| 2020-05-20 06:46:59 | REVIEWED BY JERRY SMITH: |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 20050041 609 8TH ST |
| | |
| | |
| | 1ST REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | 1. PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN INDICATING |
| | THE MAKE AND MODEL OF THE PUMP PER WPB FBC 107.2.1. |
| | 2. WELL SUPPLIED IRRIGATION SYSTEM SHALL NOT IN ANY WAY |
| | BE CONNECTED TO THE POTABLE WATER SYSTEM. PER WPB FBC |
| | 107.2.1, PROVIDE DETAIL AND INSTRUCTION FOR REMOVAL OF |
| | BACKFLOW DEVICE AND CAPPING OF POTABLE WATER SYSTEM, |
| | PHYSICALLY SEPARATING THE TWO SYSTEMS AND ELIMINATING |
| | ANY POSSIBLE CROSS CONNECTION AS REQUIRED BY FBC PL |
| | 608.1. |
| | 3. THE TEXT IN NOTE 12 ON THE PUMP DETAIL IS OBSCURED. |
| | PER WPB FBC 107.2.1, CLARIFY. |
| | |
| | ADDITIONAL COMMENTS |
| | A SEPARATE PERMIT MAY BE REQUIRED FOR THE WELL |
| | A SEPARATE ELECTRICAL PERMIT MAY BE REQUIRED FOR THE |
| | PUMP |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | ALL PLANS TO BE SIGNED AND SEALED BY THE DESIGNER AS |
| | REQUIRED BY FAC AND FS. |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-246-0882 MOBILE |
| | |
| | 20050041 609 8TH ST |
| | |
| | |