Plan Review Details - Permit 20050532
Plan Review Stops For Permit 20050532
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2020-08-17 Cont ID  
Sent By ccole Date 2020-08-17 Time 09:31 Rev Time 0.00
Received By ccole Date 2020-08-17 Time 09:31 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2020-08-11 Cont ID  
Sent By ccole Date 2020-08-11 Time 11:55 Rev Time 0.00
Received By ccole Date 2020-08-11 Time 11:19 Sent To  
Notes
2020-08-11 11:57:202ND REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20050532
 8/11/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE REVISED GAS ISOMETRIC IS LACKING THESE DETAILS
 AND INFORMATION. PLEASE REVISE PER THE NOTES BELOW:
  
 A) SHOW HOW THE GAS PIPE SUPPLYING THE APPLIANCES IN
 THE HOUSE IS CONNECTING TO THE METER. INDICATE THE TYPE
 AND SIZE OF SUPPLY PIPE, AND TOTAL LENGTH OF THE RUN TO
 THE MOST REMOTE OUTLET.- SECTION G2413.3 FBC RES.
 B) PROVIDE THE INDIVIDUAL AND TOTAL LOADS OF ALL
 GAS-FIRED APPLIANCES AND EQUIPMENT BEING SUPPLIED BY
 THE METER AND METER'S TOTAL CAPACITY AS NOTED IN THE
 SUBMITTED LETTER- SECTION G2413.2 FBC RES.
 C) INDICATE WHICH PIPE SIZING TABLE WAS USED FOR THE
 NEW PE LINE TO THE POOL HEATER- SECTION G2413.4 FBC
 RES.
 2) AS PREVIOUSLY REQUESTED, SUBMIT SPECS FOR THE POOL
 WATER HEATER INDICATING THE BTUH LOAD AND REQUIRED GAS
 PRESSURE- G2441.1 FBC RES. PLEASE NOTE THE WORD ?POOL?
 WAS ADDED FOR CLARITY.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-07-17 Cont ID  
Sent By ccole Date 2020-07-17 Time 15:11 Rev Time 0.00
Received By ccole Date 2020-07-17 Time 14:26 Sent To  
Notes
2020-07-17 15:12:291ST REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20050532
 7/17/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) GAS ISOMETRIC DRAWING: THE DRAWING IS INCOMPLETE. IN
 ORDER TO ENSURE A SAFE OPERATING SYSTEM, THE DRAWING
 MUST BE MODIFIED TO SHOW THE ENTIRE GAS PIPING SYSTEM
 INCLUDING THE MAIN SUPPLY PIPE AT THE METER, LOCATION
 OF TEE, AND THE TOTAL PIPING RUNS FROM THE METER TO THE
 MOST REMOTE OUTLET. EACH BRANCH LINE SIZE AND LENGTH
 AND APPLIANCE BTUH LOAD SHALL BE INDICATED ON THE
 DRAWING - SECTIONS G2412.3 & G2412.4 FBC RES.
 A) PROVIDE THE TOTAL DEVELOPED LENGTH OF THE SYSTEM
 FROM THE METER TO THE MOST REMOTE OUTLET- SECTIONS
 G2413.4.1, G2413.4.2 & G2413.4.3 AND THE TOTAL LENGTH
 OF THE PE FROM THE TEE TO THE POOL HEATER.
 B) INDICATE WHICH PIPE SIZING TABLE WAS USED PER
 SECTION G2413.4
  
 2) PROVIDE A FLAT LINE DRAWING OR SITE PLAN DRAWING
 SHOWING THE LOCATION OF THE METER AND THE UNDERGROUND
 PE PIPING RUN TO THE POOL HEATER. INDICATE A TRACE WIRE
 BE INSTALLED PER SECTION G2415.17.3
  
 3) SUBMIT SPECS FOR THE WATER HEATER INDICATING THE
 BTUH LOAD AND REQUIRED GAS PRESSURE- G2441.1 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-08-11 Time   Rev Time 0.00
Received By lmarchan Date 2020-08-06 Time 14:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-07-17 Time   Rev Time 0.00
Received By lmarchan Date 2020-07-08 Time 10:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status N Date 2020-08-17 Cont ID  
Sent By ccole Date 2020-08-17 Time 09:31 Rev Time 0.00
Received By ccole Date 2020-08-17 Time 09:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-08-11 Cont ID  
Sent By ccole Date 2020-08-11 Time 11:55 Rev Time 0.00
Received By ccole Date 2020-08-11 Time 11:19 Sent To  
Notes
2020-08-11 11:55:30PLUMBING FOR POOL HEATER UNDER PERMIT-20040743

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-07-17 Cont ID  
Sent By ccole Date 2020-07-17 Time 15:12 Rev Time 0.00
Received By ccole Date 2020-07-17 Time 14:26 Sent To  
Notes
2020-07-17 15:15:44PLUMBING FOR POOL HEATER UNDER PERMIT-20040743

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2020-08-17 Cont ID  
Sent By ccole Date 2020-08-17 Time 09:31 Rev Time 0.00
Received By ccole Date 2020-08-17 Time 09:31 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2020-07-17 Cont ID  
Sent By ccole Date 2020-07-17 Time 15:13 Rev Time 0.00
Received By ccole Date 2020-07-17 Time 14:26 Sent To  
Notes
***NONE***