| 2020-06-05 13:12:55 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20050567 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THIS APPEARS TO BE A LOW PRESSURE SYSTEM. THE ?? |
| | RISER LEAVING THE METER MUST BE ABLE TO HANDLE THE |
| | EXISTING AND NEW LOADS ADDED. THIS IS A SFR SO THE 2017 |
| | FLORIDA RESIDENTIAL BUILDING CODE MUST BE USED. TABLE |
| | G2413.4(1) IS FOR 0.5? W.C PRESSURE DROP. THIS TABLE |
| | INDICATES THAT THIS ?? PIPE WILL ONLY SUPPORT 360,000 |
| | BTU?S THIS PIPE IS SUPPLYING THE ENTIRE SYSTEM WHICH IS |
| | 457,000BTU?S. TFBC G2412.4 |
| | |
| | 2) PLEASE LABEL EACH PIPE SIZE ALONG THIS SYSTEM. WHERE |
| | IS THE 1 ?? TRANSITION? FBC FS 107.2.1 |
| | |
| | 3) AT THE ABOVE MENTIONED 0.5? PRESSURE DROP THE ??X2? |
| | FLEXIBLE FUEL LINE WILL ONLY SUPPLY 290,900 BTU?S TO |
| | THE GENERATOR. PLEASE ADJUST THE SIZE OF FLEX HOSE TO |
| | SUPPLY THE REQUIRED 327,000BTU?S. FBC FS 107.2.1 |
| | |
| | 4) PLEASE PROVIDE THE SPEC SHEETS FOR THE RV61 |
| | REGULATOR SHOWN ON THE DRAWING. FBC FS 107.2.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | |