| 2020-05-19 12:20:12 | |
| | 1ST REVIEW FBC-2017 RES. FUEL GAS |
| | PERMIT #20041074 |
| | 5/19/2020 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE PERMIT APPLICATION, GAS RISER, AND SURVEY |
| | INDICATE A 38 KW GENERATOR TO BE INSTALLED, HOWEVER THE |
| | GENERAC SPECS SUBMITTED ARE FOR A 20/22 KW GENERATOR. |
| | PLEASE SUBMIT THE CORRECT SPECS- SECTION 107.2.1 WPB. |
| | |
| | 2) SUBMIT MANUFACTURER'S SPECIFICATIONS AND |
| | INSTALLATION INSTRUCTIONS FOR THE TANKLESS WATER |
| | HEATER- SECTION G2408.1 FBC RES. |
| | |
| | 3) THE GAS RISER DRAWING IS INCOMPLETE. PLEASE PROVIDE |
| | THE FOLLOWING CORRECTIONS: |
| | A) REMOVE THE REFERENCE TO LP GAS- SECTION 107.2.1 WPB. |
| | B) MODIFY THE DRAWING TO SHOW THE TOTAL GAS PIPING RUN |
| | FROM THE NEW METER TO THE MOST REMOTE OUTLET AND |
| | INDICATE THE TOTAL DEVELOPED LENGTH OF THE SYSTEM. |
| | IDENTIFY THE TYPES AND SIZES OF PIPING TO BE INSTALLED |
| | AND SHOW THE LENGTHS OF EACH CUT SECTION OF PIPE- |
| | SECTIONS G2413.4.1 & G2413.4.2 FBC RES. |
| | C) INDICATE THE GAS DELIVERY PRESSURE AT THE METER, AND |
| | THE STEP-DOWN PRESSURES AT THE GENERATOR AND AT THE |
| | WATER HEATER- SECTION G2413.2 & G2413.4.3 |
| | D)) SHOW THE LOCATIONS OF THE REGULATOR AT THE METER, |
| | AND ALL (MP) STEPDOWN REGULATORS AND REQUIRED SHUT OFF |
| | VALVES. PLEASE NOTE THAT WHERE CONNECTED TO RIGID |
| | PIPING, A UNION SHALL BE INSTALLED WITHIN 1 FT. OF |
| | EITHER SIDE OF THE MP REGULATOR- SECTION G2421.2(7). |
| | E) LIST ALL TABLES USED FOR SIZING THE GAS PIPING- SEE |
| | TABLES G2413.4(1) THROUGH G2413.4(21) FBC RES. |
| | |
| | 3) SURVEY AND/OR PLAN CORRECTIONS: RELOCATE THE |
| | GENERATOR A MINIMUM OF 5' FROM THE ADJACENT EXTERIOR |
| | WALL, OR VERIFY THE WALL HAS A 1-HR. FIRE RESISTANCE |
| | RATING- SECTION 4.1.4 (1) NFPA 54. A) INDICATE A |
| | MINIMUM 10' CLEARANCE FROM THE GENERATOR TO AIR INTAKES |
| | AND OPERABLE OPENINGS INTO THE BUILDING WILL BE |
| | MAINTAINED PER SECTION R303.5.1 FBC RES. |
| | |
| | 4) PROVIDE A DRAWING SHOWING THE LOCATION OF THE |
| | TANKLESS WATER HEATER ON THE EXTERIOR WALL WITH |
| | CLEARANCE DISTANCES SHOWN FROM GRADE, THE EAVES OR |
| | SOFFIT ABOVE, AND TO AIR INTAKES AND OPERABLE OPENINGS |
| | INTO THE BUILDING- SECTION G2408.1 FBC RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |