| 2020-08-26 16:27:32 | 2ND REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20050504 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | THIS IS AN ADDITION TO AN EXISTING GAS LINE. WE NEED TO |
| | MAKE SURE THAT THE EXISTING GAS LINE CAN SUPPORT THE |
| | ADDITIONAL 330,000 BTU?S FOR THE NEW GENERATOR. FOR |
| | THIS WE NEED THE DEVELOPED LENGTH TO THE MOST REMOTE |
| | GAS APPLIANCE. THIS COULD BE EITHER ON THE EXISTING GAS |
| | LINE OR IT COULD BE THE NEW GAS LINE IF IT BECOMES THE |
| | MOST REMOTE APPLIANCE ON THE GAS LINE. WE ALSO NEED THE |
| | OPERATING PRESSURE OF THE EXISTING SYSTEM. I CANNOT |
| | SIZE THE NEW LINE UNTIL I HAVE THIS INFORMATION. |
| | |
| | 1) GAS TABLE PROVIDED IS FOR A 2PSI SYSTEM BUT THE GAS |
| | RISER DIAGRAM INDICATES THE NEW PIPING IS 12? WC. |
| | PLEASE PROVIDE CORRECTED INFORMATION. FBC FS 107.2.1 |
| | |
| | 2) PLEASE INDICATE NEW PIPING MATERIAL ON THE RISER |
| | DIAGRAM. FBC FS 107.2.1 |
| | |
| | 3) PLEASE SPECIFY EXISTING GAS METER?S OPERATING |
| | PRESSURE AND PIPE MATERIAL AND SIZE OF EXISTING PIPE |
| | LEAVING THE METER ( THE PIPE THAT YOU SPLICE INTO). FBC |
| | FS 107.2.1 |
| | |
| | 4) PLEASE PROVIDE THE LONGEST DEVELOPED LENGTH TO THE |
| | MOST REMOTE APPLIANCE ON THIS GAS LINE. FBC FS 107.2.1 |
| | |
| | 5) PROVIDE SPEC SHEETS ON REGULATORS USED AND SHOW THEY |
| | ON THE GAS RISER DIAGRAM. FBC FS 107.2.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | |