Plan Review Details - Permit 20041185
Plan Review Stops For Permit 20041185
Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-06-02 Cont ID  
Sent By jpearson Date 2020-06-02 Time 12:10 Rev Time 0.00
Received By jpearson Date 2020-06-02 Time 10:55 Sent To  
Notes
2020-06-02 12:10:41CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NOTHING ABOUT THIS REVISION MAKES SENSE. THE
 REVISION SHEET SUBMITTED STATES THAT THIS IS ELECTRICAL
 CHANGES TO 19020657, BUT THE ELECTRICAL PERMIT FOR THIS
 HAS BEEN CLOSED. IN OUR SYSTEM, IT STATES THIS IS A
 REVISION TO 19070714 WHICH HAS BEEN REVOKED. THE PLANS
 UPLOADED ARE FIRE ALARM PLANS AND ONE SHEET OF A
 TECHNOLOGY PLAN, NEITHER OF WHICH SHOW ELECTRICAL
 OUTLETS. FIRE ALARM IS A SEPARATE PERMIT. WHAT IS THE
 PURPOSE OF THIS REVISION? IF NEW WORK HAS BEEN
 COMPLETED AFTER THE ELECTRICAL PERMIT IS CLOSED, A NEW
 PERMIT WILL BE REQUIRED. IT IS RECOMMENDED THAT YOU
 CONTACT REVIEWER TO DISCUSS. WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-06-02 Cont ID  
Sent By jleahy Date 2020-05-18 Time 08:16 Rev Time 0.00
Received By jpearson Date 2020-05-18 Time 08:09 Sent To  
Notes
2020-06-02 12:06:06CHANGED STATUS BASED ON 2ND REVIEW.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-05-22 Cont ID  
Sent By pleduc Date 2020-05-22 Time   Rev Time 0.00
Received By pleduc Date 2020-05-22 Time 13:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-06-02 Time   Rev Time 0.00
Received By lmarchan Date 2020-05-21 Time 15:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-05-18 Cont ID  
Sent By jleahy Date 2020-05-18 Time 08:17 Rev Time 0.00
Received By jleahy Date 2020-04-30 Time 16:13 Sent To  
Notes
2020-05-07 16:14:50PAPER PLAN CONVERTED TO DIGITAL FOR REVIEW. PLAN NO
 SIGNED AND SEALED. MASTER WAS DIGITAL SUBMITTAL. JG.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-06-02 Cont ID  
Sent By jpearson Date 2020-06-02 Time 12:13 Rev Time 0.00
Received By jpearson Date 2020-06-02 Time 12:13 Sent To  
Notes
2020-06-02 12:13:08PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A
 DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY
 VERIFICATION. PROVIDE CORRECTION. THE TECHNOLOGY SHEET
 DOES NOT HAVE A DIGITAL SIGNATURE. WPB FBC 107.1; FS
 471/481

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-05-18 Cont ID  
Sent By jleahy Date 2020-05-18 Time 08:16 Rev Time 0.00
Received By jleahy Date 2020-05-18 Time 08:16 Sent To  
Notes
2020-05-07 16:10:37PAPER PLAN CONVERTED TO DIGITAL FOR REVIEW. PLAN NO
 SIGNED AND SEALED. MASTER WAS DIGITAL SUBMITTAL. JG.