| 2020-06-29 08:54:31 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20050603 |
| | ADD: 3507 BROADWAY |
| | CONT: RG & VC GENERAL CONTRACTING |
| | TEL: 561-667-2065 |
| | E-MAIL: CONSTRUCTION [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. JUNE 29TH/ 2020 |
| | ACTION: DENIED |
| | |
| | 1) THE PERMIT APPLICATION INDICATES UNDER THE HEADING |
| | TRADES ADDITIONAL PARKING AND FA?ADE RENOVATIONS. THE |
| | HEADING FOR DISCERPTION OF WORK WAS LEFT BLANK. THE |
| | ONLY PARKING SPACES ARE SHOWN ON THE SURVEY/ SITE PLAN. |
| | THERE IS NO NOTATION OF WHAT ADDITIONAL PARKING IS TO |
| | TAKE PLACE. THE SURVEY/ SITE PLAN DOES NOT SHOW THE |
| | REQUIRED STRIPING OF THE PARKING LOT. |
| | ACCESSIBLE PARKING SPACE / STALL PAINTING. 2017 |
| | ACCESSIBILITY CODE SECTION 502.2 VEHICLE SPACES. EACH |
| | PARKING SPACE MUST BE AT LEAST 12 FEET WIDE, SHALL BE |
| | MARKED TO DEFINE THE WIDTH, AND SHALL HAVE AN ADJACENT |
| | ACCESS AISLE COMPLYING WITH 502.3. |
| | ADVISORY 502.3.3MARKING THE METHOD AND MARKING OF COLOR |
| | OF MARKING ARE NOT SPECIFIED BY THESE REQUIREMENTS BUT |
| | MAY BE ADDRESSED BY STATE OR LOCAL LAWS OR REGULATIONS. |
| | WEST PALM MUNI-CODE ARTICLE XV PARKING DETAIL, 94-485 |
| | ILLUSTRATES WITH MEASUREMENTS FOR DOUBLE STRIPE STALL |
| | PAINTING. |
| | |
| | 2A) SHEET A-1 SHOWS A DETAIL FOR THE INSTALLATION OF |
| | HARDIE-PLANK SIDING. PLEASE PROVIDE THE PRODUCT |
| | APPROVAL FOR THIS SYSTEM EITHER A MIAMI-DADE NOA OR |
| | FLORIDA PRODUCT APPROVAL. |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(C) PANEL WALLS: HARDIE-PLANK WALL SYSTEMS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | |
| | 2B) WITHIN THE PRODUCT APPROVAL PLEASE CIRCLE THE TYPE |
| | OF SUB-SYSTEM, INSTALLATION SYSTEM INTO SUBSTRATE, |
| | ANCHOR LENGTH & SPACING AND ASSOCIATED PRESSURES. |
| | |
| | 2C) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE |
| | 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 3) PLEASE PROVIDE THE WIND DESIGN CRITERIA FOR THE |
| | PRODUCT APPROVAL. 2017 FBC-B 1603.1.4 WIND DESIGN DATA. |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| | STRUCTURE: |
| | |
| | 3.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| | MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS |
| | DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1. |
| | |
| | 3.2. RISK CATEGORY. |
| | |
| | 3.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| | THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. |
| | HEIGHT AND EXPOSURE. ASCE 7-10 TABLE 30.3.1. |
| | |
| | 3.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| | |
| | 3.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED |
| | BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR |
| | THE DESIGN OF THE STRUCTURE, PSF. |
| | |
| | 3.6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| | EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| | BUILDING. 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. |
| | |
| | 4) SHEET A2 & A3 BOTH SHOW A PROPOSED ALUMINUM GATE |
| | &FENCE/ PANEL SYSTEM. NO DESIGN CRITERIA WAS GIVEN FOR |
| | THE PANEL SYSTEM, POST SIZE SQUARE OR ROUND, DEPTH OF |
| | POST IN THE GROUND, ANCHORING OF POST, NO INFORMATION |
| | ON THE GATE AND LATCHING SYSTEM. 107.2.1.2. ADDITIONAL |
| | INFORMATION IS REQUIRED. CONSTRUCTION DOCUMENTS SHALL |
| | BE SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE |
| | AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT |
| | IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |