Plan Review Details - Permit 20041164
Plan Review Stops For Permit 20041164
Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2020-06-24 Cont ID  
Sent By lmarchan Date 2020-06-24 Time 14:21 Rev Time 0.00
Received By lmarchan Date 2020-06-17 Time 09:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2020-06-17 Cont ID  
Sent By lmarchan Date 2020-06-17 Time 09:27 Rev Time 0.00
Received By lmarchan Date 2020-06-10 Time 10:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2020-06-10 Cont ID  
Sent By lmarchan Date 2020-06-10 Time 09:35 Rev Time 0.00
Received By lmarchan Date 2020-06-03 Time 16:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-06-03 Cont ID  
Sent By lmarchan Date 2020-06-03 Time 15:50 Rev Time 0.00
Received By lmarchan Date 2020-05-21 Time 09:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-05-21 Cont ID  
Sent By lmarchan Date 2020-05-21 Time 09:07 Rev Time 0.00
Received By lmarchan Date 2020-05-13 Time 13:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-05-12 Cont ID  
Sent By cpuell Date 2020-05-12 Time 10:34 Rev Time 0.00
Received By cpuell Date 2020-05-06 Time 14:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-05-01 Cont ID  
Sent By lmarchan Date 2020-05-01 Time 08:34 Rev Time 0.00
Received By lmarchan Date 2020-04-30 Time 11:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2020-06-24 Cont ID  
Sent By medwards Date 2020-06-24 Time 09:30 Rev Time 0.00
Received By medwards Date 2020-06-24 Time 14:01 Sent To  
Notes
2020-06-24 09:33:27THERE APPEARS TO BE NO NEW REVISIONS IN THIS UPLOAD.
 THE PROJECT WAS APPROVED IN THE 6TH CYCLE.

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2020-06-15 Cont ID  
Sent By medwards Date 2020-06-15 Time 10:52 Rev Time 0.00
Received By medwards Date 2020-06-15 Time 10:50 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2020-06-08 Cont ID  
Sent By medwards Date 2020-06-08 Time 10:23 Rev Time 0.00
Received By medwards Date 2020-06-08 Time 09:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2020-05-26 Cont ID  
Sent By medwards Date 2020-05-26 Time 15:45 Rev Time 0.00
Received By medwards Date 2020-05-26 Time 15:34 Sent To  
Notes
2020-05-26 15:47:22NOTHING IN THIS SUBMISSION ADDRESSES THE 3RD CYCLE
 COMMENTS REVIEWER WROTE. PLEASE ADDRESS THE 3RD CYCLE
 REVIEW COMMENTS AND RESUBMIT.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2020-05-20 Cont ID  
Sent By medwards Date 2020-05-20 Time 13:44 Rev Time 0.00
Received By medwards Date 2020-05-20 Time 13:44 Sent To  
Notes
2020-05-20 13:44:58REVIEW FBC-2017 MECHANICAL
 PERMIT-20041164
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE REFRIGERANT CLASSIFICATION, AMOUNT
 AND OEL FOR THE REFRIGERANT R-448A IN LINE WITH TABLE
 1103.1. FBC M 1102.2
  
 2) PLEASE PROVIDE VOLUME CALCULATIONS FOR ALL THE
 REFRIGERATION SYSTEMS. FBC M 1104.4
  
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2020-05-07 Cont ID  
Sent By medwards Date 2020-05-07 Time 08:27 Rev Time 0.00
Received By medwards Date 2020-05-07 Time 07:28 Sent To  
Notes
2020-05-07 08:28:062ND REVIEW FBC-2017 MECHANICAL
 PERMIT-20041164
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SEE 1ST CYCLE REVIEW COMMENTS. PLEASE PROVIDE
 DATA FOR ALL REFRIGERATION EQUIPMENT. FBC FS 107.2.1
 2) PLEASE PROVIDE REQUIRED INFORMATION ABOUT SYSTEMS
 PER- FBC M 1102.1
 3) PLEASE PROVIDE CALCULATIONS FOR ENTIRE SYSTEM. FBC M
 1104.4
 4)
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-05-01 Cont ID  
Sent By medwards Date 2020-05-01 Time 07:36 Rev Time 0.00
Received By medwards Date 2020-05-01 Time 07:20 Sent To  
Notes
2020-05-01 07:37:191ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20041164
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 THIS PERMIT IS FOR THE REFRIGERATION SYSTEMS FOR THE
 RACETRAC. PLEASE SUBMIT CODE COMPLIANT DRAWINGS
 ADDRESSING REQUIREMENTS FROM CHAPTER 11 OF THE FBC M
 CODE FOR THE REFRIGERATION FOR ALL EQUIPMENT ON THIS
 PROJECT. THE DOCUMENTS UPLOADED WITH THIS PROJECT ARE
 FOR THE MECHANICAL SYSTEMS ON THIS PROJECT. I CANNOT DO
 A REVIEW FOR THE REFRIGERATION ON THIS PROJECT UNTIL
 THE CORRECT DOCUMENTS HAVE BEEN SUBMITTED. FBC FS
 107.2.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 7 Status P Date 2020-06-24 Cont ID  
Sent By medwards Date 2020-06-24 Time 14:01 Rev Time 0.00
Received By medwards Date 2020-06-24 Time 14:01 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status F Date 2020-06-15 Cont ID  
Sent By medwards Date 2020-06-15 Time 10:52 Rev Time 0.00
Received By medwards Date 2020-06-15 Time 10:52 Sent To  
Notes
2020-06-15 10:54:16ROOF PLAN STILL HAS NOT BEEN SIGNED AND SEALED BY THE
 DESIGNER.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status F Date 2020-06-09 Cont ID  
Sent By medwards Date 2020-06-09 Time 17:30 Rev Time 0.00
Received By medwards Date 2020-06-08 Time 10:24 Sent To  
Notes
2020-06-09 17:31:19THE MECHANICAL ROOF PLAN STILL NEEDS TO BE SIGNED AND
 SEALED BY THE DESIGNER.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2020-05-26 Cont ID  
Sent By medwards Date 2020-05-26 Time 15:48 Rev Time 0.00
Received By medwards Date 2020-05-26 Time 15:47 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2020-05-21 Cont ID  
Sent By medwards Date 2020-05-21 Time 08:26 Rev Time 0.00
Received By medwards Date 2020-05-21 Time 08:26 Sent To  
Notes
2020-05-21 08:28:52BOTH MECHANICAL SHEETS AND THE ROOF SHEET STILL HAVE
 NOT BEEN DIGITALLY SIGNED AND STAMPED BY THE DESIGNER.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-05-07 Cont ID  
Sent By medwards Date 2020-05-07 Time 09:05 Rev Time 0.00
Received By medwards Date 2020-05-07 Time 09:00 Sent To  
Notes
2020-05-07 09:05:18SHEETS - M001, M120, M120 DO NOT HAVE A SIGNATURE OR A
 SEAL FROM THE DESIGNER.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-05-01 Cont ID  
Sent By medwards Date 2020-05-01 Time 07:37 Rev Time 0.00
Received By medwards Date 2020-05-01 Time 07:37 Sent To  
Notes
2020-05-01 07:40:06PLEASE MAKE SURE THE DESIGNER OF THE REFRIGERATION
 DRAWINGS GOING TO BE SUBMITTED IN THE NEXT CYCLE SIGNS
 AND SEALS HIS DRAWINGS. THE DRAWINGS SUBMITTED IN THIS
 REVIEW WERE NOT SIGNED OR SEALED. FBC FS 107.2.1


Account Summary | Usage Policy | Privacy Policy