Plan Review Details - Permit 20050207
Plan Review Stops For Permit 20050207
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-06-21 Cont ID  
Sent By jwitmer Date 2020-06-21 Time 14:15 Rev Time 0.00
Received By jwitmer Date 2020-06-21 Time 14:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-06-25 Cont ID  
Sent By jleahy Date 2020-06-25 Time 10:48 Rev Time 0.00
Received By jleahy Date 2020-06-25 Time 10:40 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-06-10 Cont ID  
Sent By pleduc Date 2020-06-10 Time   Rev Time 0.00
Received By pleduc Date 2020-06-10 Time 14:46 Sent To  
Notes
2020-06-10 14:47:29ELECTICAL WORK PER NFPA 70
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-07-16 Cont ID  
Sent By lmarchan Date 2020-07-16 Time 11:44 Rev Time 0.00
Received By lmarchan Date 2020-06-09 Time 16:01 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-07-16 Cont ID  
Sent By shill Date 2020-07-07 Time 12:18 Rev Time 0.00
Received By medwards Date 2020-07-16 Time 10:45 Sent To  
Notes
2020-07-16 10:47:15PAPER DRAWINGS ARE IN THE OFFICE AND ON FILE.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
2020-07-07 12:19:51ORIGINAL ENGINEERING TO BE REVIEWED AFTER ALL REVIEWS
 HAVE PASSED
 PAPER ENGINEERING IS CONSISTENT WITH PLANS IN
 PROJECTDOX
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-06-25 Cont ID  
Sent By jleahy Date 2020-06-25 Time 10:51 Rev Time 0.00
Received By jleahy Date 2020-06-25 Time 10:50 Sent To  
Notes
2020-06-25 10:57:58CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PLAN NOT DIGITALLY SIGNED.
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 IS REQUIRED TO BE SIGNED (AND SEALED FOR DESIGN
 PROFESSIONALS) BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED OR SIGNED/SEALED
 PAPER SET MAY BE SUPPLIED TO THE BUILDING DEPARTMENT
 WHEN ALL TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481

Review Stop Z ZONING
Rev No 1 Status P Date 2020-07-15 Cont ID  
Sent By awooten Date 2020-07-15 Time   Rev Time  
Received By awooten Date 2020-07-15 Time   Sent To  
Notes
***NONE***