Plan Review Details - Permit 20050119
Plan Review Stops For Permit 20050119
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status N Date 2020-05-13 Cont ID  
Sent By jwitmer Date 2020-05-13 Time 07:26 Rev Time 0.00
Received By jwitmer Date 2020-05-13 Time 06:45 Sent To  
Notes
2020-05-13 07:27:13NEW BUILD SSINCE 2000. NO ASBESTOS. JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2020-06-28 Cont ID  
Sent By jwitmer Date 2020-06-28 Time 16:29 Rev Time 0.00
Received By jwitmer Date 2020-06-28 Time 16:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2020-06-11 Cont ID  
Sent By jwitmer Date 2020-06-11 Time 09:29 Rev Time 0.00
Received By jwitmer Date 2020-06-11 Time 08:47 Sent To  
Notes
2020-06-11 09:29:092017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20050119
 ADD: 651 OKEECHOBEE BLVD. / SUITE: 811
 CONT: PULY USA
 TEL: 561-358-9468
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURS. JUNE 11TH/ 2020
 ACTION: DENIED
  
 1) 2ND REQUEST. IN THE 2ND VERSION OF PLANS IT LOOKS
 LIKE THERE HAS BEEN A SIGNTURE LINE ADDED IN THE
 TITLEBLOCK FOR THE QUALIFIER OF THE COMPANY BUT NO
 SIGNATURE.
 CERTIFICATION BY CONTRACTOR. THE CONTRACTOR (QUALIFIER)
 THAT CREATED / DRAWN THE SET OF PLANS WILL NEED TO
 IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE
 PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR
 THE TRADE YOU ARE LICENSED IN AND PLANS DRAWN.
 107.3.4.3 CERTIFICATION BY CONTRACTOR.
  
 2) 2ND REQUEST. THE SUBMITTED 3 FLOOR PLANS SHOW THE
 REMOVAL OF EXISTING FLOORING AND NEW FLOOR TILE BEING
 INSTALLED WITH SOUND UNDERLAYMENT. IN VERSION 2 OF THE
 FLOOR PLANS THE DESCRIPTION OF THE FLOOR UNDERLAYMENT
 TO BE USED WITH THE MARBLE/ TILE FLOOR IS PROTECTO
 WHISPERMAT HW. PLEASE NOTE WHISPER MAT HW IS TO BE
 INSTALLED WITH WOOD FLOORING, IT HAS NEVER BEEN TESTED
 FOR INSTALATION WITH EITHER TILE OR MARBLE FLOORING.
 THE ONLY TESTING WE HAVE SEEN FOR THE WHISPER MAT HW IS
 ALSO FOR 8 INCH SLABS NOT THE REQUIRED 6 INCH SLABS.
  
 THE CITY IS IN RECEIPTOF TESTING FOR WHISPER MAT CS FOR
 TILE (7.3 MM) OR 5/16 INCH TILE, WE ALSO USE THIS SAME
 REPORT FOR MARBLE 5/16 INCH OR THICKER MARBLE. IF YOU
 WITH TO USE THIS PRODUCT PLEASE CHANGE THE LISTED
 PRODUCT IN THE PLANS. WE CAN UPLOAD THE PRODUCT SHEETS
 DIRECTLY INTO PROJECT DOX.
  
 NO TESTING REPORTS WERE SUBMITTED.
 FLOOR INSULATION (FBC-B 2017)
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 TYPE I AND II BUILDINGS
 2A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 2B) FBC-B 2017 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 2C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE NOTE WE ARE WORKING FROM HOME IF YOU WOULD LIKE
 TO CONTACT ME, MY CELL NUMBER IS 561-718-9724.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-05-13 Cont ID  
Sent By jwitmer Date 2020-05-13 Time 07:25 Rev Time 0.00
Received By jwitmer Date 2020-05-13 Time 06:45 Sent To  
Notes
2020-05-13 07:25:042017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20050119
 ADD: 651 OKEECHOBEE BLVD. / SUITE: 811
 CONT: PULY USA
 TEL: 561-358-9468
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. MAY 13TH/ 2020
 ACTION: DENIED
  
 1) CERTIFICATION BY CONTRACTOR. THE CONTRACTOR
 (QUALIFIER) THAT CREATED / DRAWN THE SET OF PLANS WILL
 NEED TO IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS.
 PLEASE PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE
 NUMBER FOR THE TRADE YOU ARE LICENSED IN AND PLANS
 DRAWN. 107.3.4.3 CERTIFICATION BY CONTRACTOR.
 2) THE SUBMITTED 3 FLOOR PLANS SHOW THE REMOVAL OF
 EXISTING FLOORING AND NEW FLOOR TILE BEING INSTALLED
 WITH SOUND UNDERLAYMENT. NO TESTING REPORTS WERE
 SUBMITTED.
 FLOOR INSULATION (FBC-B 2017)
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 TYPE I AND II BUILDINGS
 2A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 2B) FBC-B 2017 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 2C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 PLEASE NOTE WE ARE WORKING FROM HOME IF YOU WOULD LIKE
 TO CONTACT ME, MY CELL NUMBER IS 561-718-9724.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By jwitmer Date 2020-05-13 Time 06:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2020-06-23 Cont ID  
Sent By jleahy Date 2020-06-23 Time 14:36 Rev Time 0.00
Received By jleahy Date 2020-06-23 Time 13:05 Sent To  
Notes
2020-06-23 14:37:03PLAN NOTES NO ELECTRICAL WORK JLEAHY

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-05-21 Cont ID  
Sent By jleahy Date 2020-05-21 Time 17:31 Rev Time 0.00
Received By jleahy Date 2020-05-21 Time 17:27 Sent To  
Notes
2020-05-21 17:32:39FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NO ELECTRIC SHOWN?

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2020-06-25 Cont ID  
Sent By pleduc Date 2020-06-25 Time   Rev Time 0.00
Received By pleduc Date 2020-06-25 Time 14:10 Sent To  
Notes
2020-06-25 14:11:17THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) PROTECT FIRE SPRINKLERS AND FIRE ALARM DEVICES AND
 EQUIPMENT.
  
  
 2) DO NOT PAINT OVER SPRINKLER HEADS AND/OR FIRE ALARM
 DEVICES/EQUIPMENT.
  
  
 3) THE FS AND FA SYSTEMS SHALL BE MAINTAINED THROUGHOUT
 DEMO AND CONSTRUCTION.
  
  
 4) WITH ANY REMOVAL OF WALLS, ENSURE CODE COMPLIANT
 SPRINKLER HEAD COVERAGE IS MAINTAINED.
  
 ANY REQUIRED FIRE SPRINKLER WORK SHALL BE DONE UNDER
 SEPARATE PERMIT AND SHOP DRAWINGS.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-06-10 Cont ID  
Sent By pleduc Date 2020-06-10 Time   Rev Time 0.00
Received By pleduc Date 2020-06-10 Time 14:51 Sent To  
Notes
2020-06-10 14:51:51THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) PROTECT FIRE SPRINKLERS AND FIRE ALARM DEVICES AND
 EQUIPMENT.
  
  
 2) DO NOT PAINT OVER SPRINKLER HEADS AND/OR FIRE ALARM
 DEVICES/EQUIPMENT.
  
  
 3) THE FS AND FA SYSTEMS SHALL BE MAINTAINED THROUGHOUT
 DEMO AND CONSTRUCTION.
  
  
 4) WITH ANY REMOVAL OF WALLS, ENSURE CODE COMPLIANT
 SPRINKLER HEAD COVERAGE IS MAINTAINED.
  
 ANY REQUIRED FIRE SPRINKLER WORK SHALL BE DONE UNDER
 SEPARATE PERMIT AND SHOP DRAWINGS.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-05-08 Cont ID  
Sent By pleduc Date 2020-05-08 Time   Rev Time 0.00
Received By pleduc Date 2020-05-08 Time 14:35 Sent To  
Notes
2020-05-08 14:38:21THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) PROTECT FIRE SPRINKLERS AND FIRE ALARM DEVICES AND
 EQUIPMENT.
  
  
 2) DO NOT PAINT OVER SPRINKLER HEADS AND/OR FIRE ALARM
 DEVICES/EQUIPMENT.
  
  
 3) THE FS AND FA SYSTEMS SHALL BE MAINTAINED THROUGHOUT
 DEMO AND CONSTRUCTION.
  
  
 4) WITH ANY REMOVAL OF WALLS, ENSURE CODE COMPLIANT
 SPRINKLER HEAD COVERAGE IS MAINTAINED.
  
 ANY REQUIRED FIRE SPRINKLER WORK SHALL BE DONE UNDER
 SEPARATE PERMIT AND SHOP DRAWINGS.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2020-07-01 Time   Rev Time 0.00
Received By lmarchan Date 2020-06-24 Time 16:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-06-24 Cont ID  
Sent By ccarvaja Date 2020-06-24 Time 13:59 Rev Time 0.00
Received By ccarvaja Date 2020-06-09 Time 13:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-06-08 Cont ID  
Sent By lmarchan Date 2020-06-08 Time 11:22 Rev Time 0.00
Received By lmarchan Date 2020-05-06 Time 07:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2020-07-01 Cont ID  
Sent By ccole Date 2020-07-01 Time 10:06 Rev Time 0.00
Received By ccole Date 2020-07-01 Time 09:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-06-15 Cont ID  
Sent By ccole Date 2020-06-15 Time 17:29 Rev Time 0.00
Received By ccole Date 2020-06-15 Time 16:15 Sent To  
Notes
2020-06-15 17:30:132ND REVIEW FBC-2017 PLUMBING
 PERMIT #20050119
 6/15/20
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) COMPLIANCE WITH THE FAIR HOUSING ACCESSIBILITY
 GUIDELINES IS REQUIRED FOR THE REPLACED BATHROOM
 FIXTURES AND THE NEW SHOWER CONVERSION. PLEASE REVIEW
 COMMENTS #1 AND #1A FROM THE 1ST REVIEW PRINTED BELOW.
 BASED ON THE DRAWINGS IT IS NOT CLEAR IF USUABLE
 BATHROOM TYPE A OR B WAS CHOSEN AS THE ORIGINAL DESIGN.
 THE DESIGNER OF RECORD MUST INDICATE WHCH TYPE DESIGN
 WAS USED ON THE PLAN, AND THEN PROVIDE USABLE BATHROOM
 DETAILS FOR THE REPLACED FIXTURES AND THE NEW SHOWER
 ACCORDING TO THE GUIDELINES. PLEASE REVIEW CHAPTER 7 OF
 THE FAIR HOUSING ACT DESIGN MANUAL AND PROVIDE THE
 ENLARGED DRAWINGS AND DETAILS (WHERE REQUIRED) AS
 REQUESTED IN THE 1ST REVIEW. PLEASE NOTE THAT USABLE
 BATHROOM DESIGN TYPE A REQUIRES BOTH BATHROOMS TO MEET
 COMPLIANCE, WHEREAS TYPE B REQUIRES ONE OF THE TWO TO
 MEET FULL COMPLIANCE- SEE PAGE 7.34.
  
 1) FAIR HOUSING ACCESSIBILITY GUIDELINES: BECAUSE THE
 BUILDING WAS CONSTRUCTED IN ACCORDANCE WITH THE
 ACCESSIBILITY REQUIREMENTS OF THE FAIR HOUSING ACT AND
 THE DESIGN GUIDELINES FOR USABLE BATHROOMS IN DWELLING
 UNITS, THE ALTERATIONS THAT ARE PROPOSED IN THE
 BATHROOMS SHALL ALSO BE IN COMPLIANCE WITH THE FAIR
 HOUSING ACT. THE FAIR HOUSING ACCESSIBILITY GUIDELINES
 ARE INCLUDED IN THE FLORIDA ACCESSIBILITY CODE- 2017
 SIXTH EDITION. COMPLIANCE WITH THE GUIDELINES REQUIRES
 THAT CLEAR FLOOR SPACES FOR WHEELCHAIR APPROACHES TO
 BATH FIXTURES SHALL EITHER BE MAINTAINED AS ORIGINALLY
 DESIGNED OR PROVIDED WHERE NEW FIXTURES ARE BEING
 INSTALLED. THE PLAN IS INDICATING COMPLETE REPLACEMENT
 OF PLUMBING FIXTURES IN BATHS 1 AND 2; AND THE
 CONVERSION OF A BATHTUB TO A SHOWER IN BATH 2. ENLARGED
 DIMENSIONED DRAWINGS OF THE BATHROOMS ARE REQUIRED WITH
 CLEAR FLOOR SPACE DIAGRAMS CONFIGURED ON THE DRAWINGS.
 PLEASE SEE REQUIREMENT 7 CONTAINED IN THE GUIDELINES
 AND FIGURE 5, AND FIGURES 7A, 7C, & 7D FOR GUIDANCE.
 CONCERNING THE SHOWER, GRAB BAR AND WALL HUNG BENCH
 SEAT REINFORCEMENTS SHALL BE INSTALLED IN THE SHOWER
 WALLS TO ACCOMMODATE FUTURE INSTALLATIONS. PLEASE
 PROVIDE DIMENSIONED ELEVATION VIEWS SHOWING THE
 LOCATIONS OF THE WALL REINFORCEMENTS.
  
 1A) AS AN ALTERNATIVE TO MEETING THE GUIDELINES FOR THE
 BATH ALTERATIONS, THE OWNER AND DESIGNER OF RECORD FOR
 THE PROPOSED PROJECT MAY PROVIDE A SIGNED AND NOTARIZED
 AFFIDAVIT WHICH WOULD INDICATE ACKNOWLEDGEMENT THAT THE
 PROPOSED DESIGN DOES NOT MEET THE REQUIREMENTS OF THE
 FAIR HOUSING ACCESSIBILITY GUIDELINES, BUT WILL ALSO
 REQUIRE THE OWNER TO AGREE TO REVERT THE UNIT BACK TO
 COMPLIANCE AT TIME OF SALE IF SO REQUESTED BY THE
 BUYER. IF THIS OPTION IS CHOSEN, PLEASE SEND AN EMAIL
 TO [email protected] AND I WILL SEND A COPY OF THE FAIR
 HOUSING AFFIDAVIT. IF CHOOSING THIS OPTION IT WOULD BE
 ADVISABLE AT A MINIMUM TO INSTALL THE SHOWER WALL
 REINFORCEMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-05-27 Cont ID  
Sent By ccole Date 2020-05-27 Time 08:32 Rev Time 0.00
Received By ccole Date 2020-05-26 Time 15:43 Sent To  
Notes
2020-05-27 08:36:48 
 1ST REVIEW FBC-2017 PLUMBING
 PERMIT #20050119
 5/27/20
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) FAIR HOUSING ACCESSIBILITY GUIDELINES: BECAUSE THE
 BUILDING WAS CONSTRUCTED IN ACCORDANCE WITH THE
 ACCESSIBILITY REQUIREMENTS OF THE FAIR HOUSING ACT AND
 THE DESIGN GUIDELINES FOR USABLE BATHROOMS IN DWELLING
 UNITS, THE ALTERATIONS THAT ARE PROPOSED IN THE
 BATHROOMS SHALL ALSO BE IN COMPLIANCE WITH THE FAIR
 HOUSING ACT. THE FAIR HOUSING ACCESSIBILITY GUIDELINES
 ARE INCLUDED IN THE FLORIDA ACCESSIBILITY CODE- 2017
 SIXTH EDITION. COMPLIANCE WITH THE GUIDELINES REQUIRES
 THAT CLEAR FLOOR SPACES FOR WHEELCHAIR APPROACHES TO
 BATH FIXTURES SHALL EITHER BE MAINTAINED AS ORIGINALLY
 DESIGNED OR PROVIDED WHERE NEW FIXTURES ARE BEING
 INSTALLED. THE PLAN IS INDICATING COMPLETE REPLACEMENT
 OF PLUMBING FIXTURES IN BATHS 1 AND 2; AND THE
 CONVERSION OF A BATHTUB TO A SHOWER IN BATH 2. ENLARGED
 DIMENSIONED DRAWINGS OF THE BATHROOMS ARE REQUIRED WITH
 CLEAR FLOOR SPACE DIAGRAMS CONFIGURED ON THE DRAWINGS.
 PLEASE SEE REQUIREMENT 7 CONTAINED IN THE GUIDELINES
 AND FIGURE 5, AND FIGURES 7A, 7C, & 7D FOR GUIDANCE.
 CONCERNING THE SHOWER, GRAB BAR AND WALL HUNG BENCH
 SEAT REINFORCEMENTS SHALL BE INSTALLED IN THE SHOWER
 WALLS TO ACCOMMODATE FUTURE INSTALLATIONS. PLEASE
 PROVIDE DIMENSIONED ELEVATION VIEWS SHOWING THE
 LOCATIONS OF THE WALL REINFORCEMENTS.
  
 1A) AS AN ALTERNATIVE TO MEETING THE GUIDELINES FOR THE
 BATH ALTERATIONS, THE OWNER AND DESIGNER OF RECORD FOR
 THE PROPOSED PROJECT MAY PROVIDE A SIGNED AND NOTARIZED
 AFFIDAVIT WHICH WOULD INDICATE ACKNOWLEDGEMENT THAT THE
 PROPOSED DESIGN DOES NOT MEET THE REQUIREMENTS OF THE
 FAIR HOUSING ACCESSIBILITY GUIDELINES, BUT WILL ALSO
 REQUIRE THE OWNER TO AGREE TO REVERT THE UNIT BACK TO
 COMPLIANCE AT TIME OF SALE IF SO REQUESTED BY THE
 BUYER. IF THIS OPTION IS CHOSEN, PLEASE SEND AN EMAIL
 TO [email protected] AND I WILL SEND A COPY OF THE FAIR
 HOUSING AFFIDAVIT. IF CHOOSING THIS OPTION IT WOULD BE
 ADVISABLE AT A MINIMUM TO INSTALL THE SHOWER WALL
 REINFORCEMENTS.
  
 2) SHEET A1 & A2: PLEASE CLARIFY IF THE EXISTING TUB
 DRAIN OUTLETS WILL BE RELOCATED TO ACCOMMODATE THE NEW
 SHOWER AND TUB AND SHOWER INSTALLATIONS. IF RELOCATING
 THE DRAINS PLEASE NOTE THE FOLLOWING:
 A) REFER TO SECTION 1002.1 FBC P: THE HORIZONTAL
 DISTANCE FROM THE CENTERLINE OF THE NEW SHOWER DRAIN
 OUTLET TO THE CENTERLINE OF THE INLET OF THE EXISTING
 TRAPS SHALL NOT EXCEED 30". PLEASE PLACE A NOTE ON THE
 PLAN INDICATING COMPLIANCE.
 B) RELOCATING THE SHOWER DRAIN OUTLETS WILL REQUIRE THE
 FLOOR TO BE X-RAYED TO IN ORDER TO LOCATE REINFORCING
 STEEL OR POST STRESSED FLOOR TENDONS. PLEASE PLACE A
 NOTE ON THE PLANS TO VERIFY COMPLIANCE WILL BE MET-
 SECTION 1-07.2.1 WPB.
 C) NEW DRAIN PIPE PENETRATIONS OF THE EXISTING SLAB
 WILL REQUIRE FIRESTOPPING TO SEAL THE ANNULAR SPACE
 AROUND THE PIPING. PROVIDE A UL TESTED AND APPROVED
 FIRESTOPPING ASSEMBLY DETAIL ON THE PLAN- SECTION
 714.4.1.2 FBC B.
  
 3) A-2, SHOWER DETAIL: PROVIDE THE SLOPE OF THE SHOWER
 PAN LINER IN THE DETAIL- SEE SECTION 417.5.2 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2020-07-01 Cont ID  
Sent By ccole Date 2020-07-01 Time 10:11 Rev Time 0.00
Received By ccole Date 2020-07-01 Time 10:09 Sent To  
Notes
2020-07-01 10:11:49HAND-SIGNED CONTRACTOR PLANS