Plan Review Details - Permit 20050053
Plan Review Stops For Permit 20050053
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-09-22 Cont ID  
Sent By jwitmer Date 2020-09-22 Time 11:44 Rev Time 0.00
Received By jwitmer Date 2020-09-22 Time 11:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-07-20 Cont ID  
Sent By jwitmer Date 2020-07-20 Time 09:28 Rev Time 0.00
Received By jwitmer Date 2020-07-20 Time 09:02 Sent To  
Notes
2020-07-20 09:26:24WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20050053
 ADD: 1321 ALPHA ST. / GAZEBO
 CONT: TBD/ TO BE DETERMINED
 TEL: 561-568-8045 CONTACT: MICHAEL SANCHEZ
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
  
 1ST REVIEW
 DATE: MON. JULY 20/2020
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION STATES THIS PERMIT IS FOR THE
 BUILDING OF A GAZEBO. SHEET S7.0 HAS THE FOUNDATION
 PLAN AND ROOF FRAMING PLAN BOTH PLANS HAVE CUT SECTIONS
 THROUGH THE PLAN SHOWING THEY CAN BE FOUND ON SHEET
 S7.1. THIS REVIEW CYCLE THERE WAS NO SHEET S7.1
 SUBMITTED.
 SHEET S7.0 HAS NO FOUNDATION SCHEDULE, NOTES FOUND ON
 THIS SHEET INCLUDE FOUNDATION ME10, F-40, DETAIL 2/S7.1
 AND FOR COLUMNS CC1 ?
 2) THERE IS NO WIND DESIGN CRITERIA GIVEN FOR THE OPEN
 GAZEBO. 2017 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 2.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
  
 2.2. RISK CATEGORY.
  
 2.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE. ASCE 7-10 TABLE 30.3.1.
  
 2.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 2.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED
 BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR
 THE DESIGN OF THE STRUCTURE, PSF.
  
 2.6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING. 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 3) IT IS UNCLEAR AS TO THE DESIGN OF THE ROOF IF
 ROOFING PRODUCT APPROVALS WILL BE REQUIRED.
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES,
  
 4) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-08-06 Cont ID  
Sent By jleahy Date 2020-08-06 Time 16:20 Rev Time 0.00
Received By jleahy Date 2020-08-06 Time 16:12 Sent To  
Notes
2020-08-06 16:21:32GAZEBO ONLY PERMIT JLEAHY

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-07-17 Cont ID  
Sent By pleduc Date 2020-07-17 Time   Rev Time 0.00
Received By pleduc Date 2020-07-17 Time 10:31 Sent To  
Notes
2020-07-17 10:42:06INSTALL A 10LB ABC FIRE EXTINGUISHER
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2020-09-22 Cont ID  
Sent By jesmith Date 2020-09-22 Time 17:20 Rev Time 0.00
Received By jesmith Date 2020-09-22 Time 17:14 Sent To  
Notes
2020-09-22 17:15:23CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20050053 1321 ALPHA ST
  
 REGARDING RESPONSE LETTER DATED 9/15/2020, ?N/A. GAS
 GRILL HAS A PORTABLE REMOVABLE TANK.?
 COMMENT. A SEPARATE GAS PERMIT AND INSPECTIONS ARE
 STILL REQUIRED. THE GRILL IS ADDRESSED IN FBC FG 623.1
 COOKING APPLIANCES. PROPANE BOTTLES INCLUSIVE OF
 PORTABLE ARE ADDRESSED IN NFPA 58-14 CHAPTER 5.
 IN ACCORDANCE WITH 2017 WPB AMENDMENTS TO THE FBC, A
 PERMIT APPLICATION SHALL BE SUBMITTED BY A CERTIFIED
 GAS INSTALLER. PROVIDE MANUFACTURER?S
 SPECIFICATION/INSTALLATION MANUAL, LP TANK SUBMITTAL
 AND HOSE /REGULATOR SUBMITTAL.
 SUBMIT PLAN SHEETS G-1.2 AND P1.0 AND REFERENCE THOSE
 PLANS AND THE PERMIT NUMBER 20050053 AS MASTER PERMIT
 ON THE PERMIT APPLICATION NEGATING THE NEED FOR THE
 INSTALLER TO PROVIDE A SEPARATE DRAWING. INDICATE ON
 G-1.2 STORAGE LOCATION OF TANK, IF LEFT AT SITE AND HOW
 IT IS SECURED. INDICATE ON P1.0 THE LOCATION OF THE GAS
 GRILL.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 AGAIN, TO HELP EXPEDITE A REVIEW IT WOULD BE HELPFUL
 WHEN SUBMITTING THE APPLICATION, THIS PERMIT NUMBER BE
 REFERENCED.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2020-08-04 Cont ID  
Sent By jesmith Date 2020-08-04 Time 10:39 Rev Time 0.00
Received By jesmith Date 2020-08-04 Time 10:38 Sent To  
Notes
2020-08-04 10:39:03CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20050053 1321 ALPHA ST
  
 A GAS GRILL IS SHOWN ON 021 G-1.2 SITE DETAILS. A GAS
 PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL PACKAGE. A
 GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT THIS TIME. A
 SEPARATE GAS PERMIT AND PLANS WILL BE REQUIRED FOR A
 CONTRACTOR TO PERFORM THE RELATED WORK. PROVIDE
 COMPLETE PLANS, APPLIANCE/ EQUIPMENT SPECIFICATIONS AND
 GAS RISER THAT REFLECT THE ENTIRE SCOPE OF GAS WORK TO
 BE DONE. WPB AMEND. TO FBC SEC. 107.2.1.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
 A SEPARATE PERMIT AND PLANS ARE REQUIRED FOR THE GAS
 INSTALLATION OR MODIFICATION OF SYSTEM.
 TO HELP EXPEDITE A REVIEW IT WOULD BE HELPFUL WHEN
 SUBMITTING THE APPLICATION, THIS PERMIT NUMBER BE
 REFERENCED.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-11-19 Cont ID  
Sent By lmarchan Date 2020-11-19 Time 07:39 Rev Time 0.00
Received By lmarchan Date 2020-09-18 Time 07:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-08-20 Cont ID  
Sent By shill Date 2020-08-20 Time 17:35 Rev Time 0.00
Received By shill Date 2020-07-16 Time 10:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-09-22 Cont ID  
Sent By jesmith Date 2020-09-22 Time 17:27 Rev Time 0.00
Received By jesmith Date 2020-09-22 Time 16:16 Sent To  
Notes
2020-09-22 17:27:44PLUMBING COMMENTS: APPROVED
  
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
  
  
 20050053 1321 ALPHA ST
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-08-04 Cont ID  
Sent By jesmith Date 2020-08-04 Time 09:34 Rev Time 0.00
Received By jesmith Date 2020-08-04 Time 09:06 Sent To  
Notes
2020-08-04 09:34:03CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20050053 1321 ALPHA ST
  
 A GAS GRILL IS SHOWN ON 021 G-1.2 SITE DETAILS. A GAS
 PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL PACKAGE. A
 GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT THIS TIME. A
 SEPARATE GAS PERMIT AND PLANS WILL BE REQUIRED FOR A
 CONTRACTOR TO PERFORM THE RELATED WORK. PROVIDE
 COMPLETE PLANS, APPLIANCE/ EQUIPMENT SPECIFICATIONS AND
 GAS RISER THAT REFLECT THE ENTIRE SCOPE OF GAS WORK TO
 BE DONE. WPB AMEND. TO FBC SEC. 107.2.1.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
 A SEPARATE PERMIT AND PLANS ARE REQUIRED FOR THE GAS
 INSTALLATION OR MODIFICATION OF SYSTEM.
  
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 1. PE DIGITAL SIGNATURES FOR PLUMBING AND ELECTRICAL
 DRAWINGS ARE NOT VALID; PER THE WPB AMENDMENTS TO THE
 FBC, EACH SHEET OF PLAN IS REQUIRED TO BE SIGNED AND
 SEALED BY THE PERSON RESPONSIBLE FOR THE DESIGN. A
 DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE WITH THE
 PROPER THIRD PARTY VERIFICATION. THE DIGITAL SIGNATURE
 MUST INCLUDE THE STATEMENT "SIGNED AND SEALED" AS PER
 FAC 61G15-23.004. PROVIDE CORRECTION. WPB FBC 107.1; FS
 471/481
  
 2. PER WPB FBC 107.2.1, PROVIDE PLAN SHEET P6.1
 REFERENCED ON PLAN SHEET P1.0 TO SHOW HOSE BIB
 LOCATIONS AND PROVIDE A WATER RISER DIAGRAM.
  
  
 A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT
 THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A
 RESPONSE NARRATIVE ADDRESSING THE PLUMBING COMMENTS
 FROM THE FIRST REVIEW.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE
 DESIGNER IN ACCORDANCE WITH FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-09-22 Cont ID  
Sent By jesmith Date 2020-09-22 Time 17:28 Rev Time 0.00
Received By jesmith Date 2020-09-22 Time 17:28 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-08-04 Cont ID  
Sent By jesmith Date 2020-08-04 Time 09:36 Rev Time 0.00
Received By jesmith Date 2020-08-04 Time 09:35 Sent To  
Notes
2020-08-04 09:36:14PE DIGITAL SIGNATURES FOR PLUMBING AND ELECTRICAL
 DRAWINGS REQUIRE THIRD PARTY CERTIFICATION; PER THE WPB
 AMENDMENTS TO THE FBC, EACH SHEET OF PLAN IS REQUIRED
 TO BE SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR
 THE DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. THE DIGITAL
 SIGNATURE MUST INCLUDE THE STATEMENT "SIGNED AND
 SEALED" AS PER FAC 61G15-23.004. PROVIDE CORRECTION.
 WPB FBC 107.1; FS 471/481.
 001.1 SURVEY SHEET 2 OF 2 IS NOT DIGITALLY SIGNED AND
 SEALED.
 002 SITE PLAN SP-1 IS NOT DIGITALLY SIGNED AND SEALED.
 021 G-1.2 SITE DETAILS IS NOT DIGITALLY SIGNED AND
 SEALED.
  

Review Stop Z ZONING
Rev No 2 Status P Date 2020-11-16 Cont ID  
Sent By ajones Date 2020-11-16 Time 16:51 Rev Time 0.00
Received By ajones Date 2020-10-14 Time 10:51 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2020-08-18 Cont ID  
Sent By avann Date 2020-08-18 Time 16:30 Rev Time 0.00
Received By ajones Date 2020-08-18 Time 16:29 Sent To  
Notes
2020-08-18 16:31:568-18-20- FAILED. WAITING ON THE REVIEW AND APPROVAL OF
 A MINOR PD AMENDMENT.
  
 ANGELLA VANN
 [email protected]
 561-822-1441