Plan Review Details - Permit 20050165
Plan Review Stops For Permit 20050165
Review Stop E ELECTRICAL
Rev No 4 Status P Date 2021-01-08 Cont ID  
Sent By jleahy Date 2021-01-08 Time 12:55 Rev Time 0.00
Received By jleahy Date 2021-01-08 Time 12:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-11-06 Cont ID  
Sent By equinone Date 2020-11-06 Time 11:14 Rev Time 0.00
Received By equinone Date 2020-11-06 Time 11:14 Sent To  
Notes
2020-11-06 11:15:40PREVIOUS COMMENTS:
  
 PLANS SUBMITTED ARE ONLY COPIES NEED TO DIGITALLY
 SIGNED BY PERSON RESPONSIBLE FOR THE PLANS. ---
 COMPLETED
  
 PLAN IS REQUIRED TO BE SIGNED AND SEALED BY A DESIGN
 PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER. FS
 471.003(2)(H); 471.025; FBC 107.2.1 ---- COMPLETED
  
 ENRIQUE QUINONEZ

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-08-18 Cont ID  
Sent By jleahy Date 2020-08-18 Time 14:56 Rev Time 0.00
Received By jleahy Date 2020-08-18 Time 14:56 Sent To  
Notes
2020-08-18 14:57:11ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PLANS SUBMITTED ARE ONLY COPIES NEED TO DIGITALLY
 SIGNED BY PERSON RESPONSIBLE FOR THE PLANS.
  
 PLAN IS REQUIRED TO BE SIGNED AND SEALED BY A DESIGN
 PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER. FS
 471.003(2)(H); 471.025; FBC 107.2.1

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-07-09 Cont ID  
Sent By jleahy Date 2020-07-09 Time 11:04 Rev Time 0.00
Received By jleahy Date 2020-07-09 Time 11:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-01-27 Cont ID  
Sent By lmarchan Date 2021-01-27 Time 14:30 Rev Time 0.00
Received By lmarchan Date 2020-12-28 Time 09:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-11-20 Cont ID  
Sent By lmarchan Date 2020-11-20 Time 13:51 Rev Time 0.00
Received By lmarchan Date 2020-10-30 Time 10:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-08-31 Cont ID  
Sent By lmarchan Date 2020-08-31 Time 10:39 Rev Time 0.00
Received By lmarchan Date 2020-08-03 Time 10:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-07-09 Cont ID  
Sent By jleahy Date 2020-07-09 Time 11:04 Rev Time 0.00
Received By jleahy Date 2020-06-18 Time 09:59 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2021-01-08 Cont ID  
Sent By jleahy Date 2021-01-08 Time 12:55 Rev Time 0.00
Received By jleahy Date 2021-01-08 Time 12:55 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-11-20 Cont ID  
Sent By lmarchan Date 2020-11-20 Time 13:51 Rev Time 0.00
Received By lmarchan Date 2020-11-20 Time 13:51 Sent To  
Notes
2020-11-06 11:18:03ELECTRICAL PLANS HAVE VALID DIGITAL SIGNATURE. EQ

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-08-31 Cont ID  
Sent By medwards Date 2020-08-31 Time 10:25 Rev Time 0.00
Received By medwards Date 2020-08-31 Time 10:23 Sent To  
Notes
2020-08-31 10:27:02PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A
 DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY
 VERIFICATION. PROVIDE CORRECTION. ALTERNATIVELY, A
 SIGNED/SEALED PAPER SET MAY BE SUPPLIED TO THE BUILDING
 DEPARTMENT WHEN ALL TRADES ARE APPROVED. WPB FBC 107.1;
 FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-07-09 Cont ID  
Sent By jleahy Date 2020-07-09 Time 11:04 Rev Time 0.00
Received By jleahy Date 2020-07-09 Time 11:04 Sent To  
Notes
2020-07-09 11:05:14CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 SIGNATURE AND PAGE ARE A COPY WHICH IS OK, BUT WE NEED
 A CLEAN COPY OF THE PLAN FOR STAMPING. PLEASE UPLOAD A
 CLEAN COPY OF THE PLANS AND PLACE THE ORIGINALS IN THE
 SIGNATURE FILE, WE WILL USE THE NEW FOR STAMPING..

Review Stop Z ZONING
Rev No 4 Status P Date 2021-01-27 Cont ID  
Sent By jroach Date 2021-01-27 Time 13:48 Rev Time 0.00
Received By jroach Date 2021-01-27 Time 13:48 Sent To  
Notes
2021-01-27 13:48:29SCOPE OF THIS REVIEW IS LIMITED TO SITE LIGHTING ONLY!
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 3 Status F Date 2020-11-20 Cont ID  
Sent By jroach Date 2020-11-20 Time 13:40 Rev Time 0.00
Received By jroach Date 2020-11-20 Time 13:40 Sent To  
Notes
2020-11-20 13:40:54ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 11.20.2020
 PERMIT NO.: 20050165
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. [ SATISFIED ] - WHAT IS THE DIFFERENCE BETWEEN THIS
 PERMIT AND THAT WHICH HAS BEEN SUBMITTED UNDER PERMIT
 #20050167? THE DESCRIPTION, PLANS, ETC. APPEAR TO ALL
 BE THE SAME.
  
 2. [ NOT SATISFIED ] - PHOTOMETRIC LEVELS SHALL BE
 PROVIDED ALONG ALL PROPERTY LINES. LEVELS SHALL NOT
 EXCEED 1.0 FOOTCANDLES WHEN MEASURED AT THE PROPERTY
 LINE.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG

Review Stop Z ZONING
Rev No 2 Status F Date 2020-08-05 Cont ID  
Sent By jroach Date 2020-08-05 Time 15:57 Rev Time 0.00
Received By jroach Date 2020-08-05 Time 15:57 Sent To  
Notes
2020-08-05 15:57:17ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 08.05.2020
 PERMIT NO.: 20050165
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. [ SATISFIED ] - WHAT IS THE DIFFERENCE BETWEEN THIS
 PERMIT AND THAT WHICH HAS BEEN SUBMITTED UNDER PERMIT
 #20050167? THE DESCRIPTION, PLANS, ETC. APPEAR TO ALL
 BE THE SAME.
  
 2. [ NOT SATISFIED ] - PHOTOMETRIC LEVELS SHALL BE
 PROVIDED ALONG ALL PROPERTY LINES. LEVELS SHALL NOT
 EXCEED 1.0 FOOTCANDLES WHEN MEASURED AT THE PROPERTY
 LINE.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG

Review Stop Z ZONING
Rev No 1 Status F Date 2020-06-29 Cont ID  
Sent By jroach Date 2020-06-29 Time 15:00 Rev Time 0.00
Received By jroach Date 2020-06-29 Time 15:00 Sent To  
Notes
2020-06-29 15:01:17ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 06.29.2020
 PERMIT NO.: 20050165
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. WHAT IS THE DIFFERENCE BETWEEN THIS PERMIT AND THAT
 WHICH HAS BEEN SUBMITTED UNDER PERMIT #20050167? THE
 DESCRIPTION, PLANS, ETC. APPEAR TO ALL BE THE SAME.
  
 2. PHOTOMETRIC LEVELS SHALL BE PROVIDED ALONG ALL
 PROPERTY LINES. LEVELS SHALL NOT EXCEED 1.0 FOOTCANDLES
 WHEN MEASURED AT THE PROPERTY LINE.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  