| 2020-05-27 11:37:07 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THERE ARE NO INDICATIONS OF SPRINKLER HEADS AT THE |
| | BOTTOM OF THE ELEVATORS. |
| | |
| | SHEET FS 5.2 OF THE MASTER PERMIT INDICATES A SPRINKLER |
| | HEAD IN THE ELEVATOR PIT. |
| | |
| | PER NFPA 13 |
| | |
| | 8.15.5 ELEVATOR HOISTWAYS AND MACHINE ROOMS. |
| | 8.15.5.1* SIDEWALL SPRAY SPRINKLERS SHALL BE INSTALLED |
| | AT THE BOTTOM |
| | OF EACH ELEVATOR HOISTWAY NOT MORE THAN 2 FT (0.61 M) |
| | ABOVE THE FLOOR OF THE PIT. |
| | 8.15.5.2 THE SPRINKLER REQUIRED AT THE BOTTOM OF THE |
| | ELEVATOR |
| | HOISTWAY BY 8.15.5.1 SHALL NOT BE REQUIRED FOR |
| | ENCLOSED, NONCOMBUSTIBLE |
| | ELEVATOR SHAFTS THAT DO NOT CONTAIN COMBUSTIBLE |
| | HYDRAULIC FLUIDS. |
| | |
| | 8.15.5.3 AUTOMATIC FIRE SPRINKLERS SHALL NOT BE |
| | REQUIRED IN ELEVATOR |
| | MACHINE ROOMS, ELEVATOR MACHINERY SPACES, CONTROL |
| | SPACES, OR |
| | HOISTWAYS OF TRACTION ELEVATORS INSTALLED IN ACCORDANCE |
| | WITH THE |
| | APPLICABLE PROVISIONS IN NFPA 101, OR THE APPLICABLE |
| | BUILDING |
| | CODE, WHERE ALL OF THE FOLLOWING CONDITIONS ARE MET: |
| | (1) THE ELEVATOR MACHINE ROOM, MACHINERY SPACE, CONTROL |
| | ROOM, CONTROL SPACE, OR HOISTWAY OF TRACTION ELEVATOR |
| | IS |
| | DEDICATED TO ELEVATOR EQUIPMENT ONLY. |
| | (2) THE ELEVATOR MACHINE ROOM, MACHINE ROOM, MACHINERY |
| | SPACE, CONTROL ROOM, CONTROL SPACE, OR HOISTWAY OF |
| | TRACTION |
| | ELEVATORS ARE PROTECTED BY SMOKE DETECTORS, OR OTHER |
| | AUTOMATIC |
| | FIRE DETECTION, INSTALLED IN ACCORDANCE WITH NFPA72. |
| | (3) THE ELEVATOR MACHINERY SPACE, CONTROL ROOM, CONTROL |
| | SPACE, |
| | OR HOISTWAY OF TRACTION ELEVATORS IS SEPARATED FROM THE |
| | REMAINDER |
| | OF THE BUILDING BY WALLS AND FLOOR/CEILING OR ROOF/ |
| | CEILING ASSEMBLIES HAVING A FIRE RESISTANCE RATING OF |
| | NOT LESS |
| | THAN THAT SPECIFIED BY THE APPLICABLE BUILDING CODE. |
| | (4) NO MATERIALS UNRELATED TO ELEVATOR EQUIPMENT ARE |
| | PERMITTED |
| | TO BE STORED IN ELEVATOR MACHINE ROOMS, MACHINERY |
| | SPACES, CONTROL ROOMS, CONTROL SPACES, OR HOISTWAYS OF |
| | TRACTION |
| | ELEVATORS. |
| | (5) THE ELEVATOR MACHINERY IS NOT OF THE HYDRAULIC |
| | TYPE. |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH ELEVATOR |
| | INFORMATION IN COMPLIANCE WITH THE CODE. |
| | |
| | |
| | |
| | 2) SHEET FS -THERE DOES NOT APPEAR TO BE A SPRINKLER |
| | HEAD AT THE TOP OF STAIRWAY # 1 |
| | |
| | IT MAY BE THAT THE STAIRWAY GOES UP TO THE ROOF BUT IT |
| | IS NOT INDICATED WITH A PLAN SHEET; SEE 2A BELOW. |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY |
| | |
| | |
| | |
| | 2A) SHEET FS 2.5 OF THE MASTER PERMIT INDICATES THE |
| | STAIRWAY # 1 GOING TO THE ROOF WITH A SPRINKER HEADS |
| | LOCATED AT THE TOP. |
| | |
| | YOU DO NOT HAVE A PLAN SHEET WHERE THE ROOF PLAN IS |
| | APPLICABLE. |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY. |
| | |
| | |
| | |
| | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |