Plan Review Details - Permit 20041072
Plan Review Stops For Permit 20041072
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-08-27 Cont ID  
Sent By rmcphers Date 2020-08-27 Time 14:41 Rev Time 0.00
Received By rmcphers Date 2020-08-27 Time 14:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-07-20 Cont ID  
Sent By rmcphers Date 2020-07-20 Time 11:00 Rev Time 0.00
Received By rmcphers Date 2020-07-20 Time 10:53 Sent To  
Notes
2020-07-20 11:00:38SFR ADDITION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PRODUCT APPROVALS FOR THE DOORS HAS EXPIRED. PLEASE
 PROVIDE UPDATED COPIES. (REVIEWED AND MARKED APPROVED
 BY THE DESIGNER OF RECORD)
 2) FLAT ROOF PRODUCT APPROVAL = PLEASE CIRCLE THE
 ROOFING SYSTEM TO BE USED IN THE PRODUCT APPROVAL.
 ROOFING SYSTEM TO BE USED ON THE PROVIDED PRODUCT
 APPROVAL MAY REQUIRE ADDITIONAL SIGNED AND SEALED
 ATTACHMENT DETAILS FROM AN ARCHITECT OR ENGINEER FOR
 ROOF WIND ZONES 2 AND 3 WHICH MAY REQUIRE A HIGHER
 PRESSURE THAN THE MAXIMUM SHOWN ON THE PRODUCT
 APPROVAL- SEE GENERAL LIMITATION NUMBER 7 ON THE
 PRODUCT APPROVAL. SIGNED AND SEALED DRAWINGS OR
 DOCUMENTS WILL NEED TO BE DIGITALLY SIGNED AND SEALED
 TO BE USED IN ELECTRONIC PLAN REVIEW.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-05-12 Cont ID  
Sent By rmcphers Date 2020-05-12 Time 11:46 Rev Time 0.00
Received By rmcphers Date 2020-05-12 Time 09:20 Sent To  
Notes
2020-05-12 11:45:26SFR ADDITION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) ALL DRAWINGS NEED TO BE DIGITALLY SIGNED BY THE
 ARCHITECT OR ENGINEER.
 2) PRODUCT APPROVALS FOR THE DOORS AND ROOFING HAVE
 EXPIRED. PLEASE PROVIDE UPDATED COPIES.
 3) FLAT ROOF PRODUCT APPROVAL = PLEASE CIRCLE THE
 ROOFING SYSTEM TO BE USED IN THE PRODUCT APPROVAL.
 ROOFING SYSTEM TO BE USED ON THE PROVIDED PRODUCT
 APPROVAL MAY REQUIRE ADDITIONAL SIGNED AND SEALED
 ATTACHMENT DETAILS FROM AN ARCHITECT OR ENGINEER FOR
 ROOF WIND ZONES 2 AND 3 WHICH MAY REQUIRE A HIGHER
 PRESSURE THAN THE MAXIMUM SHOWN ON THE PRODUCT
 APPROVAL- SEE GENERAL LIMITATION NUMBER 7 ON THE
 PRODUCT APPROVAL. SIGNED AND SEALED DRAWINGS OR
 DOCUMENTS WILL NEED TO BE DIGITALLY SIGNED AND SEALED
 TO BE USED IN ELECTRONIC PLAN REVIEW.
 4) PRODUCT APPROVALS AND TRUSS ENGINEERING SHOULD BE
 REVIEWED AND MARKED APPROVED BY THE BUILDING DESIGNER
 OF RECORD.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-07-18 Cont ID  
Sent By fgiaquin Date 2020-07-18 Time 10:30 Rev Time 0.00
Received By fgiaquin Date 2020-07-18 Time 09:45 Sent To  
Notes
2020-07-18 10:32:14HOLD ON ELECTRICAL SUB, MUST BE CONTRACTOR CANNOT BE
 OWNER BUILDER. OWNER IS HOMESTEADED IN THE COUNTY.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-05-19 Cont ID  
Sent By jleahy Date 2020-05-19 Time 11:27 Rev Time 0.00
Received By jleahy Date 2020-05-19 Time 08:08 Sent To  
Notes
2020-05-19 11:36:10ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) CONTRACTOR NEEDED, OWNER IS HOME STEADED IN THE
 COUNTY.
  
 2) PANEL LOCATION IS IN GARAGE OR LIVING ROOM NEED TO
 KNOW WHICH. IF IN GARAGE THE WORKING CLEARACNES ARE IN
 VIOLATION OF 110.26
  
 3) SMOKE ALARMS ARE REQUIRED IN THE EXISTING PORTION OF
 HOME.
 PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED PER
 CODE. SHOW ON PLAN ALL EXISTING ALARMS. IF NONE ARE
 EXISTING OR NOT TO CODE, SHOW AS NEW INSTALLATIONS. FBC
 R314.3, FBC 107.2.1
  
 4) OUTLET SPACING IS REQUIRED IN NEW AREAS OF ADDITION
 ROOM TO THE RIGHT OF THE KITCHEN IS LACKING OUTLET
 SPACING.
  
 5) ALL KITCHEN COUNTER OUTLETS TO BE GFCI
 PROTECTED.210.8
 E3902.6 KITCHEN RECEPTACLES. 125-VOLT, SINGLE-PHASE,
 15- AND 20-AMPERE RECEPTACLES THAT SERVE COUNTERTOP
 SURFACES SHALL HAVE GROUND-FAULT CIRCUIT-INTERRUPTER
 PROTECTION FOR PERSONNEL. [210.8(A)(6)].

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-08-27 Cont ID  
Sent By rmcphers Date 2020-08-27 Time 14:42 Rev Time 0.00
Received By rmcphers Date 2020-08-18 Time 07:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-07-20 Cont ID  
Sent By rmcphers Date 2020-07-20 Time 11:04 Rev Time 0.00
Received By rmcphers Date 2020-07-02 Time 13:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-05-21 Time   Rev Time 0.00
Received By lmarchan Date 2020-05-01 Time 08:55 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2020-08-29 Cont ID  
Sent By lmarchan Date 2020-08-29 Time 07:11 Rev Time 0.00
Received By lmarchan Date 2020-08-27 Time 15:17 Sent To  
Notes
2020-08-29 06:50:28RECEIPT MU-2020-33372 - $393.79 - PAID
2020-08-27 15:17:578/27/20 EMAILED IMPACT FEE OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-05-12 Cont ID  
Sent By rmcphers Date 2020-05-12 Time 11:48 Rev Time 0.00
Received By rmcphers Date 2020-05-12 Time 11:46 Sent To  
Notes
2020-05-12 11:47:32PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2020-05-05 Cont ID  
Sent By hmoser Date 2020-05-05 Time 13:39 Rev Time 0.00
Received By hmoser Date 2020-05-05 Time 10:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2020-08-19 Cont ID  
Sent By ccole Date 2020-08-19 Time 13:04 Rev Time 0.00
Received By ccole Date 2020-08-19 Time 12:38 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-07-09 Cont ID  
Sent By ccole Date 2020-07-09 Time 13:25 Rev Time 0.00
Received By ccole Date 2020-07-09 Time 11:48 Sent To  
Notes
2020-07-09 13:28:112ND REVIEW FBC-2017 RES. PLUMBING
 PERMIT- 20041072
 7/9/2020
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 10A: THE FLAT LINE DRAIN DRAWING FOR THE
 MASTER BATHROOM AND THE SANITARY ISOMETRIC DO NOT
 MATCH. THE RISER APPEARS TO SHOW THE VENT STACK AT THE
 LAVATORIES CONNECTING DOWN STREAM OF THE OTHER BATH
 FIXTURES WHICH PER THE FLOOR PLAN LAYOUT WOULD NOT BE
 POSSIBLE. PLEASE REFER TO SECTIONS P3108.1 & P3108.1.2
 FBC P FOR PROPER WET VENTING OF THE SYSTEM AND CORRECT
 THE ISOMETRIC DRAWING.
  
 2) 10A, KITCHEN RISER: SHOW THE WATER SUPPLY AND DRAIN
 CONNECTIONS TO THE DISHWASHER, AND THE SUPPLY LINE TO
 THE REFRIGERATOR ICE MAKER. INDICATE HOW THE DISHWASHER
 SUPPLY LINE WILL BE PROTECTED FROM BACKFLOW PER
 SECTIONS P 2717.1 AND P2902.1 FBC RES., AND PROVIDE A
 WATER HAMMER ARRESTOR AND BACKFLOW PREVENTER FOR THE
 SUPPLY LINE TO THE ICE MAKER- SEE SECTIONS 2902.1 AND
 P2903.5.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-05-21 Cont ID  
Sent By ccole Date 2020-05-21 Time 11:28 Rev Time 0.00
Received By ccole Date 2020-05-21 Time 11:12 Sent To  
Notes
2020-05-21 11:35:431ST REVIEW FBC-2017 PLUMBING
 PERMIT 20041072
 5/21/2020
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) NO PLUMBING SCOPE OF WORK OR PLUMBING PLANS
 SUBMITTED. PROVIDE A SANITARY ISOMETRIC DRAWING, AND
 NOTES AND DETAILS TO CLARIFY THE SCOPE OF THE PLUMBING
 WORK- SECTIONS 107.2.1 & 107.3.5.3 WPB.
  
 2) SHEET 10: PLEASE CLARIFY THE NOTE IN THE EXIST
 BATHROOM TUB, IS THE BATHTUB BEING CONVERTED TO A
 SHOWER? - SECTION 107.2.1 WPB.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2020-08-27 Cont ID  
Sent By rmcphers Date 2020-08-27 Time 14:41 Rev Time 0.00
Received By rmcphers Date 2020-08-27 Time 14:41 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2020-07-20 Cont ID  
Sent By rmcphers Date 2020-07-20 Time 11:01 Rev Time 0.00
Received By rmcphers Date 2020-07-20 Time 11:01 Sent To  
Notes
2020-07-20 11:01:42SEE BUILDING PLAN REVIEW

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2020-05-12 Cont ID  
Sent By rmcphers Date 2020-05-12 Time 11:48 Rev Time 0.00
Received By rmcphers Date 2020-05-12 Time 11:48 Sent To  
Notes
2020-05-12 11:48:41SEE BUILDING PLAN REVIEW

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-08-27 Cont ID  
Sent By rmcphers Date 2020-08-27 Time 14:42 Rev Time 0.00
Received By rmcphers Date 2020-08-27 Time 14:42 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-07-20 Cont ID  
Sent By rmcphers Date 2020-07-20 Time 11:03 Rev Time 0.00
Received By rmcphers Date 2020-07-20 Time 11:03 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-05-12 Cont ID  
Sent By rmcphers Date 2020-05-12 Time 11:48 Rev Time 0.00
Received By rmcphers Date 2020-05-12 Time 11:48 Sent To  
Notes
2020-05-12 11:49:14SEE BUILDING PLAN REVIEW

Review Stop Z ZONING
Rev No 4 Status P Date 2020-08-28 Cont ID  
Sent By llouie Date 2020-08-28 Time   Rev Time 0.00
Received By llouie Date 2020-08-28 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2020-08-21 Cont ID  
Sent By llouie Date 2020-08-21 Time   Rev Time 0.00
Received By llouie Date 2020-08-21 Time   Sent To  
Notes
2020-08-21 10:59:36** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) THE SITE PLAN SHOWING SETBACK DIMENSIONS OF THE
 PROPOSED EXPANSION TO THE PROPERTY LINES AND LOCATION
 OF THE A/C UNIT CONCRETE PAD SEEMS TO HAVE DISAPPEARED
 FROM THE PERMIT SUBMITTAL. THIS IS A CRITICAL DOCUMENT
 ZONING MUST APPROVE.
  
  
 NOTES:
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE ANY
 QUESTIONS.
  
 * Z = SF7
  

Review Stop Z ZONING
Rev No 2 Status F Date 2020-07-13 Cont ID  
Sent By llouie Date 2020-07-13 Time   Rev Time 0.00
Received By llouie Date 2020-07-13 Time   Sent To  
Notes
2020-07-13 12:43:56** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) SURVEY SHALL BE SIGNED AND SEALED BY A FLORIDA
 REGISTERED LAND SURVEYOR.
  
 2.) PER PROPERTY OWNER, EXISTING SITE ELEMENTS MISSING
 ON THE SURVEY.
  
  
 NOTES:
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE ANY
 QUESTIONS.
  
 * Z = SF7
  

Review Stop Z ZONING
Rev No 1 Status F Date 2020-05-05 Cont ID  
Sent By llouie Date 2020-05-05 Time   Rev Time  
Received By llouie Date 2020-05-05 Time   Sent To  
Notes
2020-05-05 14:53:43** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) SITE PLAN SHOWING SETBACK DISTANCES TO THE PROPERTY
 LINE AND LOCATION OF THE A/C UNIT CONCRETE PAD
 (INCLUDING SETBACKS) ARE MISSING. PLEASE PROVIDE.
  
 2.) THE VALUE OF THE CONSTRUCTION ($65,000) EXCEEDS 50%
 OF THE STRUCTURE'S VALUE ($108,798) ACCORDING TO THE
 P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT
 TO SECTION 94-441(C)(2) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPE ON THE
 SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. IF THE
 SITE CONFORMS TO ARTICLE XIV, THEN TWO (2) COPIES OF A
 LANDSCAPE PLAN DEMONSTRATING COMPLIANCE SHALL BE
 INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE SITE DOES
 NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE ZONING
 APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE PERMIT AND
 IRRIGATION PERMIT SHALL BE SUBMITTED SHOWING MATERIAL
 TO BRING THE SITE INTO CONFORMITY.
  
  
 NOTES:
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE ANY
 QUESTIONS.
  
 * Z = SF7
  