| 2020-06-12 11:10:30 | PLAN REVIEW - PLUMBING |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER BUILDING - PX3169 |
| | PLANS EXAMINER 1&2 FAMILY - SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. SANITARY RISER SHOWS TWO TUBS. PLUMBING PLAN SHOWS |
| | ONE TUB AND ONE SHOWER. |
| | 107.2 CONSTRUCTION DOCUMENTS. |
| | |
| | 2. PROVIDE THE FOLLOWING STATEMENT IN PLUMBING NOTES |
| | FOR SHOWER VALVES - |
| | P2708.4SHOWER CONTROL VALVES. INDIVIDUAL SHOWER AND |
| | TUB/ SHOWER COMBINATION VALVES SHALL BE EQUIPPED WITH |
| | CONTROL VALVES OF THE PRESSURE-BALANCE, |
| | THERMOSTATIC-MIXING OR COMBINATION |
| | PRESSURE-BALANCE/THERMOSTATIC-MIXING VALVE TYPES WITH A |
| | HIGH LIMIT STOP IN ACCORDANCE WITH ASSE 1016/ASME |
| | A112.1016/CSA B125.16. THE HIGH LIMIT STOP SHALL BE SET |
| | TO LIMIT THE WATER TEMPERATURE TO NOT GREATER THAN |
| | 120?F (49?C). IN-LINE THERMOSTATIC VALVES SHALL NOT BE |
| | USED FOR COMPLIANCE WITH THIS SECTION. |
| | |
| | 3. SANITARY RISER SHOWS A DOUBLE SINK IN ONE BATH |
| | GROUP. PLUMBING PLAN SHOWS SINGLE LAV. IN EACH BATH |
| | GROUP. |
| | 107.2 CONSTRUCTION DOCUMENTS. |
| | |
| | 4. PROVIDE WATER DISTRIBUTION RISER DIAGRAHM. |
| | P2903.1WATER SUPPLY SYSTEM DESIGN CRITERIA. THE WATER |
| | SERVICE AND WATER DISTRIBUTION SYSTEMS SHALL BE |
| | DESIGNED, AND PIPE SIZES SHALL BE SELECTED SUCH THAT |
| | UNDER CONDITIONS OF PEAK DEMAND, THE CAPACITIES AT THE |
| | POINT OF OUTLET DISCHARGE SHALL NOT BE LESS THAN SHOWN |
| | IN TABLE P2903.1. |
| | |
| | 5. PROVIDE DEMENSIONS TO SHOWER PAN DETAIL PER P2709.1 |
| | AND P2709.2 |
| | P2709.1 SHOWER PAN CONSTRUCTION. FBC 107.2.1 |
| | WHERE A SHOWER RECEPTOR HAS A FINISHED CURB THRESHOLD, |
| | IT SHALL BE NOT LESS THAN 1 INCH (25 MM) BELOW THE |
| | SIDES AND BACK OF THE RECEPTOR. THE CURB SHALL BE NOT |
| | LESS THAN 2 INCHES (51 MM) AND NOT MORE THAN 9 INCHES |
| | (229 MM) DEEP WHEN MEASURED FROM THE TOP OF THE CURB TO |
| | THE TOP OF THE DRAIN. THE FINISHED FLOOR SHALL SLOPE |
| | UNIFORMLY TOWARD THE DRAIN NOT LESS THAN 1/4 UNIT |
| | VERTICAL IN 12 UNITS HORIZONTAL (2-PERCENT SLOPE) NOR |
| | MORE THAN 1/2 UNIT VERTICAL PER 12 UNITS HORIZONTAL |
| | (4-PERCENT SLOPE) AND FLOOR DRAINS SHALL BE FLANGED TO |
| | PROVIDE A WATER-TIGHT JOINT IN THE FLOOR. |
| | P2709.3 SHOWER PAN LINING INSTALLATION. |
| | LINING MATERIALS SHALL BE SLOPED ONE FOURTH UNIT |
| | VERTICAL IN 12 UNITS HORIZONTAL (2-PERCENT SLOPE) TO |
| | WEEP HOLES IN THE SUBDRAIN BY MEANS OF A SMOOTH, |
| | SOLIDLY FORMED SUBBASE, SHALL BE PROPERLY RECESSED AND |
| | FASTENED TO APPROVED BACKING SO AS NOT TO OCCUPY THE |
| | SPACE REQUIRED FOR THE WALL COVERING, AND SHALL NOT BE |
| | NAILED OR PERFORATED AT ANY POINT LESS THAN 1 INCH |
| | (25.4 MM) ABOVE THE FINISHED THRESHOLD. |
| | |
| | |
| | |
| | |
| | |