Plan Review Details - Permit 20050331
Plan Review Stops For Permit 20050331
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-08-31 Cont ID  
Sent By jwitmer Date 2020-08-31 Time 14:02 Rev Time 0.00
Received By jwitmer Date 2020-08-31 Time 13:42 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-07-27 Cont ID  
Sent By jwitmer Date 2020-07-27 Time 14:44 Rev Time 0.00
Received By jwitmer Date 2020-07-27 Time 13:30 Sent To  
Notes
2020-07-27 14:34:31WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20050331
 ADD: PORTE COCHERE / HIGH/ LOW
 CONT: MCGEE CORP.
 TEL: 704-893-3744
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JULY 27TH/ 2020
 ACTION: DENIED
  
 1) PLEASE NOTE THAT NONE OF THE STRUCTURAL PLANS REFER
 TO A MINIMUM BUILDING TYPE FOR THE PORTE COCHERE. UNDER
 THE RECLADDING PERMIT 19110539 THIS WAS A COMMENT SINCE
 THE PORTE COCHERE WAS ALSO SHOWN ON THAT PLAN. IT WAS
 DECIDED TO FIRE SPRINKLER THE PORTE COCHERE CANOPY THIS
 WOULD ALLOW BOTH THE EXISTING STRUCTURE AND THE NEW
 PORTE COCHERE TO BE CONSIDERED TYPE V-B CONSTRUCTION.
 BASICALLY AN ADDITION TO THE EXISTING BUILDING, NO
 ASSUMED PROPERTY LINE BETWEEN BUILDINGS. PLEASE NOTE ON
 THE PORTE COCHERE THE MINIMUM CONSTRUCTION TYPE AS V-B
 SPRINKLERED. SPRINKLER PERMIT, REVIEW AND FEES ARE
 UNDER SEPARATE PERMIT.
  
 2) THE SUBMITTED STRUCTURAL SHEETS BY ASHUTOSH PATEL P.
 E. NEED AN DIGITAL SIGNATURE. 61G15-23.005 PROCEDURES
 FOR SIGNING AND SEALING ELECTRONICALLY TRANSMITTED
 PLANS (DIGITAL SIGNATURES), SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS.
  
 FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A
 SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE
 OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON
 DIGITALLY SIGNED AND SEALED ENGINEERING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 3) WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS
 REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION FOR FIELD WIELDING, ON THE JOB-SITE
 WIELDING. THIRD PARTY CERTIFICATION WILL BE REQUIRED.
 REPORTS SUBMITTED TO BUILDING INSPECTOR AT TIME OF
 FRAMING INSPECTION.
 2017 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT
 561-805-6666.
  
 4) THE STRUCTURAL FOUNDATION PLAN UNDER GENERAL NOTE 14
 GIVES THE WIND DESIGN CRITERIA BUT NOT THE PRESSURES
 FOR THE ROOF DECK. COMPONENTS AND CLADDING 1609.6.4.4.1
 OF THE 2017 FBC-B.
  
 5A) PLEASE SUBMIT ROOFING PRODUCT APPROVALS FOR THE
 ROOF DECK. 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE
 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY
 OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES,
  
 5B) PLEASE HIGHLIGHT (CIRCLE) THE TYPE OF METAL PANEL
 TO BE INSTALLED, ALLOWABLE SPANS AND ASSOCIATED
 PRESSURES. FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL
 ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR
 ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS,
 IF ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3.
  
 5C) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2020-08-18 Cont ID  
Sent By fgiaquin Date 2020-08-18 Time 22:08 Rev Time 0.00
Received By fgiaquin Date 2020-08-18 Time 21:20 Sent To  
Notes
2020-08-18 22:08:17NO ELECTRICAL WORK REVIEWED OR APPROVED

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-08-26 Cont ID  
Sent By pleduc Date 2020-08-26 Time   Rev Time 0.00
Received By pleduc Date 2020-08-26 Time 15:15 Sent To  
Notes
2020-08-26 15:18:15THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE FIRE SPRINKLER SYSTEM SHALL BE MAINTAINED
 THROUGHOUT CONSTRUCTION, INCLUDING DEMO.
  
  
 2) ANY AND ALL WORK ON THE FIRE SPRINKLER SYSTEM SHALL
 BE DONE UNDER SEPARATE SHOP DRAWINGS AND BY CERTIFIED
 FIRE SPRINKLER CONTRACTORS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-07-22 Cont ID  
Sent By pleduc Date 2020-07-22 Time   Rev Time 0.00
Received By pleduc Date 2020-07-22 Time 13:31 Sent To  
Notes
2020-07-22 16:32:05THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE FIRE SPRINKLER SYSTEM SHALL BE MAINTAINED
 THROUGHOUT CONSTRUCTION, INCLUDING DEMO.
  
  
 2) ANY AND ALL WORK ON THE FIRE SPRINKLER SYSTEM SHALL
 BE DONE UNDER SEPARATE SHOP DRAWINGS AND BY CERTIFIED
 FIRE SPRINKLER CONTRACTORS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-09-08 Cont ID  
Sent By lmarchan Date 2020-09-08 Time 10:31 Rev Time 0.00
Received By lmarchan Date 2020-08-25 Time 14:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-08-18 Cont ID  
Sent By fgiaquin Date 2020-08-18 Time 22:08 Rev Time 0.00
Received By fgiaquin Date 2020-07-21 Time 15:03 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2020-07-27 Cont ID  
Sent By jwitmer Date 2020-07-27 Time 14:36 Rev Time 0.00
Received By jwitmer Date 2020-07-27 Time 13:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2020-09-03 Cont ID  
Sent By jwitmer Date 2020-09-03 Time 07:11 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-08-12 Cont ID  
Sent By hmoser Date 2020-08-12 Time 08:57 Rev Time 0.00
Received By hmoser Date 2020-08-12 Time 08:47 Sent To  
Notes
2020-08-12 08:57:50NO AIR CONDITIONING PLAN SUBMITTED HM.

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-09-03 Cont ID  
Sent By lcrespo Date 2020-09-03 Time 06:23 Rev Time 0.00
Received By lcrespo Date 2020-09-03 Time 06:23 Sent To  
Notes
2020-09-03 06:23:3809/03/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2020-08-12 Cont ID  
Sent By abelisle Date 2020-08-12 Time 19:08 Rev Time 0.00
Received By abelisle Date 2020-08-12 Time 17:43 Sent To  
Notes
2020-08-12 19:08:488/12/2020 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-08-31 Cont ID  
Sent By jwitmer Date 2020-08-31 Time 14:03 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2020-08-25 14:43:42DIGITALLY SIGNED FILE IN 'SIGNATURES' FOLDER

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-07-27 Cont ID  
Sent By jwitmer Date 2020-07-27 Time 14:36 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2020-07-27 14:36:10THE SUBMITTED STRUCTURAL SHEETS BY ASHUTOSH PATEL P. E.
 NEED AN DIGITAL SIGNATURE. 61G15-23.005 PROCEDURES FOR
 SIGNING AND SEALING ELECTRONICALLY TRANSMITTED PLANS
 (DIGITAL SIGNATURES), SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS. FLORIDA ADMINISTRATIVE CODE 61G15-23.005
 (3)(C) A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE?S SIGNATURE SHALL NOT BE
 USED ON DIGITALLY SIGNED AND SEALED ENGINEERING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  

Review Stop Z ZONING
Rev No 2 Status P Date 2020-09-03 Cont ID  
Sent By awooten Date 2020-09-03 Time   Rev Time 0.00
Received By awooten Date 2020-09-03 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2020-08-11 Cont ID  
Sent By awooten Date 2020-08-11 Time   Rev Time  
Received By awooten Date 2020-08-11 Time   Sent To  
Notes
***NONE***