| Plan Review Stops For Permit 20050553 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2020-07-06 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2020-07-06 |
Time |
11:54 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2020-07-06 |
Time |
11:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2020-06-29 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2020-06-29 |
Time |
11:40 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2020-06-29 |
Time |
11:29 |
Sent To |
|
|
| Notes |
| 2020-06-29 11:42:12 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: THE COMMENTS FROM | | | THE FIRST REVIEW HAVE NOT BEEN ADDRESSED. | | | | | | 1) THE LATERAL WIND PRESSURE THAT IS MARKED ON THE | | | GENERATOR PAD DRAWING FOR RG038 OF 36 PSF IS NOT | | | ADEQUATE FOR THIS PROJECT. RISK CATEGORY II IN EXPOSURE | | | C IN PALM BEACH COUNTY REQUIRES 41.65 PSF. FBC R301 | | | | | | 2) THE ENGINEER'S DIGITAL SIGNATURE AND SEAL IS | | | REQUIRED ON THE GENERATOR PAD DRAWING. FS 471 & FAC | | | 61G15 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2020-06-10 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2020-06-10 |
Time |
11:23 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2020-06-10 |
Time |
11:17 |
Sent To |
|
|
| Notes |
| 2020-06-10 11:35:05 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE LATERAL WIND PRESSURE THAT IS MARKED ON THE | | | GENERATOR PAD DRAWING FOR RG038 OF 36 PSF IS NOT | | | ADEQUATE FOR THIS PROJECT. RISK CATEGORY II IN EXPOSURE | | | C IN PALM BEACH COUNTY REQUIRES 41.65 PSF. FBC R301 | | | | | | 2) THE ENGINEER'S DIGITAL SIGNATURE AND SEAL IS | | | REQUIRED ON THE GENERATOR PAD DRAWING. FS 471 & FAC | | | 61G15 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2020-07-02 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-07-02 |
Time |
11:27 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-07-02 |
Time |
11:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2020-06-12 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-06-12 |
Time |
12:44 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-06-12 |
Time |
12:41 |
Sent To |
|
|
| Notes |
| 2020-06-12 13:08:46 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | | 5TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, | | | PART VIII ELECTRICAL | | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) VALUE FOR THIS SIZE OF GENERATOR AND TWO TRANSFER | | | SWITCHES IS LOW. (26,983) (38KW, 2-200A TS) | | | | | | 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF | | | THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF | | | BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS, | | | MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE | | | UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE | | | DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED, | | | QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS | | | (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE | | | BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION | | | OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT | | | VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, | | | MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK, | | | ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS, | | | OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. | | | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED | | | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES | | | (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY | | | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT | | | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2020-07-06 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2020-07-06 |
Time |
13:42 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2020-07-06 |
Time |
11:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2020-07-02 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-07-02 |
Time |
11:27 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-06-17 |
Time |
14:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2020-06-12 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-06-12 |
Time |
13:08 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-05-27 |
Time |
10:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2020-07-06 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2020-07-06 |
Time |
12:01 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2020-07-06 |
Time |
12:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2020-06-29 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2020-06-29 |
Time |
11:40 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2020-06-29 |
Time |
11:40 |
Sent To |
|
|
| Notes |
| 2020-06-29 11:40:43 | THE GENERATOR PAD DRAWING IS REQUIRED TO BE DIGITALLY | | | SIGNED AND SEALED BY THE ENGINEER. FS 471 & FAC 61G15 |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2020-06-10 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2020-06-10 |
Time |
11:23 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2020-06-10 |
Time |
11:23 |
Sent To |
|
|
| Notes |
| 2020-06-10 11:25:19 | THE GENERATOR PAD DRAWING IS REQUIRED TO BE DIGITALLY | | | SIGNED AND SEALED BY THE ENGINEER. FS 471 & FAC 61G15 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
kalexand |
Date |
2020-06-05 |
Time |
|
Rev Time |
|
| Received By |
|
Date |
2020-06-05 |
Time |
|
Sent To |
I |
|
| Notes |
|
|