| 2020-06-22 11:00:39 | 3RD REVIEW FBC-2017 RES. FUEL GAS |
| | PERMIT #20041097 |
| | 6/22/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P-3G: THE NEW ENGINEERED ISOMETRIC IS |
| | INDICATING A 2PSI SYSTEM CONNECTING TO THE UNDERGROUND |
| | PE AT THE EXTERIOR AND THEN RUNNING CONTINUOUSLY |
| | THROUGH THE HOUSE WITH NO REGULATORS SHOWN AT ANY OF |
| | THE OUTLETS TO THE APPLIANCES- SECTIONS G2421.1 & |
| | G2421.2 FBC RES. |
| | COMPARING THE ORIGINAL ISOMETRIC SUBMITTED BY CATOE & |
| | SONS INC, IT APPEARS A REGULATOR IS MISSING AT THE |
| | RISER LOCATION ON THE EXTERIOR WALL PRIOR TO THE GAS |
| | PIPE PENETRATING INTO THE HOUSE. THE ORIGINAL ISO |
| | INDICATED METALLIC PIPE AT THE RISER AND REGULATOR |
| | LOCATION, HOWEVER THE NEW ENGINEERED DRAWING INDICATES |
| | CSST MAKING THE CONNECTION TO THE UG/PE. PLEASE NOTE |
| | THAT A LISTED TRANSITION FITTING IS REQUIRED TO MAKE |
| | THE CSST/PE CONNECTION ? SECTION G2415.17.2, AND THE |
| | CSST MUST BE INSTALLED AN A PROTECTIVE HOUSING ON THE |
| | EXTERIOR WALL- SECTIONS G2415.2 & G2415.9 FBC RES. |
| | PLEASE REVISE THE ISOMETRIC DRAWING TO SHOW LOCATIONS |
| | OF THE REQUIRED REGULATORS, AND INDICATE THE MAKES AND |
| | MODELS OF THE REGULATORS AND SHOW THE GAS INPUT |
| | PRESSURES AND REQUIRED ORIFICE SIZES AT THE APPLIANCES. |
| | SUBMIT MANUFACTURER?S SPECIFICATIONS AND INSTALLATION |
| | MANUALS FOR THE REGULATORS. |
| | |
| | 2) COMMENTS #3, 4, 5, 6, 8 FROM THE 2ND REVIEW PRINTED |
| | BELOW HAVE NOT BEEN ADRESSED. PLEASE CORRECT THE NEW |
| | ISOMETRIC PER COMMENT #3. CONCERNING COMMENTS 4-8, IF |
| | THE INSTALLATION AND VENTING OF APPLIANCES ARE NOT |
| | INCLUDED, THE NEW ENGINEER SHALL NOTE THAT ON THE |
| | PLANS- SECTION 107.2.1 WPB. |
| | 3) THE SUBMITTED MANUFACTURER'S SPECIFICATIONS FOR THE |
| | WATER HEATER AND THE COOKTOP INDICATE APPLIANCE GAS |
| | LOADS THAT DON'T MATCH THE PLANS: |
| | A) THE SPECS INDICATE SELECTED MODEL RG240T6N AT 40,000 |
| | BTUH; THE ISOMETRIC AND THE COMBUSTION AIR CALCS |
| | INDICATE 80,000 BTUH. |
| | B) THE SPECS INDICATE THE COOKTOP WITH ALL SIX BURNERS |
| | OPERATING AT 99,000 BTUH, THE ISOMETRIC INDICATES |
| | 120,000 BTUH, AND THE CALCS INDICATE 72,000 BTUH. |
| | C) THE SPECS FOR THE BBQ DO NOT INDICATE WHAT THE BTUH |
| | GAS LOAD OF THE APPLIANCE IS- SECTION 107.2.1 WPB. |
| | 4) THE REQUESTED INSTALLATION GUIDELINES FOR THE WATER |
| | HEATER, AND THE SPECS FOR THE CLOTHES DRYER WERE NOT |
| | PROVIDED- SECTION G2408.1 RES. |
| | 5) THE REQUESTED GAS VENTING PLAN AND INSTALLATION |
| | GUIDELINES FOR THE WATER HEATER WERE NOT PROVIDED- |
| | SECTION G2425.1 FBC RES. A) THE COPIED VENTING FIGURES |
| | FROM THE FBC-17 FUEL GAS ARE NOT ACCEPTABLE- SECTION |
| | 107.2.1 WPB. PROVIDE A SITE-SPECIFIC GAS VENTING |
| | DIAGRAM SHOWING THE TYPE AND SIZE OF VENT, VENT RUN |
| | THROUGH AND OUT OF THE BUILDING, TERMINATION LOCATION, |
| | HEIGHTS ABOVE THE ROOF, AND ANCHORING DETAILS. SUBMIT |
| | SPECIFICATIONS FOR ALL THE VENT FLUES, CONNECTORS, AND |
| | TERMINATION CAPS- SECTIONS G2426.1 THROUGH G2426.7 FBC |
| | RES. |
| | 6) THE GAS VENTING DIAGRAM FOR THE BBQ IS INCOMPLETE. |
| | IF THE BBQ IS LOCATED UNDER OVERHEAD CONSTRUCTION THE |
| | SPECS INDICATE A 1200 CFM EXHAUST HOOD IS REQUIRED. A) |
| | PROVIDE MANUFACTURER'S SPECIFICATIONS FOR THE HOOD AND |
| | VENT FLUE- SECTIONS G2426.1- G2426.7 26.7 FBC RES. B) |
| | PROVIDE A GAS VENTING DIAGRAM SHOWING THE TYPE AND SIZE |
| | OF VENT, VENT RUN AND TERMINATION LOCATION. INDICATE |
| | THE TERMINATION HEIGHT ABOVE THE ROOF (IF APPLICABLE) |
| | AND PROVIDE ANCHORING DETAILS. C) SHOW THE REQUIRED |
| | CLEARANCES FOR THE BBQ, THE EXHAUST HOOD AND THE VENT |
| | PER THE SPECS. |
| | 7) COMBUSTION AIR. PLEASE REFER TO SECTION G2407.5.1 |
| | (304.5.1) STANDARD METHOD. IF USING INDOOR AIR, THE |
| | MINIMUM REQUIRED VOLUME SHALL BE 50 CUBIC FEET PER |
| | 1,000 BTU/H OF THE APPLIANCE INPUT RATING. |
| | 8) PLEASE INDICATE HOW MAKEUP AIR IS BEING PROVIDED FOR |
| | THE CLOTHES DRYER AND PROVIDE A CALCULATION- SECTION |
| | G2407.1 FBC RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |