Plan Review Details - Permit 20050560
Plan Review Stops For Permit 20050560
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-06-17 Cont ID  
Sent By rmcdouga Date 2020-06-17 Time 10:44 Rev Time 0.00
Received By rmcdouga Date 2020-06-17 Time 10:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-06-02 Cont ID  
Sent By rmcdouga Date 2020-06-02 Time 08:06 Rev Time 0.00
Received By rmcdouga Date 2020-06-02 Time 08:04 Sent To  
Notes
2020-06-02 08:13:14PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT SIGNED AND SEALED WINDLOAD CALCULATIONS AND
 INSTALLATION DRAWINGS FROM A FLORIDA LICENSED ENGINEER.
 FBC 107

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-06-17 Cont ID  
Sent By rmcdouga Date 2020-06-17 Time 10:44 Rev Time 0.00
Received By rmcdouga Date 2020-06-11 Time 13:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-06-02 Cont ID  
Sent By rmcdouga Date 2020-06-02 Time 08:13 Rev Time 0.00
Received By rmcdouga Date 2020-05-20 Time 11:07 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-06-17 Cont ID  
Sent By rmcdouga Date 2020-06-17 Time 10:44 Rev Time 0.00
Received By rmcdouga Date 2020-06-17 Time 10:44 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-06-02 Cont ID  
Sent By rmcdouga Date 2020-06-02 Time 08:06 Rev Time 0.00
Received By rmcdouga Date 2020-06-02 Time 08:06 Sent To  
Notes
2020-06-02 08:12:08SUBMIT SIGNED AND SEALED WINDLOAD CALCULATIONS AND
 INSTALLATION DRAWINGS FROM A FLORIDA LICENSED ENGINEER.
 THE ENGINEER'S DIGITAL SIGNATURE IS REQUIRED ON
 ELECTRONICALLY SUBMITTED DOCUMENTS. PAPER SUBMITALS
 REQUIRE ORIGINAL SIGNATURE AND SEAL, NO COPIES OR OTHER
 FACSIMILES ARE ACCEPTABLE. FS 471 AND FAC 61G15.

Review Stop Z ZONING
Rev No 2 Status P Date 2020-06-16 Cont ID  
Sent By llouie Date 2020-06-16 Time   Rev Time 0.00
Received By llouie Date 2020-06-16 Time   Sent To  
Notes
2020-06-16 10:47:58PROPOSED SIGN WIDTH = 25.75 FT. (MAX. ALLOWED = 25.8
 FT.)
  
 PROPOSED SIGN HEIGHT = 12 INCHES (MAX. ALLOWED = 36
 INCHES)

Review Stop Z ZONING
Rev No 1 Status F Date 2020-05-21 Cont ID  
Sent By llouie Date 2020-05-21 Time   Rev Time  
Received By llouie Date 2020-05-21 Time   Sent To  
Notes
2020-05-21 17:03:12** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) WIDTH OF THE SIGN CANNOT EXCEED 60% OF THE WIDTH OF
 THE BUILDING FACADE. PROPOSED WALL SIGN EXCEEDS THIS
 REQUIREMENT (64%). [ZLDR S.94-215(O)(4)]
  
  
 NOTES:
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * MAXIMUM ALLOWABLE SIGN HEIGHT PERMITTED: 36 INCHES.
  
 * MAXIMUM ALLOWABLE SIGN WIDTH: 60% OF THE BUILDING
 FACADE.
  
 * ZONE: CMUD - CORE SUBDISTRICT
  