| 2020-06-16 13:38:09 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20050520 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) MASTER PROJECT NUMBER 20030300 DOES NOT LIST A GAS |
| | REVIEW. PLEASE SUBMIT THE GAS PERMIT APPLICATION FOR |
| | THIS PROJECT. FBC FS 107.2.1 |
| | |
| | 2) PLEASE PROVIDE GAS TABLE NUMBERS USED TO SIZE THIS |
| | SYSTEM. FBC FS 107.2.1 |
| | |
| | 3) WORDING ABOUT THE NEW GALV. PIPE AT METER ON THE |
| | BOTTOM OF THE PAGE HAS BEEN CUT OFF. PLEASE REWORK THIS |
| | AREA SO WE CAN READ THE COMMENT. PLEASE SHOW A DETAIL |
| | DRAWING OF THE METER AND ALL THE CONNECTIONS TO IT, |
| | INCLUDE PIPE SIZES AND MATERIAL. FBC FS 107.2.1. |
| | |
| | 4) PLEASE PROVIDE SPEC SHEETS ON THE GENERATOR AND NEW |
| | REGULATORS USED FOR THIS PROJECT. INCLUDE MODEL |
| | NUMBERS. FBC FS 107.2.1 |
| | |
| | 5) HOW IS GAS CONNECTING TO GENERATOR? IF USING A FLEX |
| | HOSE PLEASE SUBMIT SPEC SHEET ALONG WITH THE SIZE AND |
| | LENGTH OF HOSE. VERIFY WHICH PRESSURE DROP WILL BE USED |
| | ON THE SPEC SHEET. FBC FS 107.2.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL. 33401 |
| | 561-805-6728 |
| | [email protected] |
| | |