Plan Review Details - Permit 20050095
Plan Review Stops For Permit 20050095
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2020-06-22 Cont ID  
Sent By cpuell Date 2020-06-22 Time 10:20 Rev Time 0.00
Received By cpuell Date 2020-06-22 Time 10:20 Sent To  
Notes
2020-06-22 10:24:09TAKING OVER MELLOW MUSHROOM

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2020-05-26 Cont ID  
Sent By cpuell Date 2020-05-26 Time 08:59 Rev Time 0.00
Received By cpuell Date 2020-05-26 Time 08:59 Sent To  
Notes
2020-05-26 09:00:30PLEASE EMAIL A SITE PLAN SHOWING THE EXACT LOCATION TO
 [email protected]

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status N Date 2020-05-19 Cont ID  
Sent By jwitmer Date 2020-05-19 Time 10:01 Rev Time 0.00
Received By jwitmer Date 2020-05-18 Time 16:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-07-09 Cont ID  
Sent By pvalenti Date 2020-07-09 Time 16:37 Rev Time 0.00
Received By pvalenti Date 2020-07-09 Time 14:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-06-19 Cont ID  
Sent By pvalenti Date 2020-06-19 Time 14:49 Rev Time 0.00
Received By pvalenti Date 2020-06-16 Time 08:53 Sent To  
Notes
2020-06-16 14:12:59PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 2ND BUILDING REVIEW DENIED:
  
 1) FBC B/WPB AMENDMENTS 109.3, THE BUILDING VALUATION
 IS TOO LOW. PROVIDE DETAILED COST BREAK DOWN INCLUDING:
 BUILDING, ROOFING, MECHANICAL, ELECTRIC & PLUMBING.
 2) FBC B 107, PROVIDE CITY PLACE APPROVAL STAMP ON
 PLANS.
 3) OK
 4) OK WITH PROVISO: 107.3.4.1 & 1803.5.2, PROVIDE THE
 GEO-TECH REPORT WITH ENGINEER'S APPROVAL AND DESIGNER
 OF RECORD'S REVIEW STAMP PRIOR TO CANOPY FOOTING STEEL
 PLACEMENT.
 5) FBC EC C401.2, PROVIDE ENERGY CODE
 DOCUMENTS/CALCULATIONS. (THE BUILDING ENERGY COSTSHALL
 BE EQUAL TO OR LESS THAN 85 PERCENT OF THE STANDARD
 REFERENCEDESIGN BUILDING)
 6) OK WITH PROVISO:
 AWS D1.1 CLAUSE 3.1: AT TIME OF INSPECTION PLEASE
 PROVIDE A WELD PROCEDURE SPECIFICATION; THE W.P.S.
 SPECIFIES THE REQUIRED ESSENTIAL VARIABLES INCLUDING:
 BASE MATERIALS, JOINTS, PROCESS, AND FILLER METALS TO
 BE USED.
 AWS D1.1 CLAUSE 4.15: AT TIME OF INSPECTION PLEASE
 PROVIDE A WELDER PERFORMANCE QUALIFICATION RECORD; THE
 W.P.Q.R. PROVIDES INFORMATION WHICH CAN BE USED TO
 VERIFY THE WELDER?S QUALIFICATION AND CERTIFICATION AS
 IT RELATES TO THE WELDING REQUIREMENTS OF THE PROJECT.
 7) OK
 8) FBC B 107.3.4.1, PROVIDE ALL DEFERRED SUBMITTALS
 INCLUDING PRODUCT APPROVALS ON PLANS. THESE PRODUCT
 APPROVALS SHALL BE REVIEW STAMPED BY THE DESIGNER OF
 RECORD.
 9) FBC B 107, IDENTIFY GLAZING/ MULLIONS. PLEASE
 IDENTIFY ON THEPRODUCT APPROVAL BEFORE SUBMITTING TO
 DESIGNER OFRECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF
 GLAZING,MULLION SIZE, LENGTH IF UNREINFORCED OR
 REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER'S
 INSTRUCTIONS.FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
 10) OK
 11A) OK
 11B) OK
 11C) FBC B 107.2.1.2, THE PLANS ARE INCOMPLETE. ON PAGE
 A-604 SEVERAL DETAILS REFERENCE PAGE A-907. THERE IS NO
 PAGE A-907.
 11D) OK
 12) FBC B 107, FBC A 505.2 & 505.3, PROVIDE THE
 ACCESSIBLE PARKING SPACE AND ACCESS AISLE STRIPING AND
 MEASUREMENT DETAILS ON PAGE A-200 FOR THE RECHARGEABLE
 STATIONS.
 13) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. A
 THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-05-19 Cont ID  
Sent By jwitmer Date 2020-05-19 Time 10:15 Rev Time 0.00
Received By jwitmer Date 2020-05-18 Time 16:02 Sent To  
Notes
2020-05-19 10:05:032017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20050095
 ADD: 700 S. ROSEMARY AVE. SUITE# 100
 CONT: TBD / TO BE DETERMINED
 TEL: ?????
 E-MAIL: [email protected] CONTACT: ISAAC MIKEL
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: 5/18-19/2020
 ACTION: DENIED
  
 1) THE DECLARED VALUE IS EXTREMELY LOW, MAYBE THAT
 WOULD BE THE VALUE OF THE DEMOLITION INCLUDING TRUCKS,
 DRIVERS AND DUMP FEES. THIS PERMIT IS FOR THE REMODEL
 OF DEMOLITION AND REMODEL OF A 4604 SQ. FT. TENANT
 SPACE PLUS NEW CANOPY. THE PRICE GIVEN MAY REFLECT THE
 VALUE FOR THE PLANS NOT THE PROJECT. A REALISTIC VALUE
 WILL NEED TO BE ADJUSTED BEFORE THE NEXT PLAN REVIEW
 CAN START.
 109.3* BUILDING PERMIT VALUATION. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE UNDER
 ESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE TOTAL REPLACEMENT PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRICAL,
 PLUMBING, MECHANICAL, INTERIOR FINISHES, NORMAL SITE
 WORK (EXCAVATION AND BACKFILL FOR BUILDINGS),
 ARCHITECTURAL AND DESIGN FEES, MARKETING COST, OVERHEAD
 AND PROFIT; EXCLUDING ONLY LAND VALUE. VALUATION
 REFERENCES MAY INCLUDE THE LATEST PUBLISHED DATA OF
 NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE
 MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS.
 WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING
 PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE
 QUALIFIER AND OWNER AND BRINGS IN THE LISTED
 SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE
 QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND
 LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE
 FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN
 LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR
 EACH PERMIT.
  
 ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK
 STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE
 AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS &
 FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL
 TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED
 SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE,
 LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR
 FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE
 REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT.
 PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE
 ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE
 STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE
 REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE
 BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE
 BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR
 THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE
 PRIME OR MASTER PERMIT.
  
 2) THERE IS A NOTE, OR HOLD THAT THE SUBMITTED SET OF
 PLANS HAS NOT BEEN REVIEWED BY CITY PLACE MANAGEMENT
 NOR BEEN APPROVED WITH THEIR CITY PLACE STAMP OF
 APPROVAL.
  
 3) THE SUBMITTED STRUCTURAL CANOPY CALCULATIONS ARE NOT
 DIGITALLY SIGNED AND SEALED.
 FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A
 SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE
 OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON
 DIGITALLY SIGNED AND SEALED ENGINEERING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS.
  
 4) MISSING IS A SOILS REPORT FOR THE NEW CANOPY
 FOUNDATIONS. QUESTIONABLE SOILS. SHEET S-001 INDICATES
 A REPORT BY UNIVERSAL ENGINEERING SCIENCES JULY 01/
 2019.2017 FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE THE
 CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL
 IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO
 THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
  
 5) MISSING ARE ENERGY CODE DOCUMENTS. 2017 ENERGY CODE
 SECTION C401.2 APPLICATION.
 COMMERCIAL BUILDINGS SHALL COMPLY WITH ONE OF THE
 FOLLOWING:
 3.1.THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1,
 EXCLUDING SECTION 9.4.1.1(G) OF THE STANDARD.
 3.2.THE REQUIREMENTS OF SECTIONS C402 THROUGH C405. IN
 ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY WITH
 SECTION C406 AND TENANT SPACES SHALL COMPLY WITH
 SECTION C406.1.1.
 3.3.THE REQUIREMENTS OF SECTIONS C402.5, C403.2, C404,
 C405.2, C405.3, C405.5, C405.6 AND C407. THE BUILDING
 ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85 PERCENT
 OF THE STANDARD REFERENCE DESIGN BUILDING.
  
 6) THE STRUCTURAL SHEETS ALL REFER TO THE IBC FOR CODE
 REFERENCES. PLEASE NOTE THAT THE 2015 IBC MAYBE THE
 BASE CODE THE 2017 FLORIDA BUILDING CODE-BUILDING WAS
 DEVELOPED FROM BUT IS DIFFERENT FROM THE IBC. IN THE
 IBC THE CODE SPEAKS ABOUT THE INSPECTIONS REQUIRED BY
 SPECIAL INSPECTORS FOR CODE SECTIONS 1704 AND 1705.
 PLEASE NOTE THAT UNDER THE 2017 FBC-B THE SECTIONS 1704
 & 1705 ARE RESERVED. THE CITY WILL PERFORM ALL BUILDING
 INSPECTIONS WITH THE EXCEPTION OF BOLTED AND WELDED
 CONNECTIONS.
 WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS
 REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION. THIRD PARTY CERTIFICATION WILL BE REQUIRED.
 2017 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT
 561-805-6666.
  
 7) SHEET S-001 DOES PROVIDE THE WIND DESIGN CRITERIA
 BUT NOT THE PRESSURES FOR COMPONENTS & CLADDING.
 2017 FBC-B 1603.1.4 WIND DESIGN DATA. THE FOLLOWING
 INFORMATION RELATED TO WIND LOADS SHALL BE SHOWN,
 REGARDLESS OF WHETHER WIND LOADS GOVERN THE DESIGN OF
 THE LATERAL FORCE-RESISTING SYSTEM OF THE STRUCTURE:
 7.1. COMPLIED. ULTIMATE DESIGN WIND SPEED, VULT,
 (3-SECOND GUST), MILES PER HOUR AND NOMINAL DESIGN WIND
 SPEED, VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
 7.2. COMPLIED. RISK CATEGORY.
 7.3. COMPLIED. WIND EXPOSURE. APPLICABLE WIND DIRECTION
 IF MORE THAN ONE WIND EXPOSURE IS UTILIZED. TABLE
 1609.7.2. HEIGHT AND EXPOSURE. ASCE 7-10 TABLE 30.3.1.
 7.4. COMPLIED. APPLICABLE INTERNAL PRESSURE
 COEFFICIENT.
  
 7.5. MISSING. DESIGN WIND PRESSURES TO BE USED FOR
 EXTERIOR COMPONENTS AND CLADDING MATERIALS SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF.
  
 6. 7.6. MISSING. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR
 HEIGHT & EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 6.7.7. MISSING. 1609.3.1 WIND SPEED CONVERSION VULT TO
 VASD.
  
 7) COMPONENTS & CLADDING
 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 INSULATION, LIGHTWEIGHT CONCRETE INSULATION, CURBS,
 ROOF TOP VENTILATORS
 (G) PRE-ENGINEERED A/C STANDS
  
 8A) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 8B) DELEGATED ENGINEERING. 61G15-30.003 ENGINEERING
 DOCUMENT CLASSIFICATION. FL 61G-15-30.006 (3) THE
 DELEGATED ENGINEER SHALL FORWARD THE DELEGATED
 ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR
 REVIEW.
  
 8C) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 8D) DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 9) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 10) SHEET G-003 DETAIL 4 LEGEND ADA MOUNTING HEIGHTS.
 WE REFER TO THE 2017 FLORIDA BUILDING CODE
 ACCESSIBILITY CODE USED IN THE STATE OF FLORIDA. DO NOT
 MEASURE TO THE CENTERLINE OF THE GRAB BAR BUT THE TOP
 OF THE GRIPPING SURFACE. 2017 FBC-ACCESSIBILITY CODE
 SECTION 609.4 POSITION OF GRAB BARS. GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION, 33 INCHES MINIMUM
 AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED
 TO THE TOP OF THE GRIPPING SURFACE, NOT CENTERLINE.
  
 11) SHEET A-604:
  
 11A) DETAIL # 1. THE BUILT IN CLOSET ROD IS SHOWN AT 5
 FEET ABOVE FINISH FLOOR. THE PLAN DOES NOT SHOW
 EQUIVALENT FACILITATION 103 OF THE 2017
 FBC-ACCESSIBILITY CODE, OUT OF REACH RANGES SECTIONS:
 308 REACH RANGES
 308.2 FORWARD REACH./ 308.2.1 UNOBSTRUCTED/ 308.2.2
 OBSTRUCTED HIGH REACH.
 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2
 OBSTRUCTED HIGH REACH.
 COAT HOOKS: 603.4.
  
 11B) DETAIL # 4. PLEASE NOTE THE STOP OF THE SHELF THE
 MICROWAVE SITS ON IS AT A HEIGHT OF 4.66 FEET OR 4 FOOT
 8 INCHES. PLEASE PROVIDE COMPLIANCE WITH THE 2017
 FBC-ACCESSIBILITY CODE SECTIONS:
 308 REACH RANGES
 308.2 FORWARD REACH./ 308.2.1 UNOBSTRUCTED/ 308.2.2
 OBSTRUCTED HIGH REACH.
 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2
 OBSTRUCTED HIGH REACH.
  
 309 OPERABLE PARTS
 309.3 HEIGHT. OPERABLE PARTS SHALL BE PLACED WITHIN ONE
 OR MORE OF THE REACH RANGES SPECIFIED IN 308.
 309.4 OPERATION. OPERABLE PARTS SHALL BE OPERABLE WITH
 ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING,
 PINCHING, OR TWISTING OF THE WRIST. THE FORCE REQUIRED
 TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS (22.2 N)
 MAXIMUM.
  
 11C) DETAIL # 8. DETAIL 8 INDICATES AN ADA SINK CABINET
 AND A CUT SECTION LABELED 8/A907. THERE IS NO SHEET
 A-907 NO CUT SECTION. 107.2.1.2 ADDITIONAL INFORMATION
 REQUIRED.
  
 11D) DETAIL # 9. DETAIL 9 ILLUSTRATES A CORK BOARD WITH
 THE BOTTOM OF THE CORK BOARD IS AT 4FEET, DOES NOT
 COMPLY WITH THE 2017 FBC-ACCESSIBILITY CODE SECTIONS:
 308 REACH RANGES
 308.2 FORWARD REACH./ 308.2.1 UNOBSTRUCTED/ 308.2.2
 OBSTRUCTED HIGH REACH.
 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2
 OBSTRUCTED HIGH REACH.
  
 12) SHEET A-200 SHOWS PARKING WITHIN THE PARKING GARAGE
 RECHARGEABLE STATIONS, WHAT IS MISSING IS ACCESSIBLE
 PARKING SPACE AND ACCESS AISLE. 2017 FBC-ACCESSIBILITY
 CODE SECTIONS:
 12A) 103 EQUIVALENT FACILITATION.
  
 12B) ACCESSIBLE PARKING SPACE / STALL PAINTING. 2017
 ACCESSIBILITY CODE SECTION 502.2 VEHICLE SPACES. EACH
 PARKING SPACE MUST BE AT LEAST 12 FEET WIDE, SHALL BE
 MARKED TO DEFINE THE WIDTH, AND SHALL HAVE AN ADJACENT
 ACCESS AISLE COMPLYING WITH 502.3.
 ADVISORY 502.3.3MARKING THE METHOD AND MARKING OF COLOR
 OF MARKING ARE NOT SPECIFIED BY THESE REQUIREMENTS BUT
 MAY BE ADDRESSED BY STATE OR LOCAL LAWS OR REGULATIONS.
 WEST PALM MUNI-CODE ARTICLE XV PARKING DETAIL, 94-485
 ILLUSTRATES WITH MEASUREMENTS FOR DOUBLE STRIPE STALL
 PAINTING.
  
 13) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 PLEASE NOTE WE ARE WORKING FROM HOME IF YOU WOULD LIKE
 TO CONTACT ME, MY CELL NUMBER IS 561-718-9724.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-07-09 Cont ID  
Sent By jleahy Date 2020-07-09 Time 18:24 Rev Time 0.00
Received By jleahy Date 2020-07-09 Time 17:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-06-22 Cont ID  
Sent By jleahy Date 2020-06-22 Time 15:22 Rev Time 0.00
Received By jleahy Date 2020-06-22 Time 15:14 Sent To  
Notes
2020-06-22 15:27:45CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PARKING SPACE CHARGES ARE IN ANOTHER BUILDING AND WILL
 HAVE TO BE PERMITED SEPARATELY FROM THE TENNANT SPACE,
 PLEASE REMOVE THESE PAGES FROM THE TENNANT SPACE
 PACKAGE AND PERMIT THEM SEPARATELY.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-06-05 Cont ID  
Sent By jpearson Date 2020-06-05 Time 11:03 Rev Time 0.00
Received By jpearson Date 2020-06-05 Time 07:23 Sent To  
Notes
2020-06-05 11:03:12CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. THIS SHOLD
 NOT INCLUDE THE VALUE OF WORK IN THE PARKING GARAGE AS
 THIS WILL BE A SEPARATE PERMIT. IT SHOULD ALSO NOT
 INCLUDE ANY OF THE REQUIRED ADDITIONAL PERMITS AS NOTED
 IN COMMENT 2. WPB FBC 109.3
 2. FIRE ALARM, LOW VOLTAGE SYSTEMS, DAS, LIGHTNING
 PROTECTION, GENERATORS, COMMERCIAL HOOD SYSTEMS, WALK
 IN COOLERS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS
 (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF
 THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND PLAN SUBMITTALS FOR ANY
 OF THESE SYSTEMS PRESENT. WPB FBC 105.1, 107.2.1
 3. WORK IN PARKING GARAGE ALSO REQUIRES A SEPARATE
 PERMIT AND SUBMITTALS. REMOVE THESE SHEETS FROM
 SUBMITTAL. WPB FBC 105.1
 4. ALL WORK IN ROSEMARY SQUARE REQUIRES APPROVAL FROM
 PROPERTY MANAGEMENT. PROVIDE THE PROPERTY MANAGEMENT
 STAMP ON PLANS, OR A LETTER OF APPROVAL OF PLANS. WPB
 FBC 107.2.1
 5. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 6. PROVIDE GFCI PROTECTION FOR ALL RECEPTACLE OUTLETS
 IN BATHROOMS. NEC 210.8
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2020-07-09 Cont ID  
Sent By pleduc Date 2020-07-09 Time   Rev Time 0.00
Received By pleduc Date 2020-07-09 Time 10:25 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-06-19 Cont ID  
Sent By pleduc Date 2020-06-19 Time   Rev Time 0.00
Received By pleduc Date 2020-06-16 Time 13:36 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-05-11 Cont ID  
Sent By pleduc Date 2020-05-11 Time   Rev Time 0.00
Received By pleduc Date 2020-05-11 Time 13:35 Sent To  
Notes
2020-05-11 14:04:23THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET FP 101 - THERE IS NO INDICATIONS OF FIRE
 SPRINKLER PROTECTION UNDER THE CANOPY WHERE VEHICLES
 ARE PROPOSED TO BE STORED.
  
 PER NFPA 13,
  
 CHAPTER 4 GENERAL REQUIREMENTS
 4.1 LEVEL OF PROTECTION. A BUILDING, WHERE PROTECTED BY
 AN
 AUTOMATIC SPRINKLER SYSTEM INSTALLATION, SHALL BE
 PROVIDED WITH
 SPRINKLERS IN ALL AREAS EXCEPT WHERE SPECIFIC SECTIONS
 OF THIS
 STANDARD PERMIT THE OMISSION OF SPRINKLERS.
  
 FIRE SPRINKLER PROTECTION IS REQUIRED. PLEASE CORRECT.
  
  
  
 2) SHEET M 101 - CONNECTING THE A/C OUTSIDE AIR AT
 EXISTING POINTS1 & 4 IS INDICATED; HOWEVER, THERE IS NO
 INDICATION OF REQUIRED FIRE DAMPERS AT THE TENANT WALL
 EITHER PROPOSED OR NEW.
  
 PER NFPA 101, CHAPTER 38, NEW BUSINESS
  
 38.5.2 HEATING, VENTILATING, AND AIR-CONDITIONING.
 HEATING,
 VENTILATING, AND AIR-CONDITIONING EQUIPMENT SHALL
 COMPLY WITH THE
 PROVISIONS OF SECTION 9.2.
  
 NFPA 101, CH 9
  
 9.2 HEATING, VENTILATING, AND AIR-CONDITIONING.
 9.2.1 AIR-CONDITIONING, HEATING, VENTILATION DUCTWORK,
 AND RELATED EQUIPMENT.
 AIR-CONDITIONING, HEATING, VENTILATING DUCTWORK AND
 RELATED EQUIPMENT
 SHALL BE IN ACCORDANCE WITH NFPA 90A,
 STANDARD FOR THE INSTALLATION OF AIR-CONDITIONING AND
 VENTILATING
 SYSTEMS, OR NFPA 90B, STANDARD FOR THE INSTALLATION OF
 WARM AIR
 HEATING AND AIR-CONDITIONING SYSTEMS, AS APPLICABLE,
 UNLESS SUCH
 INSTALLATIONS ARE APPROVED EXISTING INSTALLATIONS,
 WHICH SHALL BE
 PERMITTED TO BE CONTINUED IN SERVICE.
  
 NFPA 90A
  
 5.3* PENETRATIONS ? PROTECTION OF OPENINGS.
 5.3.1 FIRE-RATED WALLS AND PARTITIONS.
 5.3.1.1* APPROVED FIRE DAMPERS SHALL BE PROVIDED WHERE
 AIR
 DUCTS PENETRATE OR TERMINATE AT OPENINGS IN WALLS OR
 PARTITIONS
 REQUIRED TO HAVE A FIRE RESISTANCE RATING OF 2 HOURS OR
 MORE.
 5.3.1.1.1* FIRE DAMPERS SHALL NOT BE REQUIRED WHERE
 OTHER
 OPENINGS THROUGH THE WALL ARE NOT REQUIRED TO BE
 PROTECTED.
 5.3.1.2 APPROVED FIRE DAMPERS SHALL BE PROVIDED IN ALL
 AIR
 TRANSFER OPENINGS IN PARTITIONS THAT ARE REQUIRED TO
 HAVE A FIRE
 RESISTANCE RATING AND IN WHICH OTHER OPENINGS ARE
 REQUIRED TO
 BE PROTECTED.
  
 PLEASE REVIEW AND PROVIDE DETAILS
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-07-15 Cont ID  
Sent By lmarchan Date 2020-07-15 Time 08:02 Rev Time 0.00
Received By lmarchan Date 2020-07-08 Time 10:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-06-26 Cont ID  
Sent By lmarchan Date 2020-06-29 Time 11:53 Rev Time 0.00
Received By ccarvaja Date 2020-06-15 Time 11:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-06-05 Time   Rev Time 0.00
Received By lmarchan Date 2020-05-08 Time 14:05 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2020-05-19 Cont ID  
Sent By jwitmer Date 2020-05-19 Time 10:00 Rev Time 0.00
Received By jwitmer Date 2020-05-18 Time 16:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2020-07-09 Cont ID  
Sent By medwards Date 2020-07-09 Time 14:48 Rev Time 0.00
Received By medwards Date 2020-07-09 Time 14:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-06-26 Cont ID  
Sent By medwards Date 2020-06-26 Time 08:22 Rev Time 0.00
Received By medwards Date 2020-06-26 Time 08:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-05-11 Cont ID  
Sent By medwards Date 2020-05-11 Time 13:44 Rev Time 0.00
Received By medwards Date 2020-05-11 Time 13:44 Sent To  
Notes
2020-05-11 13:44:431ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20050095
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-301- PLEASE PROVIDE OUTSIDE AIR CALCULATIONS
 FOR EACH ROOM. FBC M TABLE 403.3.1.1
  
 2) PROVIDE ENERGY CALCULATIONS AND MANUAL J
 CALCULATIONS. FBC EC 107.2.1
  
 3) PROVIDE SPECIFICATION SHEETS FOR FCU-1, FCU-2, CRU-1
 AND EF-1. FBC FS 107.2.1
  
 4) PLEASE PROVIDE RATING OF TENANT SEPARATION WALL. IF
 IT IS A RATED WALL, PLEASE SHOW CODE COMPLIANT DAMPERS
 FOR THE FRESH AIR AND EXHAUST AIR DUCTS WHERE THEY
 PENETRATE THIS WALL. FBC FS 107.2.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2020-07-09 Cont ID  
Sent By ccole Date 2020-07-09 Time 17:35 Rev Time 0.00
Received By ccole Date 2020-07-09 Time 16:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-06-24 Cont ID  
Sent By ccole Date 2020-06-24 Time 10:07 Rev Time 0.00
Received By ccole Date 2020-06-23 Time 14:58 Sent To  
Notes
2020-06-24 10:07:292ND REVIEW FBC-2017 PLUMBING
 PERMIT- 20050095
 6/24/2020
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 THE 1ST REVIEW COMMENTS LISTED BELOW WERE NOT
 COMPLETELY ADDRESSED. THE COMMENTS WILL BE MARKED AS
 PASSED OR FAILED. PLEASE NOTE ADDITIONAL REMARKS FOR
 FAILED COMMENTS.
  
 1) FAILED. SHEET P-000: PROVIDE PLUMBING FIXTURE
 CALCULATIONS IN ACCORDANCE WITH TABLE 403.3 FBC P.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED NUMBER OF FIXTURES. THE ARCHITECT OF RECORD'S
 RESPONSE WAS TO SEE PLUMBING. THE SCHEDULE WAS NOT
 PROVIDED ON PLUMBING PLANS.
  
 2) FAILED. PROVIDE ENLARGED DIMENSIONED TOILET ROOM
 FLOOR PLANS AND DETAILS SHOWING COMPLIANCE WITH THE
 FBC-17 ACCESSIBILITY. THE ENLARGED DRAWINGS SHALL SHOW:
 A) FAILED- NEW PLANS SHEET A-205: CLEAR FLOOR SPACE
 DIMENSIONS FOR THE WATER CLOSETS- SECTION 604.3 FBC
 ACC. THE PLAN SHOWS A FLOOR MOUNTED WATER CLOSET WHICH
 REQUIRES A 59" DEEP X60" WIDE CLEAR FLOOR SPACE- FIGURE
 604.8.1.1 & SECTION 604.8.1.7 FBC ACC.
 B) FAILED. CLEAR FLOOR SPACE DIMENSIONS FOR THE
 LAVATORIES- SECTION 606.2. BECAUSE DIMENSIONS HAVE NOT
 BEEN PROVIDED FOR THE TOILET COMPARTMENTS. THE
 LOCATIONS OF THE LAVS CANNOIT BE APPROVED AT THIS TIME-
 SECTION 604.8.1.6 FBC ACC.
 C) FAILED. TOILET COMPARTMENT WIDTH AND LENGTH
 MEASUREMENTS- SECTIONS 604.2-604.8. FBC ACC, AND
 SECTION 405.3.1 FBC P. DIMENSIONS NOT PROVIDED.
 D) FAILED TOILET COMPARTMENT DOOR WIDTHS, DOOR SWINGS,
 AND WHEELCHAIR APPROACHES- SECTION 604.8.1.2 &
 604.8.1.3 FBC ACC. SHEET A-201- PLEASE REFER TO FIGURES
 404.2.4 (B), (C), & (J): PROVIDE THE WIDTH DIMENSIONS
 OF THE BOH CORRIDOR AND CLEARANCE MEASUREMENT
 BETWEENTHE DRINKING FOUNTAINS AND RESTROOM 103 DOORWAY.
 E) PASSED. TURNING SPACE DIAMETERS- SECTION 304.3.
 F) FAILED. CENTERLINES OF THE WATER CLOSETS FROM THE
 SIDE WALLS OR PARTITIONS- SECTION 604.2. SHEET A-201
 SHOWS 1'10-7/8" TO CENTERLINE OF THE WATER CLOSET- SEE
 SECTION 604.2: MINIMUM 16" AND MAXIMUM 18" TO CENTELINE
 FROM ADJACENT WALL. THE CORRECT DIMENSION IS SHOWN ON
 A-205.
  
 3) FAILED. PROVIDE TOILET ROOM ELEVATION DRAWINGS
 INDICATING:
 A) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SECTION 604.4.
 B) HEIGHTS OF THE FRONT RIM OF THE LAVATORY FROM THE
 FINISHED FLOOR- SECTION 606.3
 C) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION
 306.
 D) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS- SECTION 604.5
 E) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS-
 SECTION 604.6.
 F) LOCATIONS, CLEARANCES, AND MOUNTING HEIGHTS FOR
 PAPER DISPENSERS- SECTION 604.7
 G) HEIGHTS OF THE MIRROR FROM THE FINISHED FLOOR TO THE
 BOTTOM OF THE REFLECTIVE SURFACES- SECTION 603.3.
 PLEASE NOTE THE AOR RESPONSE WAS TO SEE SHEETS A-605
 AND G-003, HOWEVER A-605 DOES NOT SHOW ANY MOUNTING
 HEIGHT MEASUREMENTS. G-003 SHOWS A WALL HUNG WATER
 CLOSET, HOWEVER A FLOOR MOUNTED HAS BEEN SPECIFIED.
 CONCERNING THE GRAB BARS AT THE TOILET PAPER DISPENSER,
 REFER TO SECTION 60. 3 AND FIGURE 609.3 AND VERIFY
 COMPLIANCE.
  
 4) FAILED. P-000 & P-101: REFER TO SECTION 211.1.2 FBC
 ACC, AND TABLE 404.3 FBC P. NO FEWER THAN TWO DRINKING
 FOUNTAINS SHALL BE PROVIDED. ONE DRINKING FOUNTAIN
 SHALL COMPLY WITH SECTIONS 602.1 & 602.6, AND ONE SHALL
 COMPLY WITH 602.7. SECTION 602.7 REQUIRES THAT SPOUT
 OUTLETS FOR STANDING PERSONS SHALL BE 38 INCHES MINIMUM
 AND 43 INCHES MAXIMUM FROM THE FINISHED FLOOR. REVISE
 THE PLANS TO SHOW COMPLIANCE AND PROVIDE THESE DETAILS:
 A) THE CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR
 FORWARD WHEELCHAIR APPROACH- SECTION 602.2. FBC ACC.
 B) KNEE AND TOE CLEARANCES- SECTION 306.
 C) SPOUT HEIGHT AND SPOUT LOCATION- SECTION 602.4 AND
 602.5.
 THE AOR RESPONSE WAS TO SEE DETAIL 2/A-606, HOWEVER NO
 CLEARANCES OR DIMENSIONS ARE PROVIDED ON THE DETAIL.
  
 5) PASSED. P101: THE CONDENSATE FROM THE FCU'S SHALL
 NOT DRAIN INTO THE CITY SANITARY SEWER PER SEC.90-126
 WPB CODE OR ORDINANCES. PLEASE PROVIDE AN APPROVED
 LOCATION SUCH AS THE STORM DRAIN OR PERMEABLE GROUND.
  
 6) PASSED. P101: NOTE #6 REFERS TO CIVIL PLANS FOR ROOF
 DRAINAGE AND STORM DRAINAGE CONTINUATIONS. PLEASE
 PROVIDE THE CIVIL PLANS.
  
 7) FAILED. P001 & P101: ROOF DRAINAGE SYSTEM:
 A) PROVIDE CALCULATIONS FOR SIZING OF THE SYSTEM-
 SECTION 1106.1- 1106.5 FBC P.
 B) VERIFY PROPOSED ROOF DESIGN IS IN COMPLIANCE WITH
 SECTION 1101.7 FOR MAX PONDING DEPTH LOAD ETC.
 C) SHOW THE LOCATIONS OF EMERGENCY ROOF DRAINS OR
 OVERFLOW SCUPPERS, AND PROVIDE SIZING CALCULATIONS -
 SECTIONS 1108.1- 1108.3. SEE SECTION 1503.4 FBC B FOR
 SCUPPER DESIGN.
 D) IDENTIFY THE MAKE AND MODEL OF THE ROOF DRAIN SHOWN
 IN THE DETAIL AND SUBMIT MANUFACTURER?S SPECIFICATIONS-
 SECTIONS 1102.6 &1105.1.
 COMMENTS 6A-6D WERE NOT ADDRESSED
 REFER TO FIGURE 1106.5 FBC P: THE RAINFALL RATE IS
 CALCULATED AT 5"/HR.
  
 8) NEW COMMENT- SHEET P101: PROVIDE A BACKFLOW
 PREVENTER FOR THE WATER SUPPLY LINE TO THE REMOTE
 CHILLER- SECTION 608.3 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-06-04 Cont ID  
Sent By ccole Date 2020-06-04 Time 16:09 Rev Time 0.00
Received By ccole Date 2020-06-04 Time 13:59 Sent To  
Notes
2020-06-04 16:11:011ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20050095
 6/4/2020
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P-000: PROVIDE PLUMBING FIXTURE CALCULATIONS
 IN ACCORDANCE WITH TABLE 403.3 FBC P. PROVIDE A
 SCHEDULE THAT INDICATES THE REQUIRED AND PROVIDED
 NUMBER OF FIXTURES.
  
 2) PROVIDE ENLARGED DIMENSIONED TOILET ROOM FLOOR PLANS
 AND DETAILS SHOWING COMPLIANCE WITH THE FBC-17
 ACCESSIBILITY. THE ENLARGED DRAWINGS SHALL SHOW:
 A) CLEAR FLOOR SPACE DIMENSIONS FOR THE WATER CLOSETS-
 SECTION 604.3 FBC ACC.
 B) CLEAR FLOOR SPACE DIMENSIONS FOR THE LAVATORIES-
 SECTION 606.2.
 C) TOILET COMPARTMENT WIDTH AND LENGTH MEASUREMENTS-
 SECTIONS 604.2-604.8. FBC ACC, AND SECTION 405.3.1 FBC
 P.
 D) TOILET COMPARTMENT DOOR WIDTHS, DOOR SWINGS, AND
 WHEELCHAIR APPROACHES- SECTION 604.8.1.2 & 604.8.1.3
 FBC ACC.
 E) TURNING SPACE DIAMETERS- SECTION 304.3.
 F) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE WALLS
 OR PARTITIONS- SECTION 604.2.
  
 3) PROVIDE TOILET ROOM ELEVATION DRAWINGS INDICATING:
 A) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SECTION 604.4.
 B) HEIGHTS OF THE FRONT RIM OF THE LAVATORY FROM THE
 FINISHED FLOOR- SECTION 606.3
 C) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION
 306.
 D) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS- SECTION 604.5
 E) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS-
 SECTION 604.6.
 F) LOCATIONS, CLEARANCES, AND MOUNTING HEIGHTS FOR
 PAPER DISPENSERS- SECTION 604.7
 G) HEIGHTS OF THE MIRROR FROM THE FINISHED FLOOR TO THE
 BOTTOM OF THE REFLECTIVE SURFACES- SECTION 603.3.
  
 4) P-000 & P-101: REFER TO SECTION 211.1.2 FBC ACC, AND
 TABLE 404.3 FBC P. NO FEWER THAN TWO DRINKING FOUNTAINS
 SHALL BE PROVIDED. ONE DRINKING FOUNTAIN SHALL COMPLY
 WITH SECTIONS 602.1 ? 602.6, AND ONE SHALL COMPLY WITH
 602.7. SECTION 602.7 REQUIRES THAT SPOUT OUTLETS FOR
 STANDING PERSONS SHALL BE 38 INCHES MINIMUM AND 43
 INCHES MAXIMUM FROM THE FINISHED FLOOR. REVISE THE
 PLANS TO SHOW COMPLIAN E AND PROVIDE THESE DETAILS:
 A) THE CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR
 FORWARD WHEELCHAIR APPROACH- SECTION 602.2. FBC ACC.
 B) KNEE AND TOE CLEARANCES- SECTION 306.
 C) SPOUT HEIGHT AND SPOUT LOCATION- SECTION 602.4 AND
 602.5.
  
 5) P101: THE CONDENSATE FROM THE FCU'S SHALL NOT DRAIN
 INTO THE CITY SANITARY SEWER PER SEC.90-126 WPB CODE OR
 ORDINANCES. PLEASE PROVIDE AN APPROVED LOCATION SUCH AS
 THE STORM DRAIN OR PERMEABLE GROUND.
  
 6) P101: NOTE #6 REFERS TO CIVIL PLANS FOR ROOF
 DRAINAGE AND STORM DRAINAGE CONTINUATIONS. PLEASE
 PROVIDE THE CIVIL PLANS.
  
 7) P001 & P101: ROOF DRAINAGE SYSTEM:
 A) PROVIDE CALCULATIONS FOR SIZING OF THE SYSTEM-
 SECTION 1106.1- 1106.5 FBC P.
 B) VERIFY PROPOSED ROOF DESIGN IS IN COMPLIANCE WITH
 SECTION 1101.7 FOR MAX PONDING DEPTH LOAD ETC.
 C) SHOW THE LOCATIONS OF EMERGENCY ROOF DRAINS OR
 OVERFLOW SCUPPERS, AND PROVIDE SIZING CALCULATIONS -
 SECTIONS 1108.1- 1108.3. SEE SECTION 1503.4 FBC B FOR
 SCUPPER DESIGN.
 D) IDENTIFY THE MAKE AND MODEL OF THE ROOF DRAIN SHOWN
 IN THE DETAIL AND SUBMIT MANUFACTURER?S SPECIFICATIONS-
 SECTIONS 1102.6 &1105.1.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-07-09 Cont ID  
Sent By pvalenti Date 2020-07-09 Time 16:37 Rev Time 0.00
Received By pvalenti Date 2020-07-09 Time 14:13 Sent To  
Notes
2020-07-09 16:42:09PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 SIGNATURE REVIEW APPROVED WITH PROVISO:
  
 PRIOR TO INSPECTIONS DOCUMENTS THAT HAVE NOT BEEN
 DIGITALLY SIGNED/SEALED (INCLUDING THE NO THRESHOLD
 LETTER AND APPLICATION) MUST HAVE ORIGINAL SIGNATURES
 /SEALS.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-06-16 Cont ID  
Sent By pvalenti Date 2020-06-16 Time 10:15 Rev Time 0.00
Received By pvalenti Date 2020-06-16 Time 10:15 Sent To  
Notes
2020-06-16 10:18:52PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 SIGNATURE REVIEW APPROVED WITH PROVISO:
  
 ALL SUBMITTED PLAN SHEETS WILL BE SUBMITTED WITH
 ORIGINAL SIGNATURES AND SEALS AS PER CONTRACTOR.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-06-03 Cont ID  
Sent By pvalenti Date 2020-06-03 Time 15:52 Rev Time 0.00
Received By pvalenti Date 2020-06-03 Time 08:57 Sent To  
Notes
2020-06-03 16:11:22PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 SIGNATURE REVIEW DENIED:
  
 FBC B AND WPB AMENDMENTS 107.2.1, F.S. 471 & F.S.481,
 PLEASE PROVIDE DIGITAL SIGNATURES ON PLANS WITH THIRD
 PARTY VERIFICATION AS PER THE REQUIREMENTS OF THE
 FLORIDA STATUTES.

Review Stop Z ZONING
Rev No 3 Status P Date 2020-07-14 Cont ID  
Sent By eschneid Date 2020-07-14 Time 16:00 Rev Time 1.00
Received By eschneid Date 2020-07-14 Time 13:11 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2020-06-29 Cont ID  
Sent By eschneid Date 2020-06-29 Time 10:27 Rev Time 0.00
Received By eschneid Date 2020-06-25 Time 13:26 Sent To  
Notes
2020-06-26 16:28:43FAILED
  
 PROVIDE WRITTEN RESPONSE TO COMMENTS.
  
 1) REPEAT COMMENT: THE CITYPLACE RETAIL MANAGEMENT
 APPROVAL WAS NOT PROVIDED. THIS MAY BE STAMPED ON THE
 PLANS OR SEPARATE LETTER WHICH REFERENCES THE SPECIFIC
 PLANS THEY HAVE APPROVED. ---- THIS WAS STATED IN THE
 RESPONSE, BUT NOT PROVIDED.
  
 2) THE FOLLOWING REQUIRE SEPARATE BUILDING PERMIT
 APPLICATIONS WITH THEIR OWN SETS OF PLANS:
  
 A. THE WORK IN THE PARKING LOT (THIS IS ON A SEPARATE
 PARCEL).
 B. SIGNAGE - INCLUDING THE INTERIOR LUCID SIGN THAT IS
 VISIBLE OUTSIDE THE BUILDING
  
 3) REPEAT COMMENT: THE PLANS SHEETS SHOWING THE
 SPECIFICS FOR THE ITEMS LISTED IN COMMENT 2 MUST BE
 REMOVED FROM THE PLAN SET AS PART OF THE INTERIOR BUILD
 OUT RESUBMITTAL. ---- NOT ALL SHEETS REMOVED. EX. SHEET
 A-200, E-202.
  
 4) THE PAVER PATTERN UNDER THE CANOPY AND WITHIN THE
 LEASE LINE IS REQUIRED TO BE A DIFFERENT PATTERN AND
 COLOR THAN THE PLAZA OUTSIDE OF THE LEASE LINE TO
 CLEARLY DIFFERENTIATE THE PATIO FROM THE PLAZA. THIS
 NEEDS TO BE INDICATED ON THE PLANS. EX. SHEETS A-101,
 A-202. NOTE: SHEET L1.00 IS NOT THE LATEST, APPROVED
 VERSION OF THIS SHEET.
  
 5) THE PLANS MAY NOT SHOW THE DISPLAY CARS OUTSIDE OF
 THE LEASE LINE. EX. SHEET A-203, E-101
  
 6) PROVIDE THE PHOTOMETRIC CALCULATIONS FOR THE
 EXTERIOR LIGHTING BEING PROPOSED AT THE CANOPY. THE
 LIGHTING MUST MEET THE REQUIREMENTS OF SECTION
 94-113(B) EXTERIOR LIGHTING "ALL BUILDINGS SHALL
 PROVIDE EXTERIOR LIGHTING EVERY NIGHT FROM DUSK TO DAWN
 TO ILLUMINATE BUILDING ENTRANCES, ADJACENT SIDEWALKS,
 AND PATHS, AT A MINIMUM OF 0.6 FOOTCANDLES AS MEASURED
 AT THE BACK EDGE OF THE CURB AND ONE FOOT ABOVE THE
 SIDEWALK. THIS MEASUREMENT SHALL INCLUDE LIGHT
 EMANATING FROM PUBLIC AND PRIVATE SOURCES. UNSHIELDED
 LIGHT FIXTURES SHALL BE PROHIBITED." ADDITIONALLY, THE
 LIGHTING MAY NOT CREATE GLARE TO THE ADJACENT
 RIGHTS-OF-WAY.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
 [email protected]
  
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2020-05-20 Cont ID  
Sent By eschneid Date 2020-05-20 Time 15:39 Rev Time 2.00
Received By eschneid Date 2020-05-20 Time 11:17 Sent To  
Notes
2020-05-20 15:41:15FAILED
  
 PROVIDE WRITTEN RESPONSE TO COMMENTS.
  
 1) THE CITYPLACE RETAIL MANAGEMENT APPROVAL WAS NOT
 PROVIDED. THIS MAY BE STAMPED ON THE PLANS OR SEPARATE
 LETTER WHICH REFERENCES THE SPECIFIC PLANS THEY HAVE
 APPROVED.
  
 2) THE FOLLOWING REQUIRE SEPARATE BUILDING PERMIT
 APPLICATIONS WITH THEIR OWN SETS OF PLANS:
  
 A. THE EXTERIOR CANOPY.
 B. THE EXTERIOR PLAZA WORK.
 C. THE WORK IN THE PARKING LOT (THIS IS ON A SEPARATE
 PARCEL).
 D. SIGNAGE ? INCLUDING THE INTERIOR LUCID SIGN THAT IS
 VISIBLE OUTSIDE THE BUILDING
  
 3) THE PLANS SHEETS SHOWING THE SPECIFICS FOR THE ITEMS
 LISTED IN COMMENT 2 MUST BE REMOVED FROM THE PLAN SET
 AS PART OF THE INTERIOR BUILD OUT RESUBMITTAL.
  
 4) THE INTERIOR LUCID SIGN IS REQUIRED TO BE PERMITTED
 WITH THE SIGN PERMIT AND COUNTS AGAINST THE ALLOWED
 SQUARE FOOTAGE AS IT IS VISIBLE FROM THE EXTERIOR OF
 THE BUILDING.
  
 5) PROVIDE THE TRANSPARENCY CALCULATIONS FOR THE WEST
 AND SOUTH ELEVATIONS. A MINIMUM OF 50% TRANSPARENCY IS
 REQUIRED ON EACH FRONTAGE BETWEEN GRADE AND 10 FEET IN
 HEIGHT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy