Plan Review Details - Permit 20050293
Plan Review Stops For Permit 20050293
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-05-19 Cont ID  
Sent By rmcdouga Date 2020-05-19 Time 15:32 Rev Time 0.00
Received By rmcdouga Date 2020-05-19 Time 15:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-05-19 Cont ID  
Sent By jleahy Date 2020-05-19 Time 15:30 Rev Time 0.00
Received By jleahy Date 2020-05-19 Time 12:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-05-29 Time   Rev Time 0.00
Received By lmarchan Date 2020-05-28 Time 08:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-05-26 Time   Rev Time 0.00
Received By jgomez Date 2020-05-09 Time 16:49 Sent To  
Notes
2020-05-18 16:49:35CONVERTED TO DIGITAL. JG.
2020-05-11 13:51:1505/11/2020 TALKED TO SAMANTHA. NO FEES PAID. PLAN
 REVIEWS NOT PERFORMED. NOT CONTACT INFO. SENT TO
 LIBRARY UNDER "FEES NO PAID". JG.
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-05-29 Cont ID  
Sent By ccole Date 2020-05-29 Time 14:23 Rev Time 0.00
Received By ccole Date 2020-05-29 Time 14:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-05-26 Cont ID  
Sent By ccole Date 2020-05-26 Time 14:17 Rev Time 0.00
Received By ccole Date 2020-05-26 Time 13:18 Sent To  
Notes
2020-05-26 14:19:001ST REVIEW FBC-2017 PLUMBING
 PERMIT 20050293
 5/26/2020
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE AN ENLARGED DRAWING OF THE NEW SHOWER THAT
 SHOWS THE DIMENSIONS FROM THE REAR FINISHED WALL OUT TO
 THE CENTERLINE OF THE THRESHOLD. REVIEW SECTION P2708.1
 FBC RES. PRINTED BELOW AND SHOW COMPLIANCE:
  
 SHOWER COMPARTMENTS SHALL HAVE NOT LESS THAN 900 SQUARE
 INCHES OF INTERIOR CROSS-SECTIONAL AREA. SHOWER
 COMPARTMENTS SHALL BE NOT LESS THAN 30 INCHES IN
 MINIMUM DIMENSION MEASURED FROM THE FINISHED INTERIOR
 DIMENSION OF THE SHOWER COMPARTMENT, EXCLUSIVE OF
 FIXTURE VALVES, SHOWER HEADS, SOAP DISHES, AND SAFETY
 GRAB BARS OR RAILS. THE MINIMUM REQUIRED AREA AND
 DIMENSION SHALL BE MEASURED FROM THE FINISHED INTERIOR
 DIMENSION AT A HEIGHT EQUAL TO THE TOP OF THE THRESHOLD
 AND AT A POINT TANGENT TO ITS CENTERLINE AND SHALL BE
 CONTINUED TO A HEIGHT OF NOT LESS THAN 70 INCHES (1778
 MM) ABOVE THE SHOWER DRAIN OUTLET. HINGED SHOWER DOORS
 SHALL OPEN OUTWARD.
  
 2) INDICATE ON THE DRAWING THE LOCATION OF THE SHOWER
 DRAIN. PLEASE NOTE IF THE NEW DRAIN IS LOCATED IN THE
 CENTER OF THE SHOWER, THE HORIZONTAL DISTANCE FROM THE
 CENTERLINE OF THE NEW SHOWER DRAIN OUTLET TO THE
 CENTERLINE OF THE INLET OF THE EXISTING TRAP SHALL NOT
 EXCEED 30"- SECTION P3201.6 FBC RES. PLEASE NOTE THAT
 THE SHOWER DRAIN OUTLET SHALL NOT BE LESS THAN 1-1/2"
 IN DIAMETER- SECTION P2708.2 FBC RES.
  
 3) PROVIDE A DETAIL FOR INSTALLATION OF THE NEW SHOWER
 RECEPTOR INDICATING THE HEIGHT OF THE NEW CURB
 THRESHOLD AND THE SLOPE OF THE FINISHED FLOOR TO THE
 DRAIN. INDICATE THE TYPE OF SHOWER RECEPTOR LINER TO BE
 USED- SECTIONS P2709.1 AND P2709.2 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2020-05-29 Cont ID  
Sent By ccole Date 2020-05-29 Time 14:23 Rev Time 0.00
Received By ccole Date 2020-05-29 Time 14:13 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2020-05-19 Cont ID  
Sent By rmcdouga Date 2020-05-19 Time 15:33 Rev Time 0.00
Received By rmcdouga Date 2020-05-19 Time 15:33 Sent To  
Notes
2020-05-18 16:50:19NO ARCHITECT OR ENGINEER. JG.