| Plan Review Stops For Permit 20041072 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2020-08-27 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-08-27 |
Time |
14:41 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-08-27 |
Time |
14:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2020-07-20 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-07-20 |
Time |
11:00 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-07-20 |
Time |
10:53 |
Sent To |
|
|
| Notes |
| 2020-07-20 11:00:38 | SFR ADDITION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PRODUCT APPROVALS FOR THE DOORS HAS EXPIRED. PLEASE | | | PROVIDE UPDATED COPIES. (REVIEWED AND MARKED APPROVED | | | BY THE DESIGNER OF RECORD) | | | 2) FLAT ROOF PRODUCT APPROVAL = PLEASE CIRCLE THE | | | ROOFING SYSTEM TO BE USED IN THE PRODUCT APPROVAL. | | | ROOFING SYSTEM TO BE USED ON THE PROVIDED PRODUCT | | | APPROVAL MAY REQUIRE ADDITIONAL SIGNED AND SEALED | | | ATTACHMENT DETAILS FROM AN ARCHITECT OR ENGINEER FOR | | | ROOF WIND ZONES 2 AND 3 WHICH MAY REQUIRE A HIGHER | | | PRESSURE THAN THE MAXIMUM SHOWN ON THE PRODUCT | | | APPROVAL- SEE GENERAL LIMITATION NUMBER 7 ON THE | | | PRODUCT APPROVAL. SIGNED AND SEALED DRAWINGS OR | | | DOCUMENTS WILL NEED TO BE DIGITALLY SIGNED AND SEALED | | | TO BE USED IN ELECTRONIC PLAN REVIEW. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2020-05-12 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-05-12 |
Time |
11:46 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-05-12 |
Time |
09:20 |
Sent To |
|
|
| Notes |
| 2020-05-12 11:45:26 | SFR ADDITION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) ALL DRAWINGS NEED TO BE DIGITALLY SIGNED BY THE | | | ARCHITECT OR ENGINEER. | | | 2) PRODUCT APPROVALS FOR THE DOORS AND ROOFING HAVE | | | EXPIRED. PLEASE PROVIDE UPDATED COPIES. | | | 3) FLAT ROOF PRODUCT APPROVAL = PLEASE CIRCLE THE | | | ROOFING SYSTEM TO BE USED IN THE PRODUCT APPROVAL. | | | ROOFING SYSTEM TO BE USED ON THE PROVIDED PRODUCT | | | APPROVAL MAY REQUIRE ADDITIONAL SIGNED AND SEALED | | | ATTACHMENT DETAILS FROM AN ARCHITECT OR ENGINEER FOR | | | ROOF WIND ZONES 2 AND 3 WHICH MAY REQUIRE A HIGHER | | | PRESSURE THAN THE MAXIMUM SHOWN ON THE PRODUCT | | | APPROVAL- SEE GENERAL LIMITATION NUMBER 7 ON THE | | | PRODUCT APPROVAL. SIGNED AND SEALED DRAWINGS OR | | | DOCUMENTS WILL NEED TO BE DIGITALLY SIGNED AND SEALED | | | TO BE USED IN ELECTRONIC PLAN REVIEW. | | | 4) PRODUCT APPROVALS AND TRUSS ENGINEERING SHOULD BE | | | REVIEWED AND MARKED APPROVED BY THE BUILDING DESIGNER | | | OF RECORD. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2020-07-18 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2020-07-18 |
Time |
10:30 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2020-07-18 |
Time |
09:45 |
Sent To |
|
|
| Notes |
| 2020-07-18 10:32:14 | HOLD ON ELECTRICAL SUB, MUST BE CONTRACTOR CANNOT BE | | | OWNER BUILDER. OWNER IS HOMESTEADED IN THE COUNTY. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2020-05-19 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-05-19 |
Time |
11:27 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-05-19 |
Time |
08:08 |
Sent To |
|
|
| Notes |
| 2020-05-19 11:36:10 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) CONTRACTOR NEEDED, OWNER IS HOME STEADED IN THE | | | COUNTY. | | | | | | 2) PANEL LOCATION IS IN GARAGE OR LIVING ROOM NEED TO | | | KNOW WHICH. IF IN GARAGE THE WORKING CLEARACNES ARE IN | | | VIOLATION OF 110.26 | | | | | | 3) SMOKE ALARMS ARE REQUIRED IN THE EXISTING PORTION OF | | | HOME. | | | PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED PER | | | CODE. SHOW ON PLAN ALL EXISTING ALARMS. IF NONE ARE | | | EXISTING OR NOT TO CODE, SHOW AS NEW INSTALLATIONS. FBC | | | R314.3, FBC 107.2.1 | | | | | | 4) OUTLET SPACING IS REQUIRED IN NEW AREAS OF ADDITION | | | ROOM TO THE RIGHT OF THE KITCHEN IS LACKING OUTLET | | | SPACING. | | | | | | 5) ALL KITCHEN COUNTER OUTLETS TO BE GFCI | | | PROTECTED.210.8 | | | E3902.6 KITCHEN RECEPTACLES. 125-VOLT, SINGLE-PHASE, | | | 15- AND 20-AMPERE RECEPTACLES THAT SERVE COUNTERTOP | | | SURFACES SHALL HAVE GROUND-FAULT CIRCUIT-INTERRUPTER | | | PROTECTION FOR PERSONNEL. [210.8(A)(6)]. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2020-08-27 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-08-27 |
Time |
14:42 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-08-18 |
Time |
07:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2020-07-20 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-07-20 |
Time |
11:04 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-07-02 |
Time |
13:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2020-05-21 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2020-05-01 |
Time |
08:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2020-08-29 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2020-08-29 |
Time |
07:11 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2020-08-27 |
Time |
15:17 |
Sent To |
|
|
| Notes |
| 2020-08-29 06:50:28 | RECEIPT MU-2020-33372 - $393.79 - PAID | | 2020-08-27 15:17:57 | 8/27/20 EMAILED IMPACT FEE OFFICE FOR REVIEW. LEM |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2020-05-12 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-05-12 |
Time |
11:48 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-05-12 |
Time |
11:46 |
Sent To |
|
|
| Notes |
| 2020-05-12 11:47:32 | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | | | | UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE | | | RECEIPT TO YOUR PROJECT OR EMAIL IT TO | | | [email protected] . | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2020-05-05 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2020-05-05 |
Time |
13:39 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2020-05-05 |
Time |
10:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2020-08-19 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2020-08-19 |
Time |
13:04 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2020-08-19 |
Time |
12:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2020-07-09 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2020-07-09 |
Time |
13:25 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2020-07-09 |
Time |
11:48 |
Sent To |
|
|
| Notes |
| 2020-07-09 13:28:11 | 2ND REVIEW FBC-2017 RES. PLUMBING | | | PERMIT- 20041072 | | | 7/9/2020 | | | | | | CODES IN EFFECT: | | | | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | | EDITION 2017 | | | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET 10A: THE FLAT LINE DRAIN DRAWING FOR THE | | | MASTER BATHROOM AND THE SANITARY ISOMETRIC DO NOT | | | MATCH. THE RISER APPEARS TO SHOW THE VENT STACK AT THE | | | LAVATORIES CONNECTING DOWN STREAM OF THE OTHER BATH | | | FIXTURES WHICH PER THE FLOOR PLAN LAYOUT WOULD NOT BE | | | POSSIBLE. PLEASE REFER TO SECTIONS P3108.1 & P3108.1.2 | | | FBC P FOR PROPER WET VENTING OF THE SYSTEM AND CORRECT | | | THE ISOMETRIC DRAWING. | | | | | | 2) 10A, KITCHEN RISER: SHOW THE WATER SUPPLY AND DRAIN | | | CONNECTIONS TO THE DISHWASHER, AND THE SUPPLY LINE TO | | | THE REFRIGERATOR ICE MAKER. INDICATE HOW THE DISHWASHER | | | SUPPLY LINE WILL BE PROTECTED FROM BACKFLOW PER | | | SECTIONS P 2717.1 AND P2902.1 FBC RES., AND PROVIDE A | | | WATER HAMMER ARRESTOR AND BACKFLOW PREVENTER FOR THE | | | SUPPLY LINE TO THE ICE MAKER- SEE SECTIONS 2902.1 AND | | | P2903.5. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2020-05-21 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2020-05-21 |
Time |
11:28 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2020-05-21 |
Time |
11:12 |
Sent To |
|
|
| Notes |
| 2020-05-21 11:35:43 | 1ST REVIEW FBC-2017 PLUMBING | | | PERMIT 20041072 | | | 5/21/2020 | | | | | | CODES IN EFFECT: | | | | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | | EDITION 2017 | | | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) NO PLUMBING SCOPE OF WORK OR PLUMBING PLANS | | | SUBMITTED. PROVIDE A SANITARY ISOMETRIC DRAWING, AND | | | NOTES AND DETAILS TO CLARIFY THE SCOPE OF THE PLUMBING | | | WORK- SECTIONS 107.2.1 & 107.3.5.3 WPB. | | | | | | 2) SHEET 10: PLEASE CLARIFY THE NOTE IN THE EXIST | | | BATHROOM TUB, IS THE BATHTUB BEING CONVERTED TO A | | | SHOWER? - SECTION 107.2.1 WPB. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2020-08-27 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-08-27 |
Time |
14:41 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-08-27 |
Time |
14:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2020-07-20 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-07-20 |
Time |
11:01 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-07-20 |
Time |
11:01 |
Sent To |
|
|
| Notes |
| 2020-07-20 11:01:42 | SEE BUILDING PLAN REVIEW |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2020-05-12 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-05-12 |
Time |
11:48 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-05-12 |
Time |
11:48 |
Sent To |
|
|
| Notes |
| 2020-05-12 11:48:41 | SEE BUILDING PLAN REVIEW |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2020-08-27 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-08-27 |
Time |
14:42 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-08-27 |
Time |
14:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2020-07-20 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-07-20 |
Time |
11:03 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-07-20 |
Time |
11:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2020-05-12 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-05-12 |
Time |
11:48 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-05-12 |
Time |
11:48 |
Sent To |
|
|
| Notes |
| 2020-05-12 11:49:14 | SEE BUILDING PLAN REVIEW |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2020-08-28 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2020-08-28 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2020-08-28 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2020-08-21 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2020-08-21 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2020-08-21 |
Time |
|
Sent To |
|
|
| Notes |
| 2020-08-21 10:59:36 | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | | APPLICABLE: | | | | | | 1.) THE SITE PLAN SHOWING SETBACK DIMENSIONS OF THE | | | PROPOSED EXPANSION TO THE PROPERTY LINES AND LOCATION | | | OF THE A/C UNIT CONCRETE PAD SEEMS TO HAVE DISAPPEARED | | | FROM THE PERMIT SUBMITTAL. THIS IS A CRITICAL DOCUMENT | | | ZONING MUST APPROVE. | | | | | | | | | NOTES: | | | | | | * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS. | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE ANY | | | QUESTIONS. | | | | | | * Z = SF7 | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2020-07-13 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2020-07-13 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2020-07-13 |
Time |
|
Sent To |
|
|
| Notes |
| 2020-07-13 12:43:56 | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | | APPLICABLE: | | | | | | 1.) SURVEY SHALL BE SIGNED AND SEALED BY A FLORIDA | | | REGISTERED LAND SURVEYOR. | | | | | | 2.) PER PROPERTY OWNER, EXISTING SITE ELEMENTS MISSING | | | ON THE SURVEY. | | | | | | | | | NOTES: | | | | | | * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS. | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE ANY | | | QUESTIONS. | | | | | | * Z = SF7 | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2020-05-05 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2020-05-05 |
Time |
|
Rev Time |
|
| Received By |
llouie |
Date |
2020-05-05 |
Time |
|
Sent To |
|
|
| Notes |
| 2020-05-05 14:53:43 | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | | APPLICABLE: | | | | | | 1.) SITE PLAN SHOWING SETBACK DISTANCES TO THE PROPERTY | | | LINE AND LOCATION OF THE A/C UNIT CONCRETE PAD | | | (INCLUDING SETBACKS) ARE MISSING. PLEASE PROVIDE. | | | | | | 2.) THE VALUE OF THE CONSTRUCTION ($65,000) EXCEEDS 50% | | | OF THE STRUCTURE'S VALUE ($108,798) ACCORDING TO THE | | | P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT | | | TO SECTION 94-441(C)(2) OF THE ZONING AND LAND | | | DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPE ON THE | | | SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE | | | REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. IF THE | | | SITE CONFORMS TO ARTICLE XIV, THEN TWO (2) COPIES OF A | | | LANDSCAPE PLAN DEMONSTRATING COMPLIANCE SHALL BE | | | INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE SITE DOES | | | NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE ZONING | | | APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE PERMIT AND | | | IRRIGATION PERMIT SHALL BE SUBMITTED SHOWING MATERIAL | | | TO BRING THE SITE INTO CONFORMITY. | | | | | | | | | NOTES: | | | | | | * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS. | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE ANY | | | QUESTIONS. | | | | | | * Z = SF7 | | | |
|
|