH THROUGH DEPARTMENT POLICY OTHER STANDARDS | | | FOR THE PLANS AND SPECIFICATIONS IN ORDER TO PROVIDE | | | CONFORMITY TO ITS RECORD RETENTION PROGRAM. THIS POLICY | | | MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, SHAPE, | | | CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO RECORD | | | MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE WITH | | | THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES. | | | | | | 6) 2ND REQUEST. THE SUBMITTED PLANS BY ARCHITECT HAROLD | | | TUTTLE IT WOULD APPEAR TO BE PAPER PLANS AND WOULD NEED | | | TO BE UPLOADED WITH DIGITAL SIGNATURES. ARCHITECTS: | | | FLORIDA ADMINISTRATIVE CODE 61G1-16.005. PROCEDURES FOR | | | DIGITALLY SIGNING AND SEALING AND FOR ELECTRONICALLY | | | TRANSMITTING PLANS, SPECIFICATIONS, REPORTS OR OTHER | | | DOCUMENTS. | | | | | | 1ST ROUND OF COMMENTS. CERTIFICATION BY CONTRACTOR. | | | 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE | | | EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H) | | | ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C) | | | (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT | | | WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE | | | CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE. | | | THE CONTRACTOR (QUALIFIER) THAT CREATED / DRAWN THE SET | | | OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR | | | OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME | | | AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN | | | AND PLANS DRAWN. FOR EACH TRADE THE CONTRACTOR | | | RESPONSIBLE FOR THE DESIGN UNDER THE TRADE LICENSED IN | | | MUST PRINT THEIR NAME, SIGN THEIR NAME AND LICENSE | | | NUMBER, NOTE THESE PLANS APPEAR TO BE DRAWN BY ONE | | | INDUVIAL, THEY WOULD HAVE TO BE LICENSED AS A BUILDING, | | | ELECTRICAL AND PLUMBING CONTRACTOR TO SUBMIT ALL THESE | | | TRADES UNDER ONE SHEET. | | | | | | 7) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | PLEASE NOTE WE ARE WORKING FROM HOME IF YOU WOULD LIKE | | | TO CONTACT ME, MY CELL NUMBER IS 561-718-9724. | | | | | | JAMES A. WITMER BN, PX, SFP, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6717 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2020-05-31 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2020-05-31 |
Time |
15:01 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2020-05-31 |
Time |
14:00 |
Sent To |
|
|
| Notes |
| 2020-05-31 15:01:20 | 2017 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 20050672 | | | ADD: 1320 ALPHA ST. | | | CONT: GEN-X-CONSTRUCTION | | | TEL: 561-963-4490 | | | E-MAIL: [email protected] | | | | | | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: SUN. MAY 31/2020 | | | ACTION: DENIED | | | | | | 1) THIS REVIEW THERE WERE NO PLANS SUBMITTED FOR THE | | | BUILDING REVIEW. THE PLUMBING RISERS THAT WAS SUBMITTED | | | INDICATES THAT THERE WILL BE THE REMOVAL OF DRYWALL IN | | | UNITS AND THE REMOVAL OF CONCRETE FLOORS. PLEASE SUBMIT | | | A FLOOR PLAN AND SECTIONS OF BOTH SHOWING WHAT AREAS OF | | | WALLS AND CONCRETE SLABS THAT WILL BE REMOVED AND | | | REPLACED. SHOW COMPLIANCE WITH THE 2017 FBC-B SECTIONS: | | | 1A) VAPOR BARRIER: 1805.2.1/ 1907.1. FLOORS. | | | 1B) TERMITE TREATMENT 1816.1.2 & 1816.1.3. | | | 1C) RE-INFORCEMENT OF SLAB WHERE REMOVED. 1907.2(2). | | | | | | 2) PLEASE PROVIDE IN THE FLOOR PLAN, THE R2 UNITS THAT | | | ARE BACK TO BACK AND HAVE REPLACEMENT PLUMBING IN THESE | | | WALLS. SHOW HOW CONFORMANCE WITH THE 1 HOUR FIRE | | | SEPARATION (FIRE PARTITIONS) REQUIRED BY SECTION708.1 | | | AND 420 FBC-B AND IN CONFORMANCE WITH THE FIRE | | | RESISTANCE RATING OF 708.3. | | | | | | 3) PLUMBING THAT IS WITHIN THE 1 HOUR TENANT SEPARATION | | | WALL AND EXTENDS THROUGH THE WALL MEMBRANE WILL NEED TO | | | PROVIDE COMPLIANCE WITH 714.3.2 COMPLYING WITH | | | 714.3.1.2 THROUGH- PENETRATION FIRESTOP SYSTEM. | | | | | | 4) IT IS UNKNOWN IF THIS IS A MULTIPLE STORY APARTMENT | | | COMPLEX, THIS INFORMATION WAS NOT GIVEN. IF SO | | | COMPLIANCE WITH 714.4 HORIZONTAL ASSEMBLIES AND 714.4.1 | | | THROUGH PENETRATIONS AND 714.4.1.2. HORIZONTAL | | | THROUGH-PENETRATIONS FIRESTOP ASSEMBLIES WILL NEED TO | | | SHOW COMPLIANCE. | | | | | | 5) THE BUILDING PLANS WILL NEED TO COMPLY WITH THE, | | | 107.2.1.3. QUALITY OF PLANS. BUILDING PLANS SHALL BE | | | DRAWN TO A 1/8TH INCH SCALE ON SUBSTANTIAL PAPER OR | | | OTHER ACCEPTABLE MEDIUM. THE BUILDING OFFICIAL MAY | | | ESTABLISH THROUGH DEPARTMENT POLICY OTHER STANDARDS FOR | | | THE PLANS AND SPECIFICATIONS IN ORDER TO PROVIDE | | | CONFORMITY TO ITS RECORD RETENTION PROGRAM. THIS POLICY | | | MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, SHAPE, | | | CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO RECORD | | | MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE WITH | | | THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES. | | | | | | 6) CERTIFICATION BY CONTRACTOR. 107.3.4.3 CERTIFICATION | | | BY CONTRACTOR. PLEASE NOTE THE EXCEPTION TO ENGINEERED | | | PLANS UNDER 471.003(H) ELECTRICAL/ PLUMBING/ | | | MECHANICAL, 481.229(1)(C) (BUILDING) REQUIRES THE | | | CONTRACTOR FOR THAT TRADE THAT WILL BE LICENSED IN THAT | | | TRADE, WILL ALSO BE THE CONTRACTOR THAT DESIGNS THE | | | SYSTEM UNDER THAT TRADE. THE CONTRACTOR (QUALIFIER) | | | THAT CREATED / DRAWN THE SET OF PLANS WILL NEED TO | | | IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE | | | PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR | | | THE TRADE YOU ARE LICENSED IN AND PLANS DRAWN. FOR EACH | | | TRADE THE CONTRACTOR RESPONSIBLE FOR THE DESIGN UNDER | | | THE TRADE LICENSED IN MUST PRINT THEIR NAME, SIGN THEIR | | | NAME AND LICENSE NUMBER, NOTE THESE PLANS APPEAR TO BE | | | DRAWN BY ONE INDUVIAL, THEY WOULD HAVE TO BE LICENSED | | | AS A BUILDING, ELECTRICAL AND PLUMBING CONTRACTOR TO | | | SUBMIT ALL THESE TRADES UNDER ONE SHEET. | | | | | | 7) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE | | | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED | | | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE | | | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS | | | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. | | | | | | PLEASE NOTE WE ARE WORKING FROM HOME IF YOU WOULD LIKE | | | TO CONTACT ME, MY CELL NUMBER IS 561-718-9724. | | | JAMES A. WITMER BN, PX, SFP, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6717 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2020-09-08 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-09-08 |
Time |
17:00 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-09-08 |
Time |
17:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2020-08-04 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-08-04 |
Time |
11:28 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-08-04 |
Time |
11:28 |
Sent To |
|
|
| Notes |
| 2020-08-04 11:29:00 | NO ELECTRIC SHOWN FOR WATER HEATER REPLACEMENTS JLEAHY |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2020-09-08 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-09-08 |
Time |
17:00 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-08-26 |
Time |
16:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2020-08-04 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-08-04 |
Time |
11:29 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-07-17 |
Time |
14:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2020-07-07 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2020-07-07 |
Time |
09:09 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2020-05-21 |
Time |
09:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2020-09-01 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2020-09-01 |
Time |
08:25 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2020-09-01 |
Time |
08:17 |
Sent To |
|
|
| Notes |
| 2020-09-01 08:25:12 | PLUMBING COMMENTS: APPROVED | | | | | | PROVISO: SHOWER ON THE SECOND FLOOR SHALL CONNECT TO | | | STACK OR INTERSECT WITH THE WATER CLOSET CONNECTION AT | | | THE STACK OR SHALL BE RE-VENTED. SEE FBC PL 912.1.1; | | | SEE RED-LINED PLAN SHEET P-3. | | | | | | PROVISO: ALL SERVICE VALVES SHALL BE ACCESSIBLE. SEE | | | FBC PL 606.3; SEE RED-LINED PLAN SHEET P-3. | | | | | | ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD | | | INSPECTOR'S APPROVAL | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | | PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM | | | THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND | | | NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF | | | PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY | | | ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | | AVOID VOIDING OF THE PERMIT. | | | | | | | | | | | | 20050672 1320 ALPHA ST | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2020-08-27 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2020-08-27 |
Time |
16:50 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2020-08-27 |
Time |
16:21 |
Sent To |
|
|
| Notes |
| 2020-08-27 16:23:06 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL | | | MANUAL REVISED 2017 | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH | | | EDITION | | | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION | | | FAC= FLORIDA ADMINISTRATIVE CODE | | | FS = FLORIDA STATUTES | | | | | | | | | 3RD REVIEW | | | | | | PLUMBING COMMENTS: DENIED | | | | | | CONTRACT IN SUPPORTING DOCUMENTS PROVIDES FOR | | | INSTALLATION OF NEW ACRYLIC SHOWER ENCLOSURE AND NEW | | | WATER HEATER IN EACH APARTMENT, HOWEVER, PLAN SHEET | | | A8.01 ALSO CALLS FOR REPLACEMENT OF ALL EXISTING | | | PLUMBING FIXTURES WITH NEW WHICH HAS BEEN CONFIRMED IN | | | THE COMMENT RESPONSE LETTER. PER WPB FBC 107.2.1 | | | PROVIDE UPDATED CONTRACT, REFLECTING CORRECTED VALUE. | | | | | | | | | PROVISO: SHOWER ON THE SECOND FLOOR SHALL CONNECT TO | | | STACK OR INTERSECT WITH THE WATER CLOSET CONNECTION AT | | | THE STACK OR SHALL BE RE-VENTED. SEE FBC PL 912.1.1; | | | SEE RED-LINED DRAWINGS IN PROJECT DOCS. | | | | | | PROVISO: ALL SERVICE VALVES SHALL BE ACCESSIBLE. SEE | | | FBC PL 606.3; SEE RED-LINED DRAWINGS IN PROJECT DOCS. | | | | | | | | | END OF COMMENTS. | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE | | | DESIGNER IN ACCORDANCE WITH FAC AND FS. | | | | | | | | | | | | JERALD SMITH | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | EMAIL [email protected] | | | PHONE 561-246-0882 MOBILE | | | | | | 20050672 1320 ALPHA ST | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2020-08-03 |
Time |
|
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2020-08-03 |
Time |
09:54 |
Sent To |
|
|
| Notes |
| 2020-08-03 14:40:50 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL | | | MANUAL REVISED 2017 | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH | | | EDITION | | | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION | | | FAC= FLORIDA ADMINISTRATIVE CODE | | | FS = FLORIDA STATUTES | | | | | | | | | 2ND REVIEW | | | PLUMBING COMMENTS: DENIED | | | 1. PLEASE NOTE; THE SCOPE OF WORK NOTED ON PLAN SHEET | | | A0.01 INDICATES A MUCH LARGER SCOPE INCLUDING BUT NOT | | | LIMITED TO ELECTRICAL AND MILLWORK THAN IS INDICATED IN | | | THE CONTRACT OR ON THE PERMIT APPLICATIONS. THIS | | | IMPACTS THE PERMIT FEES AND NEEDS TO BE ADDRESSED. | | | | | | 2. SERVICE VALVE | | | NOTE THAT PER FBC PL 606.1, A DEDICATED FULL-OPEN | | | SERVICE VALVES SHALL BE INSTALLED ON THE ENTRANCE TO | | | EVERY WATER SUPPLY PIPE TO A DWELLING UNIT. SERVICE | | | VALVE AT FIRST FLOOR UNITS IN THE WATER RISER DIAGRAM | | | APPEARS TO SHUT DOWN THE ENTIRE RISER. PER WPB FBC | | | 107.2.1, PROVIDE CLARIFICATION. | | | SERVICE VALVE SHALL BE ACCESSIBLE PER FBC PL 606.3. PER | | | WPB FBC 107.2.1, PROVIDE NOTE THAT THE SERVICE VALVE | | | SHALL BE ACCESSIBLE PER FBC PL 606.3. | | | | | | 3. SHUT OFF VALVE FOR WATER HEATER | | | SHUT OFF VALVES FOR THE WATER HEATER SHALL BE | | | ACCESSIBLE PER FBC PL 606.3 AND 503.1. WATER RISER | | | DIAGRAM SEEMS TO INDICATE A SHUT OFF VALVE (BALL | | | VALVE?) IN THE COLD WATER LINE GOING TO THE WATER | | | HEATER AS WELL AS A SEPARATE COLD WATER AND HOT WATER | | | SHUT OFF VALVE AT THE WATER HEATER WHICH APPEAR TO OF | | | NO USE AS THE KITCHEN MILLWORK WOULD HAVE TO BE | | | DISASSEMBLED AND/OR THE RANGE WOULD HAVE TO BE REMOVED | | | IN ORDER TO ACCESS. PER WPB FBC 107.2.1, CLARIFY. | | | PER WPB FBC 107.2.1, PROVIDE NOTE THAT THE SHUT OFF | | | VALVE FOR WATER HEATER SHALL BE ACCESSIBLE. | | | | | | 4. REPLACEMENT WATER HEATER | | | PER WPB FBC 107.2.1, SPECIFY THE REPLACEMENT WATER | | | HEATER. PROVIDE MANUFACTURER'S | | | SPECIFICATION/INSTALLATION MANUAL INCLUSIVE OF | | | ELECTRICAL CHARACTERISTICS AND WATER CONNECTIONS. | | | PROVIDE A THERMAL EXPANSION RELIEF VALVE INTO THE COLD | | | WATER SERVICE TO THE BUILDING BETWEEN THE SERVICE VALVE | | | AND THE BUILDING OR AT THE DOWNSTREAM SIDE OF THE | | | BACKFLOW PREVENTER. | | | PER WPB FBC 107.2.1, PROVIDE NOTE "THE T & P RELIEF | | | LINE/PAN DRAIN TERMINATION POINT ON THE BUILDING | | | EXTERIOR FOR EACH WATER HEATER SHALL BE LOCATED AND | | | MADE VISIBLE AND TESTED TO SHOW THAT THEY ARE CLEAR OF | | | ANY OBSTRUCTION TO THE SATISFACTION OF THE PLUMBING | | | INSPECTOR AT OR PRIOR TO FINAL INSPECTION". | | | | | | | | | 5. PLAN SHEET P4, SPECIFICATION NOTE 4, SPECIFICALLY | | | PROHIBITS THE INSTALLATION OF POTABLE WATER BELOW ANY | | | FLOOR ON GRADE OR FILL. PLAN SHEETS 2 AND 3 CLEARLY | | | SHOW POTABLE WATER INSTALLED UNDER THE FLOOR ON GRADE | | | OR FILL. PER WPB FBC 107.2.1, CLARIFY. | | | | | | 6. CONTRACT IN SUPPORTING DOCUMENTS PROVIDES FOR | | | INSTALLATION OF NEW ACRYLIC SHOWER ENCLOSURE. THERE IS | | | NO MENTION OF THIS ON THE PERMIT APPLICATION OR ON THE | | | PLANS. PER WPB FBC 107.2, CLARIFY. IF THIS IS PART OF | | | THE SCOPE OF WORK, THEN INDICATE ON THE PLANS AND | | | PROVIDE MANUFACTURER'S SPECIFICATION/INSTALLATION | | | MANUAL. | | | | | | 7. PLAN SHEET A2.01 NOTE REFERS TO A8.01 FOR PLUMBING | | | REQUIREMENTS. THE ONLY REFERENCE TO PLUMBING THAT I SEE | | | ON A8.01 IS THE VANITY TOP DETAIL SHOWING WATER CLOSET | | | AND LAVATORY PLACEMENT. ADDITIONALLY PLAN SHEET A0.01 | | | SCOPE OF WORK CALLS FOR REMOVE/REPLACE ALL PLUMBING | | | FIXTURES THROUGHOUT EACH UNIT AS WELL AS OTHER ITEMS | | | NOT NOTED CONTRACT IN SUPPORTING DOCUMENTS AND/OR IN | | | THE PERMIT APPLICATIONS. ARE THE PLUMBING FIXTURES | | | BEING REPLACED BEING REPLACED? PER WPB FBC 107.2.1, | | | CLARIFY. | | | | | | | | | END OF COMMENTS. | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE | | | DESIGNER IN ACCORDANCE WITH FAC AND FS. | | | | | | | | | | | | JERALD SMITH | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | EMAIL [email protected] | | | PHONE 561-246-0882 MOBILE | | | | | | 20050672 1320 ALPHA ST | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2020-07-07 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2020-07-07 |
Time |
08:19 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2020-06-25 |
Time |
08:58 |
Sent To |
|
|
| Notes |
| 2020-07-07 08:20:45 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL | | | MANUAL REVISED 2017 | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION | | | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH | | | EDITION | | | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION | | | FAC= FLORIDA ADMINISTRATIVE CODE | | | FS = FLORIDA STATUTES | | | | | | 20050672 1320 ALPHA ST | | | | | | 1ST REVIEW | | | PLUMBING COMMENTS: DENIED | | | | | | 1. PER WPB FBC 107.2.1, SUBMIT A FIRST AND SECOND FLOOR | | | PLAN OF BUILDING INDICATING ALL APARTMENTS AND LAUNDRY | | | ROOM, ETC. SHOW PLUMBING ROUTING AND ALL PLUMBING | | | FIXTURES; INDICATE ALL TIE IN POINTS. CLEARLY INDICATE | | | ON PLAN THAT CONFIGURATION OF REPLACEMENT PIPING IS | | | UNCHANGED. | | | NOTE: THE BUILDING PLANS WILL NEED TO COMPLY WITH THE, | | | 107.2.1.3. QUALITY OF PLANS. BUILDING PLANS SHALL BE | | | DRAWN TO A 1/8TH INCH SCALE ON SUBSTANTIAL PAPER OR | | | OTHER ACCEPTABLE MEDIUM. THE BUILDING OFFICIAL MAY | | | ESTABLISH THROUGH DEPARTMENT POLICY OTHER STANDARDS FOR | | | THE PLANS AND SPECIFICATIONS IN ORDER TO PROVIDE | | | CONFORMITY TO ITS RECORD RETENTION PROGRAM. THIS POLICY | | | MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, SHAPE, | | | CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO RECORD | | | MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE WITH | | | THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES. A PLAN OF | | | RECORD IS AVAILABLE FROM THE WPB BUILDING DEPARTMENT BY | | | CONTACTING CRAIG MCPHERSON AT 561-805-6684; EMAIL | | | [email protected]. | | | | | | 2. CERTIFICATION BY CONTRACTOR. 107.3.4.3 CERTIFICATION | | | BY CONTRACTOR. PLEASE NOTE THE EXCEPTION TO ENGINEERED | | | PLANS UNDER 471.003(H) ELECTRICAL/ PLUMBING/MECHANICAL, | | | 481.229(1)(C) (BUILDING) REQUIRES THE CONTRACTOR FOR | | | THAT TRADE THAT WILL BE LICENSED IN THAT TRADE, WILL | | | ALSO BE THE CONTRACTOR THAT DESIGNS THE SYSTEM UNDER | | | THAT TRADE. THE CONTRACTOR (QUALIFIER) THAT CREATED / | | | DRAWN THE SET OF PLANS WILL NEED TO IDENTIFY THEMSELVES | | | AS THE AUTHOR OF THE PLANS. PLEASE PRINT YOUR NAME, | | | SIGN YOUR NAME AND LICENSE NUMBER FOR THE TRADE YOU ARE | | | LICENSED IN AND PLANS DRAWN. FOR EACH TRADE THE | | | CONTRACTOR RESPONSIBLE FOR THE DESIGN UNDER THE TRADE | | | LICENSED IN MUST PRINT THEIR NAME, SIGN THEIR NAME AND | | | LICENSE NUMBER, NOTE THESE PLANS APPEAR TO BE DRAWN BY | | | ONE INDIVIDUAL; EACH DISCIPLINE SUBMITTED SHALL BE BY A | | | LICENSED CONTRACTOR IN THAT DISCIPLINE. | | | | | | 3. PER WPB FBC 107.2.1, SPECIFY ON THE PLANS MATERIAL | | | TYPE FOR SANITARY PIPING. | | | | | | 4. PROVIDE SLAB REPAIR DETAIL SHOWING COMPLIANCE WITH | | | FBC SECTIONS: | | | 1A) VAPOR BARRIER: 1805.2.1/ 1907.1. FLOORS. | | | 1B) TERMITE TREATMENT 1816.1.2 & 1816.1.3. | | | 1C) RE-INFORCEMENT OF SLAB WHERE REMOVED. 1907.2(2). | | | | | | 5. PER WPB FBC 107.2.1, PROVIDE DETAILS FOR HORIZONTAL | | | AND VERTICAL PIPE PENETRATIONS OF RATED WALLS AND | | | FLOORS SHOWING COMPLIANCE WITH FBC CHAPTER 7. | | | | | | 6. A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISED AT | | | THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A | | | RESPONSE NARRATIVE ADDRESSING THE PLUMBING COMMENTS | | | FROM THE FIRST REVIEW | | | | | | END OF COMMENTS. | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | ALL PLANS TO BE SIGNED AND SEALED BY THE DESIGNER AS | | | REQUIRED BY FAC AND FS. | | | | | | | | | JERALD SMITH | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | EMAIL [email protected] | | | PHONE 561-246-0882 MOBILE | | | | | | 20050672 1320 ALPHA ST | | | | | | | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2020-08-31 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2020-08-31 |
Time |
09:02 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2020-07-22 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2020-07-22 |
Time |
11:58 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2020-07-22 11:52:27 | THE SUBMITTED PLANS BY ARCHITECT HAROLD TUTTLE IT WOULD | | | APPEAR TO BE PAPER PLANS AND WOULD NEED TO BE UPLOADED | | | WITH DIGITAL SIGNATURES. ARCHITECTS: FLORIDA | | | ADMINISTRATIVE CODE 61G1-16.005. PROCEDURES FOR | | | DIGITALLY SIGNING AND SEALING AND FOR ELECTRONICALLY | | | TRANSMITTING PLANS, SPECIFICATIONS, REPORTS OR OTHER | | | DOCUMENTS. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2020-07-07 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2020-07-07 |
Time |
08:43 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2020-07-07 |
Time |
08:43 |
Sent To |
|
|
| Notes |
| 2020-07-07 08:45:58 | PURSUANT TO FBC 107.1, AND FS 481.229 (1) (C), AS THIS | | | THIS DESIGN EXCEEDS $25,000.00 IN VALUE, THE DESIGN | | | MUST BE PREPARED BY A PROFESSIONAL LICENSED PURSUANT TO | | | FS 481. SEE BELOW: | | | | | | FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF | | | CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL | | | INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL | | | BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT | | | APPLICATION. THE CONSTRUCTION DOCUMENTS SHALL BE | | | PREPARED BY A REGISTERED DESIGN PROFESSIONAL WHERE | | | REQUIRED BY CHAPTER 471, FLORIDA STATUTES & 61G15 | | | FLORIDA ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA | | | STATUTES & 61G1 FLORIDA ADMINISTRATIVE CODE. WHERE | | | SPECIAL CONDITIONS EXIST, THE BUILDING OFFICIAL IS | | | AUTHORIZED TO REQUIRE ADDITIONAL CONSTRUCTION DOCUMENTS | | | TO BE PREPARED BY A | | | REGISTERED DESIGN PROFESSIONAL. ELECTRONIC MEDIA | | | DOCUMENTS SHALL BE SUBMITTED WHEN REQUIRED BY THE | | | BUILDING OFFICIAL, AND MAY REQUIRE ONLY ONE SET OF | | | SUBMITTALS. | | | | | | |
|
|
|