Plan Review Details - Permit 20050101
Plan Review Stops For Permit 20050101
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2020-06-26 Cont ID  
Sent By pvalenti Date 2020-06-26 Time 11:32 Rev Time 0.00
Received By pvalenti Date 2020-06-26 Time 11:32 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2020-06-16 Cont ID  
Sent By pvalenti Date 2020-06-16 Time 16:29 Rev Time 0.00
Received By pvalenti Date 2020-06-16 Time 16:27 Sent To  
Notes
2020-06-16 16:32:04PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 ALL THAT IS NEEDED IS AN ACKNOWLEDGEMENT LETTER ON
 CONTRACTOR LETTERHEAD SIGNED BY THE CONTRACTOR AS NOTED
 BELOW.
  
 ASBESTOS REQUIREMENTS:
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-05-23 Cont ID  
Sent By pvalenti Date 2020-05-23 Time 15:56 Rev Time 0.00
Received By pvalenti Date 2020-05-22 Time 15:45 Sent To  
Notes
2020-05-23 15:57:20PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 ASBESTOS REQUIREMENTS DENIED:
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-07-20 Cont ID  
Sent By pvalenti Date 2020-07-20 Time 08:23 Rev Time 0.00
Received By pvalenti Date 2020-07-20 Time 08:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-06-16 Cont ID  
Sent By pvalenti Date 2020-06-16 Time 16:45 Rev Time 0.00
Received By pvalenti Date 2020-06-16 Time 16:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-05-23 Cont ID  
Sent By pvalenti Date 2020-05-23 Time 15:57 Rev Time 0.00
Received By pvalenti Date 2020-05-22 Time 15:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-07-16 Cont ID  
Sent By jleahy Date 2020-07-16 Time 16:53 Rev Time 0.00
Received By jleahy Date 2020-07-16 Time 16:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-06-18 Cont ID  
Sent By jleahy Date 2020-06-18 Time 17:38 Rev Time 0.00
Received By jleahy Date 2020-06-18 Time 17:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-05-21 Cont ID  
Sent By jleahy Date 2020-05-21 Time 13:08 Rev Time 0.00
Received By jleahy Date 2020-05-21 Time 12:31 Sent To  
Notes
2020-05-21 13:10:20FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 ELECTRICAL PLAN REVIEW NEEDS AN ELECTRICAL PERMIT
 APPLICATION FOR APPROVAL. PLEASE EMAIL THE ELECTRICAL
 PERMIT APPLICATION TO [email protected] AND CC
 [email protected] AND [email protected] SO WE RECEIVE IT
 ALSO. WHEN THIS EMAIL IS RECEIVED ONE OF THE REVIEWERS
 WILL APPROVE THE PLAN REVIEW. THE ORIGINAL PERMIT
 APPLICATION MUST BE SUBMITTED WHEN THE PERMIT IS PICKED
 UP.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2020-07-17 Cont ID  
Sent By pleduc Date 2020-07-17 Time   Rev Time 0.00
Received By pleduc Date 2020-07-16 Time 11:09 Sent To  
Notes
2020-07-16 11:12:39THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE EXISTING FIRE ALARM SYSTEM DEVICES SHALL BE
 MAINTAINED AND REMAIN ACTIVE THROUGHOUT THE DEMO AND
 CONSTRUCTION PERIOD.
  
 2) ANY AND ALL WORK ON THE FIRE ALARM SYSTEM OR DEVICES
 SHALL BE DONE UNDER SEPARATE PERMITS AND SHOP DRAWINGS.
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-06-16 Cont ID  
Sent By pleduc Date 2020-06-16 Time   Rev Time 0.00
Received By pleduc Date 2020-06-16 Time 13:02 Sent To  
Notes
2020-06-16 13:02:50THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE EXISTING FIRE ALARM SYSTEM DEVICES SHALL BE
 MAINTAINED AND REMAIN ACTIVE THROUGHOUT THE DEMO AND
 CONSTRUCTION PERIOD.
  
 2) ANY AND ALL WORK ON THE FIRE ALARM SYSTEM OR DEVICES
 SHALL BE DONE UNDER SEPARATE PERMITS AND SHOP DRAWINGS.
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-05-20 Cont ID  
Sent By pleduc Date 2020-05-20 Time   Rev Time 0.00
Received By pleduc Date 2020-05-20 Time 09:33 Sent To  
Notes
2020-05-20 09:53:10THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE EXISTING FIRE ALARM SYSTEM DEVICES SHALL BE
 MAINTAINED AND REMAIN ACTIVE THROUGHOUT THE DEMO AND
 CONSTRUCTION PERIOD.
  
 2) ANY AND ALL WORK ON THE FIRE ALARM SYSTEM OR DEVICES
 SHALL BE DONE UNDER SEPARATE PERMITS AND SHOP DRAWINGS.
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-07-20 Cont ID  
Sent By pvalenti Date 2020-07-20 Time 08:30 Rev Time 0.00
Received By pvalenti Date 2020-07-15 Time 09:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-06-18 Cont ID  
Sent By jleahy Date 2020-06-18 Time 17:39 Rev Time 0.00
Received By jleahy Date 2020-06-15 Time 10:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-05-23 Cont ID  
Sent By pvalenti Date 2020-05-23 Time 15:58 Rev Time 0.00
Received By pvalenti Date 2020-05-18 Time 13:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2020-07-17 Cont ID  
Sent By medwards Date 2020-07-17 Time 08:33 Rev Time 0.00
Received By medwards Date 2020-07-17 Time 08:33 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-06-16 Cont ID  
Sent By medwards Date 2020-06-16 Time 11:11 Rev Time 0.00
Received By medwards Date 2020-06-16 Time 10:55 Sent To  
Notes
2020-06-16 11:15:04THIS PROJECT IS FOR DEMO ONLY. THIS PROJECT WILL NEED
 TO HAVE A MECHANICAL DEMO PERMIT. PLEASE REMOVE ALL NEW
 WORK FROM DEMO SHEET, SHOW ONLY THE DEMO WORK BEING
 DONE. THE NEW WORK WILL COME UNDER A NEW UPFIT PERMIT.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status N Date 2020-05-23 Cont ID  
Sent By pvalenti Date 2020-05-23 Time 15:14 Rev Time 0.00
Received By pvalenti Date 2020-05-23 Time 15:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-07-17 Cont ID  
Sent By ccole Date 2020-07-17 Time 08:15 Rev Time 0.00
Received By ccole Date 2020-07-17 Time 07:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2020-06-16 Cont ID  
Sent By ccole Date 2020-06-16 Time 12:05 Rev Time 0.00
Received By ccole Date 2020-06-16 Time 11:44 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-07-17 Cont ID  
Sent By medwards Date 2020-07-17 Time 08:35 Rev Time 0.00
Received By medwards Date 2020-07-17 Time 08:34 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-06-16 Cont ID  
Sent By pvalenti Date 2020-06-16 Time 16:46 Rev Time 0.00
Received By pvalenti Date 2020-06-16 Time 16:27 Sent To  
Notes
2020-06-16 16:50:12PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 SIGNATURE REVIEW APPROVED WITH PROVISO:
  
 PROVIDE AND DROP OFF AN ORIGINAL (PAPER) SET OF SIGNED
 AND SEALED PLANS TO THE CITY FOR SIGNATURE/SEAL
 VERIFICATION.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-05-23 Cont ID  
Sent By pvalenti Date 2020-05-23 Time 15:33 Rev Time 0.00
Received By pvalenti Date 2020-05-22 Time 15:45 Sent To  
Notes
2020-05-23 15:52:18PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 SIGNATURE REVIEW DENIEDL
  
 FBC B 107.2.1, FS 471 & FS 481, THE SUBMITTED PLANS
 NEED TO BE DIGITALLY SIGNED.