Plan Review Details - Permit 20050175
Plan Review Stops For Permit 20050175
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-06-30 Cont ID  
Sent By jwitmer Date 2020-06-30 Time 13:59 Rev Time 0.00
Received By jwitmer Date 2020-06-30 Time 13:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-06-11 Cont ID  
Sent By jwitmer Date 2020-06-11 Time 10:27 Rev Time 0.00
Received By jwitmer Date 2020-06-11 Time 09:56 Sent To  
Notes
2020-06-11 10:25:012017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20050175
 ADD: 1411 N. FLAGLER DR. 2ND FLOOR
 CONT: WESTBROOKE CORP.
 TEL: 561-394-4126
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. JUNE 11TH/ 2020
 ACTION: DENIED
  
 1) SHEET A1.1:
  
 1A) IN THE BOTTOM LEFT CORNER OF THE PLAN THERE IS AN
 AREA THAT STATES WORK AREA BETWEEN STORAGE ROOM 2003
 AND CLEAN UTILITY ROOM 2034, HERE IT LOOKS LIKE IT IS A
 REPLACEMENT OF DOOR AND FRAME. THERE IS A
 IDENTIFICATION TAG 1 BUT THERE IS NO DOOR SCHEDULE, OR
 NOTE IDENTIFYING WHAT IS BEING IDENTIFIED. DOOR SIZE,
 TYPE, REQUIRED RATING, HARDWARE, ETC?
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 1B) JUST BELOW THE AREA IDENTIFIED IN COMMENT # 1 THERE
 IS A SERVICE ELEVATOR IDENTIFIED AS T2006, JUST BELOW
 THE ELEVATOR IT WOULD APPEAR ON THE EXTERIOR OF THE
 BUILDING THERE IS A SECOND AREA THAT STATES WORK AREA?
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 2) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-06-30 Cont ID  
Sent By pleduc Date 2020-06-30 Time   Rev Time 0.00
Received By pleduc Date 2020-06-30 Time 10:15 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-06-03 Cont ID  
Sent By pleduc Date 2020-06-03 Time   Rev Time 0.00
Received By pleduc Date 2020-06-03 Time 14:13 Sent To  
Notes
2020-06-03 14:18:57THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS NO SCOPE OF WORK
  
 THE TITLE BLOCK INDICATES DOOR REPAIR, THE APPLICATION
 INDICATES REPLACEMENT,
  
 PLEASE PROVIDE SPECIFIC DETAILS
  
  
 2) THERE IS NO INDICATION ON THE PLAN SHEET WHERE THE
 WORK IS TAKING PLACE.
  
 PLEASE PROVIDE A CLEAR INDICATION ON THE PLAN SHEET
 WHERE THE WORK IS LOCATED.
  
  
 3) THERE IS NO DOOR SCHEDULE INCLUDING FIRE RATINGS,
 CLOSERS, AND APPLICABLE CODE COMPLIANT HARDWARE.
  
 PLEASE PROVIDE.
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-06-30 Time 14:00 Rev Time 0.00
Received By cpuell Date 2020-06-29 Time 11:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-06-11 Time 10:27 Rev Time 0.00
Received By lmarchan Date 2020-06-01 Time 08:43 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-06-30 Cont ID  
Sent By jwitmer Date 2020-06-30 Time 13:58 Rev Time 0.00
Received By jwitmer Date 2020-06-30 Time 13:45 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-06-11 Cont ID  
Sent By jwitmer Date 2020-06-11 Time 10:25 Rev Time 0.00
Received By jwitmer Date 2020-06-11 Time 10:25 Sent To  
Notes
***NONE***