| 2020-07-14 15:48:26 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 20050034 600 @ CLEMATIS ST |
| | |
| | 2ND REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | |
| | ORIGINAL COMMENT #1 |
| | 1. PLAN SHEET L2.03 INDICATES AN EXISTING CONTROLLER |
| | FOR THE SYSTEM. PLAN SHEET L2.12 SECTION 2.14 APPEARS |
| | TO REQUIRE A NEW CONTROLLER WITH SPECIFIC REQUIREMENTS. |
| | PER WPB FBC 107.2.1, CLARIFY. |
| | |
| | RESPONSE |
| | PER THE AS BUILT PLANS PROVIDED BY THE CITY, VALVES FOR |
| | THIS BLOCK WILL USE EXISTING METER, CONTROLLER AND RAIN |
| | SENSOR (DISCUSS ASBUILT SCHEDULE L2.00) |
| | ORIGINAL COMMENT #2 |
| | |
| | |
| | 2. PER WPB FBC 107.2.1, PROVIDE LOCATION OF THE |
| | REQUIRED RAIN SENSOR AND NOTE EXISTING OR NEW. |
| | |
| | RESPONSE |
| | EXISTING CONTROLLER AND RAIN SENSOR LOCATED AT THE |
| | POLICE STATION (BEHIND DUMPSTER ENCLOSURE, OFF BANYAN |
| | BLVD.) TO BE USED FOR THIS BLOCK. |
| | |
| | |
| | NEW COMMENT |
| | PER WPB FBC 107.2.1, PROVIDE ON THE PLAN AT WHAT |
| | APPEARS TO BE THE SERVICE CONNECTION A NOTE STATING |
| | THAT |
| | 1. EXISTING CONTROLLER AND RAIN SENSOR LOCATED AT THE |
| | POLICE STATION (BEHIND DUMPSTER ENCLOSURE, OFF BANYAN |
| | BLVD.) TO BE USED FOR THIS BLOCK. |
| | 2. CONNECT TO EXISTING METER, CONTROLLER AND BACKFLOW |
| | PREVENTOR |
| | |
| | PROVISO: A FIELD INSPECTOR'S APPROVAL WHICH WILL |
| | INCLUDE FIELD REVIEW OF EXISTING BACKFLOW PREVENTER, |
| | CONTROLLER AND RAIN SENSOR FOR COMPLIANCE WILL BE |
| | REQUIRED AT TIME OF INSPECTION |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE |
| | DESIGNER IN ACCORDANCE WITH FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-246-0882 MOBILE |
| | |
| | 20050034 600 @ CLEMATIS ST |
| | |