| | 1ST REVIEW FBC-2017 RES. FUEL GAS |
| | PERMIT #20041083 |
| | 5/19/2020 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) GAS RISER: |
| | A) CORRECT THE 329 MBH GAS LOAD FOR THE GENERATOR. THE |
| | SPECS INDICATE 306MBH- SECTION 107.2.1 WPB. |
| | B) CORRECT THE TOTAL LOAD- 413 MBH- SECTION G2413.2 FBC |
| | RES. |
| | C) LIST ALL TABLES USED FOR SIZING THE GAS PIPING- SEE |
| | TABLES G2413.4(1) THROUGH G2413.4(21) FBC RES. |
| | |
| | 2) SURVEY: THE GENERATOR SHALL BE LOCATED A MINIMUM OF |
| | 5' FROM THE ADJACENT EXTERIOR WALL, OR THE WALL SHALL |
| | HAVE A 1-HR. FIRE RESISTANCE RATING- SECTION 4.1.4 (1) |
| | NFPA 37. THE GENERATOR SHALL ALSO HAVE A 10' CLEARANCE |
| | DISTANCE FROM AIR INTAKES AND OPERABLE OPENINGS INTO |
| | THE BUILDING- SECTION R303.5.1 FBC RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |