Plan Review Details - Permit 20050006
Plan Review Stops For Permit 20050006
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2020-06-02 Cont ID  
Sent By pvalenti Date 2020-06-02 Time 07:37 Rev Time 0.00
Received By pvalenti Date 2020-06-02 Time 07:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2020-05-26 Cont ID  
Sent By rmcphers Date 2020-05-26 Time 08:57 Rev Time 0.00
Received By rmcphers Date 2020-05-26 Time 08:57 Sent To  
Notes
2020-05-26 08:58:02ROOFING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
  
 ***AN INSPECTION LETTER FROM AN ENGINEER DOES NOT TAKE
 THE PLACE OF THE ADDITIONAL ATTACHMENT DETAILS REQUIRED
 IN THE REVIEW COMMENTS.***
  
 1) PLEASE PROVIDE SIGNED AND SEALED ADDITIONAL
 ATTACHMENT DETAILS FROM AN ARCHITECT OR ENGINEER FOR
 ROOF ZONES 2 AND 3 WHICH REQUIRE HIGHER WIND PRESSURES
 THAN THE MAXIMUM SHOWN ON THE PRODUCT APPROVAL (-52.5)
 - SEE GENERAL LIMITATION NUMBER 7 ON THE PRODUCT
 APPROVAL.
 2) SIGNED AND SEALED ENGINEERING PROVIDED WILL NEED TO
 BE DIGITALLY SIGNED AND SEALED BY THE ENGINEER TO BE
 USED IN ELECTRONIC PLAN REVIEW.
  
 FYI - 668.003(2) AND (3), F.S.
 (2) A PROFESSIONAL ENGINEER UTILIZING A DIGITAL
 SIGNATURE TO ELECTRONICALLY SIGN AND SEAL ENGINEERING
 PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS SHALL HAVE
 THEIR IDENTITY AUTHENTICATED BY A CERTIFICATION
 AUTHORITY

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2020-05-18 Cont ID  
Sent By rmcphers Date 2020-05-18 Time 10:50 Rev Time 0.00
Received By rmcphers Date 2020-05-18 Time 10:50 Sent To  
Notes
2020-05-18 10:54:01ROOFING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
  
 ***AN INSPECTION LETTER FROM AN ENGINEER DOES NOT TAKE
 THE PLACE OF THE ADDITIONAL ATTACHMENT DETAILS REQUIRED
 IN THE REVIEW COMMENTS.***
  
 1) PLEASE PROVIDE SIGNED AND SEALED ADDITIONAL
 ATTACHMENT DETAILS FROM AN ARCHITECT OR ENGINEER FOR
 ROOF ZONES 2 AND 3 WHICH REQUIRE HIGHER WIND PRESSURES
 THAN THE MAXIMUM SHOWN ON THE PRODUCT APPROVAL (-52.5)
 - SEE GENERAL LIMITATION NUMBER 7 ON THE PRODUCT
 APPROVAL.
 2) SIGNED AND SEALED ENGINEERING PROVIDED WILL NEED TO
 BE DIGITALLY SIGNED AND SEALED BY THE ENGINEER TO BE
 USED IN ELECTRONIC PLAN REVIEW.
  
 FYI - 668.003(2) AND (3), F.S.
 (2) A PROFESSIONAL ENGINEER UTILIZING A DIGITAL
 SIGNATURE TO ELECTRONICALLY SIGN AND SEAL ENGINEERING
 PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS SHALL HAVE
 THEIR IDENTITY AUTHENTICATED BY A CERTIFICATION
 AUTHORITY

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-05-11 Cont ID  
Sent By rmcphers Date 2020-05-11 Time 13:48 Rev Time 0.00
Received By rmcphers Date 2020-05-11 Time 13:48 Sent To  
Notes
2020-05-11 13:50:30ROOFING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE SIGNED AND SEALED ADDITIONAL
 ATTACHMENT DETAILS FROM AN ARCHITECT OR ENGINEER FOR
 ROOF ZONES 2 AND 3 WHICH REQUIRE HIGHER WIND PRESSURES
 THAN THE MAXIMUM SHOWN ON THE PRODUCT APPROVAL - SEE
 GENERAL LIMITATION NUMBER 7 ON THE PRODUCT APPROVAL.
 2) SIGNED AND SEALED ENGINEERING PROVIDED WILL NEED TO
 BE DIGITALLY SIGNED AND SEALED BY THE ENGINEER TO BE
 USED IN ELECTRONIC PLAN REVIEW.
 668.003(2) AND (3), F.S.
 (2) A PROFESSIONAL ENGINEER UTILIZING A DIGITAL
 SIGNATURE TO ELECTRONICALLY SIGN AND SEAL ENGINEERING
 PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS SHALL HAVE
 THEIR IDENTITY AUTHENTICATED BY A CERTIFICATION
 AUTHORITY

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-05-04 Cont ID  
Sent By rmcphers Date 2020-05-04 Time 09:26 Rev Time 0.00
Received By rmcphers Date 2020-05-04 Time 08:56 Sent To  
Notes
2020-05-04 09:25:42ROOFING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE CIRCLE THE "FASTENING OPTION" IN THE FLAT
 DECK PRODUCT APPROVAL PROVIDED.
 2) IF NEEDED PLEASE PROVIDE SIGNED AND SEALED
 ADDITIONAL ATTACHMENT DETAILS FROM AN ARCHITECT OR
 ENGINEER FOR ROOF ZONES 2 AND 3 WHICH MAY REQUIRE
 HIGHER WIND PRESSURES THAN THE MAXIMUM SHOWN ON THE
 PRODUCT APPROVAL - SEE GENERAL LIMITATION NUMBER 7 ON
 THE PRODUCT APPROVAL.
 3) SIGNED AND SEALED ENGINEERING PROVIDED WILL NEED TO
 BE DIGITALLY SIGNED AND SEALED BY THE ENGINEER TO BE
 USED IN ELECTRONIC PLAN REVIEW.
 668.003(2) AND (3), F.S.
 (2) A PROFESSIONAL ENGINEER UTILIZING A DIGITAL
 SIGNATURE TO ELECTRONICALLY SIGN AND SEAL ENGINEERING
 PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS SHALL HAVE
 THEIR IDENTITY AUTHENTICATED BY A CERTIFICATION
 AUTHORITY
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2020-06-02 Cont ID  
Sent By pvalenti Date 2020-06-02 Time 07:37 Rev Time 0.00
Received By pvalenti Date 2020-06-02 Time 07:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-05-26 Cont ID  
Sent By rmcphers Date 2020-05-26 Time 08:58 Rev Time 0.00
Received By rmcphers Date 2020-05-18 Time 15:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-05-18 Cont ID  
Sent By rmcphers Date 2020-05-18 Time 10:54 Rev Time 0.00
Received By rmcphers Date 2020-05-14 Time 14:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-05-11 Cont ID  
Sent By rmcphers Date 2020-05-11 Time 13:50 Rev Time 0.00
Received By rmcphers Date 2020-05-08 Time 14:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-05-04 Cont ID  
Sent By rmcphers Date 2020-05-04 Time 09:26 Rev Time 0.00
Received By rmcphers Date 2020-05-01 Time 13:42 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2020-06-02 Cont ID  
Sent By pvalenti Date 2020-06-02 Time 07:37 Rev Time 0.00
Received By pvalenti Date 2020-06-02 Time 07:37 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2020-05-26 Cont ID  
Sent By rmcphers Date 2020-05-26 Time 08:58 Rev Time 0.00
Received By rmcphers Date 2020-05-26 Time 08:58 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2020-05-18 Cont ID  
Sent By rmcphers Date 2020-05-18 Time 10:54 Rev Time 0.00
Received By rmcphers Date 2020-05-18 Time 10:54 Sent To  
Notes
2020-05-18 10:54:41SEE BUILDING PLAN REVIEW

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-05-11 Cont ID  
Sent By rmcphers Date 2020-05-11 Time 13:50 Rev Time 0.00
Received By rmcphers Date 2020-05-11 Time 13:50 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-05-04 Cont ID  
Sent By rmcphers Date 2020-05-04 Time 09:25 Rev Time 0.00
Received By rmcphers Date 2020-05-04 Time 09:25 Sent To  
Notes
***NONE***