Plan Review Details - Permit 20041058
| Plan Review Stops For Permit 20041058 |
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
2 |
Status |
P |
Date |
2020-09-08 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2020-09-08 |
Time |
14:29 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2020-09-08 |
Time |
14:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
1 |
Status |
F |
Date |
2020-06-16 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2020-06-16 |
Time |
16:16 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2020-06-16 |
Time |
13:02 |
Sent To |
|
|
| Notes |
| 2020-06-16 16:14:19 | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS | | | REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: | | | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | | RENOVATION.HTML | | | 19120504 | | | THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO | | | [email protected]. THE INFORMATION SHOULD BE IN PDF | | | FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE | | | THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2021-03-03 |
Time |
13:14 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2021-03-02 |
Time |
08:32 |
Sent To |
|
|
| Notes |
| 2021-03-03 13:16:11 | 2017 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 20041058 | | | ADD: 650 BELVEDERE RD. | | | CONT: NUNNO BUILDERS | | | TEL: 954-961-0777 | | | E-MAIL: [email protected] | | | | | | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 3RD REVIEW | | | DATE: WED. MARCH 03RD /2021 | | | ACTION: BUILDING PROVISO | | | | | | 1) BUILDING PROVISO: THE NEW ENCLOSED COOLER/ FREEZER | | | (399 SQ. FT.) TO BE UNDER A SEPARATE PERMIT, REVIEW AND | | | ASSOCIATED FEES. | | | | | | 2A) THE DESIGNER OF RECORD HAS REQUESTED THAT ALL | | | COMPONENTS & CLADDING PRODUCT APPROVALS BE DEFERRED | | | SUBMITTALS, AFTER PERMIT ISSUANCE. | | | 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS | | | SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE | | | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE | | | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO | | | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. | | | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR | | | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED | | | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST | | | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS | | | FOR REVIEW BY THE BUILDING OFFICIAL. | | | | | | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE | | | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN | | | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD | | | THEM TO THE BUILDING OFFICIAL WITH A NOTATION | | | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE | | | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO | | | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL | | | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED | | | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING | | | OFFICIAL. | | | | | | 2B) DEFERRED SUBMITTAL/ PROVISO. IDENTIFY GLAZING/ | | | MULLIONS. PLEASE IDENTIFY ON THE PRODUCT APPROVAL | | | BEFORE SUBMITTING TO DESIGNER OF RECORD AND BEFORE | | | SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS | | | WITH GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & | | | HEIGHT, TYPE OF GLAZING, MULLION SIZE, LENGTH IF | | | UNREINFORCED OR REINFORCED INFORMATION IF REQUIRED, | | | ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING | | | SIZE. 2017 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND | | | DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED | | | MANUFACTURERS INSTRUCTIONS. FASTENER SIZE AND SPACING | | | SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE | | | CALCULATED BASED ON MAXIMUM LOADS AND SPACING USED IN | | | THE TESTS. | | | | | | 3) BUILDING PROVISO: WELDED OR BOLTED CONNECTIONS. THE | | | CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE | | | SPECIFICATIONS & WELDER OPERATOR PERFORMANCE | | | QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED | | | STANDARDS AT TIME OF INSPECTION. THIRD PARTY | | | CERTIFICATION WILL BE REQUIRED. | | | 2017 FBC-B 2204.1 WELDING | | | 1. WELD PROCEDURES SPECIFICATIONS | | | 2. QUALIFICATIONS OF WELDING PERSONAL | | | 2017 FBC-B 2204.2 BOLTING. | | | IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED, | | | PLEASE CONTACT THE | | | CHIEF BUILDING INSPECTOR KEN CONRAD AT 561-805-6666. | | | | | | JAMES A. WITMER BN, PX, SFP, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6717 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2020-09-15 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2020-09-15 |
Time |
12:10 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2020-09-15 |
Time |
10:16 |
Sent To |
|
|
| Notes |
| 2020-09-15 12:09:58 | 2017 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 20041058 | | | ADD: 650 BELVEDERE RD. | | | CONT: NUNNO BUILDERS | | | TEL: 954-961-0777 | | | E-MAIL: [email protected] | | | | | | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 2ND REVIEW | | | DATE: TUES. SEPT. 15TH /2020 | | | ACTION: DENIED | | | | | | 1) SHEET C-102 SEMI-COMPLIED. IN THE UPPER RIGHT-HAND | | | CORNER OF THE PLAN THE W. P. B. CITY STANDARD IS SOWN | | | WITH 4-INCH-WIDE STRIPES. FURTHER DOWN THE SAME PAGE | | | THERE IS ANOTHER ACCESSIBLE STRIPING REVISION DETAIL | | | WITH THE LINE TYPE A & B BOTH 6-INCH STIPES PLEASE | | | CORRECT OR XXX THROUGH THIS REVISION. | | | | | | 1ST ROUND OF COMMENTS. 2017 ACCESSIBILITY CODE SECTION | | | 502.2 VEHICLE SPACES. EACH PARKING SPACE MUST BE AT | | | LEAST 12 FEET WIDE, SHALL BE MARKED TO DEFINE THE | | | WIDTH, AND SHALL HAVE AN ADJACENT ACCESS AISLE | | | COMPLYING WITH 502.3. | | | ADVISORY 502.3.3MARKING THE METHOD AND MARKING OF COLOR | | | OF MARKING ARE NOT SPECIFIED BY THESE REQUIREMENTS BUT | | | MAY BE ADDRESSED BY STATE OR LOCAL LAWS OR REGULATIONS. | | | WEST PALM MUNI-CODE ARTICLE XV PARKING DETAIL, 94-485 | | | ILLUSTRATES WITH MEASUREMENTS FOR DOUBLE STRIPE STALL | | | PAINTING. | | | | | | 2) 2ND REQUEST. BOTH SHEETS C-100 & SHEET AR1 LIST THE | | | ADDITION OF THE FREEZERS AS 458 SQ. FT. = 400SQ.FT= 858 | | | SQ. FT. IN THE 2017 FBC-B SECTION 2603.4.1.3 IN NON- | | | SPRINKLERED BUILDINGS LIMITS THE AGGREGATE FLOOR AREA | | | (TOTAL FLOOR AREA) TO 400 SQ. FT. | | | | | | 3-4) COMPLIED. | | | | | | 5) COMPLIED, MISSING PRODUCT APPROVALS ADDED TO LIST. | | | SHEET A2.0. | | | | | | 6A) 2ND REQUEST. RESPONSE STATES PLEASE SEE REVIEWED & | | | STAMPED PRODUCT APPROVALS. NONE WERE SUBMITTED. ARE ALL | | | OF THE COMPONENT & CLADDING GOING TO BE DEFERRED | | | SUBMITTALS? | | | 1ST ROUND COMMENTS. W. P. B. 107.3.4. PRODUCT | | | APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY | | | FLORIDA ADMINISTRATIVE CODE RULE 61G20 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR | | | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, | | | SHOP DRAWINGS ETC.. | | | | | | 6B) COMPLIED/ ACKNOWLEDGED. DELEGATED ENGINEERING. | | | 61G15-30.003 ENGINEERING DOCUMENT CLASSIFICATION. FL | | | 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL FORWARD | | | THE DELEGATED ENGINEERING DOCUMENTS TO THE ENGINEER OF | | | RECORD FOR REVIEW. | | | | | | 6C) SEMI-COMPLIED. RESPONSE LIST OF DEFERRED SUBMITTALS | | | DOES NOT INCLUDE THE SINGLE PLY ROOF SYSTEM. | | | 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS | | | SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE | | | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE | | | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO | | | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. | | | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR | | | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED | | | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST | | | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS | | | FOR REVIEW BY THE BUILDING OFFICIAL. | | | | | | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE | | | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN | | | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD | | | THEM TO THE BUILDING OFFICIAL WITH A NOTATION | | | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE | | | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO | | | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL | | | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED | | | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING | | | OFFICIAL. | | | | | | 7)DEFERRED SUBMITTAL/ PROVISO. IDENTIFY GLAZING/ | | | MULLIONS. PLEASE IDENTIFY ON THE PRODUCT APPROVAL | | | BEFORE SUBMITTING TO DESIGNER OF RECORD AND BEFORE | | | SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS | | | WITH GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & | | | HEIGHT, TYPE OF GLAZING, MULLION SIZE, LENGTH IF | | | UNREINFORCED OR REINFORCED INFORMATION IF REQUIRED, | | | ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING | | | SIZE. 2017 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND | | | DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED | | | MANUFACTURERS INSTRUCTIONS. FASTENER SIZE AND SPACING | | | SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE | | | CALCULATED BASED ON MAXIMUM LOADS AND SPACING USED IN | | | THE TESTS. | | | | | | 8)) COMPLIED | | | | | | 9) BUILDING PROVISO: WELDED OR BOLTED CONNECTIONS. THE | | | CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE | | | SPECIFICATIONS & WELDER OPERATOR PERFORMANCE | | | QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED | | | STANDARDS AT TIME OF INSPECTION. THIRD PARTY | | | CERTIFICATION WILL BE REQUIRED. | | | 2017 FBC-B 2204.1 WELDING | | | 1. WELD PROCEDURES SPECIFICATIONS | | | 2. QUALIFICATIONS OF WELDING PERSONAL | | | 2017 FBC-B 2204.2 BOLTING. | | | IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED, | | | PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD | | | AT 561-805-6666. | | | | | | 10) 109.3* BUILDING PERMIT VALUATION.ACKNOWLEGED. FOR | | | PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS | | | SHALL BE TOTAL REPLACEMENT PURPOSES, VALUATION OF | | | BUILDINGS AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT | | | VALUE TO INCLUDE STRUCTURAL, ELECTRICAL, PLUMBING, | | | MECHANICAL, INTERIOR FINISHES, NORMAL SITE WORK | | | (EXCAVATION AND BACKFILL FOR BUILDINGS), ARCHITECTURAL | | | AND DESIGN FEES, MARKETING COST, OVERHEAD AND PROFIT; | | | EXCLUDING ONLY LAND VALUE. VALUATION REFERENCES MAY | | | INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL | | | CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT, | | | MEANS, ETC.) WITH REGIONAL ADJUSTMENTS FOR LOCATION AS | | | PUBLISHED BY THE INTERNATIONAL CODE CONGRESS. | | | | | | THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE | | | MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS. | | | WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING | | | PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE | | | QUALIFIER AND OWNER AND BRINGS IN THE LISTED | | | SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE | | | QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND | | | LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE | | | FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN | | | LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR | | | EACH PERMIT. | | | | | | ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK | | | STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE | | | AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS & | | | FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL | | | TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED | | | SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE, | | | LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR | | | FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE | | | REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT. | | | PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE | | | ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE | | | STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE | | | REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE | | | BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE | | | BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR | | | THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE | | | PRIME OR MASTER PERMIT. | | | | | | 11) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID | | | 19 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS | | | 561-718-9724. | | | | | | JAMES A. WITMER BN, PX, SFP, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6717 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2020-06-16 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2020-06-16 |
Time |
16:16 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2020-06-16 |
Time |
13:02 |
Sent To |
|
|
| Notes |
| 2020-06-16 16:13:14 | 2017 FBC- BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 20041058 | | | ADD: 650 BELVEDERE RD. | | | CONT: NUNNO BUILDERS | | | TEL: 954-961-0777 | | | E-MAIL: [email protected] | | | | | | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: TUES. JUNE 15TH /2020 | | | ACTION: DENIED | | | | | | 1) SHEET C-100 SHOWS THE PARKING LOT WITH SINGLE LINE | | | STRIPING. | | | 2017 ACCESSIBILITY CODE SECTION 502.2 VEHICLE SPACES. | | | EACH PARKING SPACE MUST BE AT LEAST 12 FEET WIDE, SHALL | | | BE MARKED TO DEFINE THE WIDTH, AND SHALL HAVE AN | | | ADJACENT ACCESS AISLE COMPLYING WITH 502.3. | | | ADVISORY 502.3.3MARKING THE METHOD AND MARKING OF COLOR | | | OF MARKING ARE NOT SPECIFIED BY THESE REQUIREMENTS BUT | | | MAY BE ADDRESSED BY STATE OR LOCAL LAWS OR REGULATIONS. | | | WEST PALM MUNI-CODE ARTICLE XV PARKING DETAIL, 94-485 | | | ILLUSTRATES WITH MEASUREMENTS FOR DOUBLE STRIPE STALL | | | PAINTING. | | | | | | 2) BOTH SHEETS C-100 & SHEET AR1 LIST THE ADDITION OF | | | THE FREEZERS AS 458 SQ. FT. IN THE 2017 FBC-B SECTION | | | 2603.4.1.3 IN NONSPRINKLERED BUILDINGS LIMITS THE | | | AGGREGATE FLOOR AREA TO 400 SQ. FT. | | | 3) SHEET A1.0 IN THE UPPER RIGHT CORNER OF THE SHEET, | | | NOTE 11 STATES THERE IS AN OPTION FOR EXTERIOR DOOR | | | REPLACEMENT. 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION | | | 107.2.1. | | | W.P.B. ADMINISTRATIVE CODE/2017 DRAWINGS & | | | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM | | | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, | | | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE | | | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO | | | THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR | | | IN PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED | | | AS A SUBSTITUTE FOR SPECIFIC INFORMATION AND OPTIONS.". | | | CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT CLARITY TO | | | INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK | | | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE | | | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, | | | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING | | | OFFICIAL. | | | | | | 4) SHEET A1.2 SHOWS 60 SEATS BUT THE PLAN DOES NOT SHOW | | | ANY ACCESSIBLE SEATS. PLEASE SHOW COMPLIANCE WITH: | | | | | | 4A) 226.1 WHERE DINING SURFACES ARE PROVIDED FOR THE | | | CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE | | | SEATING SPACES AND STANDING SPACES AT THE DINING | | | SURFACES SHALL COMPLY WITH 902. | | | | | | 4B) 226.2 DISPERSION. DINING SURFACES AND WORK SURFACES | | | REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED | | | THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING | | | SURFACES AND WORK SURFACES. | | | | | | 4C) 206.2.5 206.2.5 RESTAURANTS AND CAFETERIAS. IN | | | RESTAURANTS AND CAFETERIAS, AN ACCESSIBLE ROUTE SHALL | | | BE PROVIDED TO ALL DINING AREAS, INCLUDING RAISED OR | | | SUNKEN DINING AREAS, AND OUTDOOR DINING AREAS. | | | | | | 4D) 902.1 .DINING SURFACES AND WORK SURFACES SHALL | | | COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL. | | | DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS, | | | TABLES, LUNCH COUNTERS, AND BOOTHS. EXAMPLES OF WORK | | | SURFACES INCLUDE WRITING SURFACES, STUDY CARRELS, | | | STUDENT LABORATORY STATIONS, BABY CHANGING AND OTHER | | | TABLES OR FIXTURES FOR PERSONAL GROOMING, COUPON | | | COUNTERS, AND WHERE COVERED BY THE ADA SCOPING | | | PROVISIONS, EMPLOYEE WORK STATIONS. | | | | | | 4E)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR | | | SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD | | | APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE | | | COMPLYING WITH 306 SHALL BE PROVIDED. | | | | | | 4E)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND | | | WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES | | | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. | | | | | | 5) SHEET A2.0 LIST SOME OF THE PRODUCT APPROVALS FOR | | | WINDOWS AND DOORS BUT IS SILENT TO THE FOLLOWING: | | | 5A) METAL WALL PANEL SYSTEM (CM) | | | 5B) ALUMINUM BATTEN SYSTEM (AL) | | | 5C) APOLIC METAL PANEL (AP) | | | | | | 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS, | | | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT | | | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, | | | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS | | | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT | | | APPROVALS: | | | (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES. | | | (B) WINDOWS & MULLIONS | | | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL | | | LOUVERS, EFIS SYSTEMS, | | | (D) ROOFING PRODUCTS AND ASSEMBLIES, CURBS, ROOF TOP | | | INSULATION, LIGHTWEIGHT CONCRETE INSULATION, ROOF TOP | | | VENTILATORS | | | (G) PRE-ENGINEERED A/C STANDS | | | | | | 6A) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS | | | WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE | | | 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR | | | JURISDICTIONAL APPROVAL. | | | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR | | | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, | | | SHOP DRAWINGS ETC.. | | | | | | 6B) DELEGATED ENGINEERING. 61G15-30.003 ENGINEERING | | | DOCUMENT CLASSIFICATION. FL 61G-15-30.006 (3) THE | | | DELEGATED ENGINEER SHALL FORWARD THE DELEGATED | | | ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR | | | REVIEW. | | | | | | 6C) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF | | | THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE | | | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE | | | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO | | | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. | | | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR | | | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED | | | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST | | | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS | | | FOR REVIEW BY THE BUILDING OFFICIAL. | | | | | | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE | | | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN | | | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD | | | THEM TO THE BUILDING OFFICIAL WITH A NOTATION | | | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE | | | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO | | | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL | | | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED | | | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING | | | OFFICIAL. | | | | | | 7) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE | | | PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF | | | RECORD AND BEFORE SUBMISSION TO THE BUILDING | | | DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE | | | IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, | | | MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED | | | INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE | | | PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1 | | | INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN | | | ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS. | | | FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH | | | INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM | | | LOADS AND SPACING USED IN THE TESTS. | | | | | | 8A) SHEETS A2.1 AND S0.2 BOTH SHOW WALL PRESSURES IN | | | VULT, THE NEGATIVE WALL PRESSURES SEAM LOW FOR THE 10 | | | SQ. FT. AT A MEAN ROOF HEIGHT OF 18 FEET. THE PLANS DO | | | NOT INDICATE ANY INTERPOLATION BETWEEN CONTOUR LINES IS | | | THIS THE CASE? | | | | | | 8B) PLEASE PROVIDE THE PRESSURES FOUND ON SHEET S0.2 IN | | | VASD SINCE BOTH THE MIAMI-DADE NOAS AND FLORIDA | | | APPROVALS ARE IN VASD. THE INSPECTORS DO NOT HAVE THE | | | TIME TO MULTIPLY THE VULT BY 0.6, SINCE THE APPROVALS | | | ARE VASD. | | | | | | 9) WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS | | | REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS & | | | WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN | | | ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF | | | INSPECTION. THIRD PARTY CERTIFICATION WILL BE REQUIRED. | | | 2017 FBC-B 2204.1 WELDING | | | 1. WELD PROCEDURES SPECIFICATIONS | | | 2. QUALIFICATIONS OF WELDING PERSONAL | | | 2017 FBC-B 2204.2 BOLTING. | | | IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED | | | PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD | | | AT 561-805-6666. | | | | | | 10) 109.3* BUILDING PERMIT VALUATION. FOR PERMITTING | | | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE | | | TOTAL REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND | | | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE | | | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR | | | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR | | | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING | | | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. | | | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED | | | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES | | | (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS | | | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE | | | CONGRESS. | | | | | | THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE | | | MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS. | | | WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING | | | PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE | | | QUALIFIER AND OWNER AND BRINGS IN THE LISTED | | | SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE | | | QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND | | | LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE | | | FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN | | | LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR | | | EACH PERMIT. | | | | | | ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK | | | STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE | | | AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS & | | | FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL | | | TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED | | | SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE, | | | LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR | | | FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE | | | REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT. | | | PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE | | | ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE | | | STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE | | | REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE | | | BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE | | | BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR | | | THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE | | | PRIME OR MASTER PERMIT. | | | | | | 11) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID | | | 19 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS | | | 561-718-9724. | | | | | | JAMES A. WITMER BN, PX, SFP, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT | | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6717 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2020-09-28 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2020-09-28 |
Time |
21:59 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2020-09-28 |
Time |
20:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2020-07-16 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2020-07-16 |
Time |
20:21 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2020-07-16 |
Time |
19:30 |
Sent To |
|
|
| Notes |
| 2020-07-16 20:19:40 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PROVIDE RISER DIAGRAM OF EXISTING SERVICE. NEC | | | 215.5; WPB FBC 107.2.1 | | | | | | 2. PROVIDE COMPLIANCE FOR THE FOLLOWING, A NOTE ON PLAN | | | WILL SUFFICE. | | | | | | A. EACH SIGN AND OUTLINE LIGHTING SYSTEM, OR FEEDER | | | CIRCUIT OR BRANCH CIRCUIT SUPPLYING A SIGN OR OUT-LINE | | | LIGHTING SYSTEM, SHALL BE CONTROLLED BY AN EXTERNALLY | | | OPERABLE SWITCH OR CIRCUIT BREAKER THAT WILL OPEN ALL | | | UNGROUNDED CONDUCTORS WITHIN SIGHT OF THE SIGN NEC | | | 600.6(A)(1) | | | | | | B. ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 405.1 | | | SHALL HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT | | | OR WHEN NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR & | | | TIME CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME | | | SWITCHES SHALL BE CAPABLE OF RETAINING PROGRAMING | | | DURING A LOSS OF POWER FOR A MINIMUM OF 10 HOURS. | | | FBC-EC 405.2.5 | | | | | | 3. THERE ARE SEVERAL OPTIONS ON THIS PLAN I.E. LIGHTING | | | NOTE #2, POWER PLAN KEY NOTE #2, POWER PLAN KEY NOTE | | | #4, POWER PLAN KEY NOTE #7. PROVIDE NOTE ON PLAN | | | STATING IF OPTIONS ARE EXERCISED REVISIONS TO THE PLAN | | | WILL BE SUBMITTED TO THE AHJ. FBC 107.4, 107.2.1 | | | | | | 4. PROVIDE NOTE ON PLAN STATING LOW VOLTAGE WILL | | | REQUIRE A SEPARATE ELECTRICAL PERMIT. FBC 107.2.1 FBC | | | 105.1 | | | | | | | | | | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | CODES IN EFFECT: | | | | | | IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN | | | PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE | | | 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A | | | COMPLETED RESUBMITTAL FORM, VIA EMAIL TO | | | [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT | | | NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE | | | RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: | | | | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | | UILDING-PERMIT-FORMS | | | | | | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2017 6TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | FRANK GIAQUINTO III | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | [email protected] | | | CELL: 561-657-1653 | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2021-02-26 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2021-02-26 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2021-02-26 |
Time |
10:51 |
Sent To |
|
|
| Notes |
| 2021-02-26 10:59:30 | SHEET E 1 - COOLER EXIT SIGNS NOT INDICATED | | | | | | | | | FIRE PROVISO: | | | | | | PROVIDE EXIT SIGNS PER REVISED SHEET A 1.0 | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2020-09-14 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2020-09-14 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2020-09-14 |
Time |
11:13 |
Sent To |
|
|
| Notes |
| 2020-09-14 11:31:29 | 2ND REVIEW COMMENTS | | | | | | | | | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | | | | THE COOLER DOORS ARE WITHIN THE MEANS OF EGRESS, THEY | | | ARE THE ONLY WAY OUT AND THE TWO INTERIOR DOORS SHALL | | | BE IDENTIFIED AND MARKED AS AN EXIT. | | | | | | BOTH DOORS ARE INDICATED AS # 9. | | | | | | THE EXTERIOR DOORS MARKED AS 3A AND 9 WOULD NOT BE | | | REQUIRED TO BE MARKED AS EXIT. | | | | | | | | | | | | THE BELOW PREVIOUS COMMENTS A RE-SUBMITTED: | | | | | | | | | 1) SHEET A 1.0 - AT THE OUSIDE OF THE NEW COOLER THERE | | | APPEARS TO BE 2 DOORS # 3A AND # 9. | | | | | | IS THIS DOOR PROPOSED AS AN EXIT DOOR FROM THE COOLER? | | | IF SO, PLEASE PROVIDE FOR COMPLAINCE WITH NFPA 101, CH | | | 7 MEANS OF EGRESS. | | | | | | BOTH DOORS OPEN OUT AND THERE APPEARS TO BE A DEADBOLT | | | ON DOOR 3A (GENERAL NOTES- DOOR 3A # 2) | | | | | | | | | | | | 2) SHEET E 1 - THERE IS NO INDICATIONS OF EXIT SIGNAGE | | | WITHIN THE NEW COOLERS. | | | | | | | | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2020-06-09 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2020-06-09 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2020-06-09 |
Time |
09:03 |
Sent To |
|
|
| Notes |
| 2020-06-09 15:10:20 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) SHEET A 1.0 - AT THE OUSIDE OF THE NEW COOLER THERE | | | APPEARS TO BE 2 DOORS # 3A AND # 9. | | | | | | IS THIS DOOR PROPOSED AS AN EXIT DOOR FROM THE COOLER? | | | IF SO, PLEASE PROVIDE FOR COMPLAINCE WITH NFPA 101, CH | | | 7 MEANS OF EGRESS. | | | | | | BOTH DOORS OPEN OUT AND THERE APPEARS TO BE A DEADBOLT | | | ON DOOR 3A (GENERAL NOTES- DOOR 3A # 2) | | | | | | | | | PER NFPA 101, CH 7 | | | | | | 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES. | | | 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED | | | READILY FROM | | | THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. | | | 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY | | | TO DOOR | | | LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER EXPOSURE TO | | | ELEVATED | | | TEMPERATURE IN ACCORDANCE WITH THE LISTING, BASED ON | | | LABORATORY | | | FIRE TEST PROCEDURES. | | | 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE | | | OF A KEY, A | | | TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM | | | THE EGRESS | | | SIDE. | | | 7.2.1.5.4 THE REQUIREMENTS OF 7.2.1.5.1 AND 7.2.1.5.3 | | | SHALL NOT | | | APPLY WHERE OTHERWISE PROVIDED IN CHAPTERS 18 THROUGH | | | 23. | | | 7.2.1.5.5 KEY-OPERATED LOCKS. | | | 7.2.1.5.5.1* EXTERIOR DOOR ASSEMBLIES SHALL BE | | | PERMITTED TO HAVE | | | KEY-OPERATED LOCKS FROM THE EGRESS SIDE, PROVIDED THAT | | | ALL OF THE | | | FOLLOWING CRITERIA ARE MET: | | | (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11 | | | THROUGH 43 FOR | | | THE SPECIFIC OCCUPANCY. | | | (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS | | | THAN 1 IN. | | | (25 MM) HIGH ON A CONTRASTING BACKGROUND THAT READS AS | | | FOLLOWS IS LOCATED ON OR ADJACENT TO THE DOOR LEAF: | | | THIS | | | DOOR TO REMAIN UNLOCKED WHEN THE | | | BUILDING IS OCCUPIED. | | | (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY | | | DISTINGUISHABLE | | | AS LOCKED. | | | (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT | | | INSIDE THE | | | BUILDING WHEN IT IS LOCKED. | | | | | | 7.2.1.5.10* A LATCH OR OTHER FASTENING DEVICE ON A DOOR | | | LEAF SHALL | | | BE PROVIDED WITH A RELEASING DEVICE THAT HAS AN OBVIOUS | | | METHOD OF | | | OPERATION AND THAT IS READILY OPERATED UNDER ALL | | | LIGHTING CONDITIONS. | | | 7.2.1.5.10.1 THE RELEASING MECHANISM FOR ANY LATCH | | | SHALL BE | | | LOCATED AS FOLLOWS: | | | (1) NOT LESS THAN 34 IN. (865 MM) ABOVE THE FINISHED | | | FLOOR FOR | | | OTHER THAN EXISTING INSTALLATIONS | | | (2) NOT MORE THAN 48 IN. (1220 MM) ABOVE THE FINISHED | | | FLOOR | | | 7.2.1.5.10.2 THE RELEASING MECHANISM SHALL OPEN THE | | | DOOR LEAF | | | WITH NOT MORE THAN ONE RELEASING OPERATION, UNLESS | | | OTHERWISE | | | SPECIFIED IN 7.2.1.5.10.3, 7.2.1.5.10.4, OR | | | 7.2.1.5.10.6. | | | | | | PLEASE REVIEW AND PROVIDE DETAILS. | | | | | | | | | | | | 2) SHEET E 1 - THERE IS NO INDICATIONS OF EXIT SIGNAGE | | | WITHIN THE NEW COOLERS. | | | | | | PER NFPA 101, CH 38 AND CH 7 | | | | | | 38.2.10 MARKING OF MEANS OF EGRESS. MEANS OF EGRESS | | | SHALL HAVE | | | SIGNS IN ACCORDANCE WITH SECTION 7.10. | | | | | | 7.10 MARKING OF MEANS OF EGRESS. | | | 7.10.1 GENERAL. | | | 7.10.1.1 WHERE REQUIRED. MEANS OF EGRESS SHALL BE | | | MARKED IN | | | ACCORDANCE WITH SECTION 7.10 WHERE REQUIRED IN CHAPTERS | | | 11 | | | THROUGH 43. | | | 7.10.1.2 EXITS. | | | 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS | | | THAT OBVIOUSLY | | | AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED | | | BY AN APPROVED | | | SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT | | | ACCESS. | | | 7.10.1.2.2* HORIZONTAL COMPONENTS OF THE EGRESS PATH | | | WITHIN AN EXIT | | | ENCLOSURE SHALL BE MARKED BY APPROVED EXIT OR | | | DIRECTIONAL EXIT SIGNS | | | WHERE THE CONTINUATION OF THE EGRESS PATH IS NOT | | | OBVIOUS. | | | | | | PLEASE PROVIDE EXIT SIGNS AS APPLICABLE. | | | | | | | | | | | | | | | 3) SHEET E 1 - WITH NO EMERGENCY LIGHTING IN THE NEW | | | COOLER, ILLUMINATION OF THE MEANS OF EGRESS IS REQUIRED | | | PER NFPA 101, CH 38 | | | | | | WITH NO WINDOWS THE EIXT SIGNS MAY NOT BE SUFFICIENT | | | FOR ILLUMINATION PURPOSES. | | | | | | 38.2.8 ILLUMINATION OF MEANS OF EGRESS. MEANS OF EGRESS | | | SHALL | | | BE ILLUMINATED IN ACCORDANCE WITH SECTION 7.8. | | | | | | 7.8.1.2 ILLUMINATION OF MEANS OF EGRESS SHALL BE | | | CONTINUOUS DURING THE | | | TIME THAT THE CONDITIONS OF OCCUPANCY REQUIRE THAT THE | | | MEANS OF EGRESS | | | BE AVAILABLE FOR USE, UNLESS OTHERWISE PROVIDED IN | | | 7.8.1.2.2. | | | 7.8.1.2.1 ARTIFICIAL LIGHTING SHALL BE EMPLOYED AT SUCH | | | LOCATIONS AND FOR | | | SUCH PERIODS OF TIME AS ARE NECESSARY TO MAINTAIN THE | | | ILLUMINATION TO THE | | | MINIMUM CRITERIA VALUES HEREIN SPECIFIED. | | | 7.8.1.2.2* UNLESS PROHIBITED BY CHAPTERS 11 THROUGH 43, | | | AUTOMATIC | | | LIGHTING CONTROL DEVICES SHALL BE PERMITTED TO | | | TEMPORARILY TURN OFF THE | | | ILLUMINATION WITHIN THE MEANS OF EGRESS, PROVIDED THAT | | | EACH LIGHTING | | | CONTROL DEVICE COMPLIES WITH ALL OF THE FOLLOWING: | | | (1) IN NEW INSTALLATIONS, THE LIGHTING CONTROL DEVICE | | | IS LISTED. | | | (2) THE LIGHTING CONTROL DEVICE IS EQUIPPED TO | | | AUTOMATICALLY ENERGIZE | | | THE CONTROLLED LIGHTS UPON LOSS OF NORMAL POWER AND IS | | | EVALUATED | | | FOR THIS PURPOSE. | | | (3) ILLUMINATION TIMERS ARE PROVIDED AND ARE SET FOR A | | | MINIMUM 15- | | | MINUTE DURATION. | | | (4) THE LIGHTING CONTROL DEVICE IS ACTIVATED BY ANY | | | OCCUPANT | | | MOVEMENT IN THE AREA SERVED BY THE LIGHTING UNITS. | | | (5) IN NEW INSTALLATIONS, THE LIGHTING CONTROL DEVICE | | | IS ACTIVATED BY | | | ACTIVATION OF THE BUILDING FIRE ALARM SYSTEM, IF | | | PROVIDED. | | | (6) THE LIGHTING CONTROL DEVICE DOES NOT TURN OFF ANY | | | LIGHTS RELIED UPON | | | FOR ACTIVATION OF PHOTOLUMINESCENT EXIT SIGNS OR PATH | | | MARKERS. | | | (7) THE LIGHTING CONTROL DEVICE DOES NOT TURN OFF ANY | | | BATTERY-EQUIPPED | | | EMERGENCY LUMINAIRES, UNIT EQUIPMENT, OR EXIT SIGNS. | | | 7.8.1.2.3* ENERGY-SAVING SENSORS, SWITCHES, TIMERS, OR | | | CONTROLLERS SHALL | | | BE APPROVED AND SHALL NOT COMPROMISE THE CONTINUITY OF | | | ILLUMINATION OF | | | THE MEANS OF EGRESS REQUIRED BY 7.8.1.2. | | | | | | PLEASE PROVIDE. | | | | | | | | | | | | 4) SHEET E 1 - THERE DOES NOT APPEAR TO BE EXIT SIGNS | | | AT THE TWO EXIT DOORS OF THE SEATING AREA. | | | | | | PER NFPA 101, CH 38 AND CH 7 | | | | | | 38.2.10 MARKING OF MEANS OF EGRESS. MEANS OF EGRESS | | | SHALL HAVE | | | SIGNS IN ACCORDANCE WITH SECTION 7.10. | | | | | | 7.10 MARKING OF MEANS OF EGRESS. | | | 7.10.1 GENERAL. | | | 7.10.1.1 WHERE REQUIRED. MEANS OF EGRESS SHALL BE | | | MARKED IN | | | ACCORDANCE WITH SECTION 7.10 WHERE REQUIRED IN CHAPTERS | | | 11 | | | THROUGH 43. | | | 7.10.1.2 EXITS. | | | 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS | | | THAT OBVIOUSLY | | | AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED | | | BY AN APPROVED | | | SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT | | | ACCESS. | | | 7.10.1.2.2* HORIZONTAL COMPONENTS OF THE EGRESS PATH | | | WITHIN AN EXIT | | | ENCLOSURE SHALL BE MARKED BY APPROVED EXIT OR | | | DIRECTIONAL EXIT SIGNS | | | WHERE THE CONTINUATION OF THE EGRESS PATH IS NOT | | | OBVIOUS. | | | | | | PLEASE REVIEW AND OR JUSTIFY. | | | | | | | | | | | | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2021-03-26 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2021-03-26 |
Time |
15:29 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2021-02-24 |
Time |
08:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2020-09-28 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2020-09-28 |
Time |
22:00 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2020-09-10 |
Time |
16:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
F |
Date |
2020-07-16 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2020-07-16 |
Time |
20:23 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2020-06-08 |
Time |
13:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2021-03-30 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2021-03-30 |
Time |
09:28 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2020-08-27 |
Time |
15:31 |
Sent To |
|
|
| Notes |
| 2021-03-25 15:08:51 | RECEIPT - MU-2020-33290 - $3273.09 - PAID | | 2020-08-27 15:31:59 | 8/27/20 EMAILED IMPACT FEE OFFICE FOR REVIEW. LEM |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2020-06-16 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2020-06-16 |
Time |
16:15 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2020-06-16 |
Time |
13:03 |
Sent To |
|
|
| Notes |
| 2020-06-16 16:15:44 | IMPACT FEES - DIGITAL SUBMITTALS: | | | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON | | | APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO | | | YOUR PROJECT OR EMAIL IT TO [email protected] . | | | PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300 | | | N. JOG RD. ROOM?S 2W01-2W14 WEST PALM BEACH, FL. | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
N |
Date |
2021-03-11 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-03-11 |
Time |
06:22 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-03-11 |
Time |
06:21 |
Sent To |
|
|
| Notes |
| 2021-03-11 06:24:14 | NO MECHANICAL WORK SHOWN ON THE SUBMITTED PLANS. THE | | | WALK IN COOLER AND FREEZER MUST BE SUBMITTED WITH A | | | SEPARATE PERMIT AND MECHANICAL REVIEW. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2020-09-21 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2020-09-21 |
Time |
13:27 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2020-09-21 |
Time |
13:16 |
Sent To |
|
|
| Notes |
| 2020-09-21 13:31:09 | PLAN DENIED NO PLAN SUBMITTED HM. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2020-07-13 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2020-07-13 |
Time |
08:34 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2020-07-13 |
Time |
07:52 |
Sent To |
|
|
| Notes |
| 2020-07-13 08:45:18 | NO AIR CONDITIONING PLANS SUBMITTED. WALK IN COOLERS | | | AND FREEZERS REQUIRE PLANS AND PERMIT. | | | IF COOLERS ARE OUTSIDE OF THE BUILDING WIND LOAD ARE | | | REQUIRED. | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2021-03-18 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2021-03-18 |
Time |
11:26 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2021-03-18 |
Time |
11:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2021-03-16 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2021-03-16 |
Time |
10:35 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2021-03-16 |
Time |
08:47 |
Sent To |
|
|
| Notes |
| 2021-03-16 10:37:26 | 3RD REVIEW FBC-2017 PLUMBING | | | PERMIT- 20041058 | | | 3/16/2021 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | COMMENTS FROM THE 1ST AND 2ND REVIEWS LISTED BELOW HAVE | | | NOT BEEN COMPLETELY ADDRESSED. NOTES IN CAPS HAVE BEEN | | | ADDED FOR FURTHER CLARIFICATION. | | | | | | 2) AR1 & A1.3: PROVIDE PLUMBING FIXTURE CALCULATIONS IN | | | ACCORDANCE WITH TABLE 403.3 FBC P. PROVIDE A SCHEDULE | | | INDICATING THE REQUIRED AND PROVIDED PLUMBING FIXTURES | | | FOR THE A2 OCCUPANCY. PLEASE NOTE THAT THE PLANS DO NOT | | | INDICATE DRINKING FOUNTAINS, OR A SERVICE SINK ARE | | | EITHER EXISTING OR PROPOSED. REFER TO SECTION 211.1- | | | 2113 FBC ACC FOR ACCESSIBLE DRINKING FOUNTAIN | | | REQUIREMENTS. SHEETS AR1 & A1.3: PLEASE INCLUDE THE | | | REQUIRED SERVICE SINK AND DRINKING FOUNTAIN IN THE | | | FIXTURE CALCULATION SCHEDULE. IF THE INTENTION IS TO | | | PROVIDE DRINKING WATER TO CUSTOMERS IN A CONTAINER FREE | | | OF CHARGE BY REQUEST PER SECTION 410.4 SUBSTITUTION, | | | PLEASE PROVIDE A NOTE IN THE SCHEDULE TO SHOW | | | COMPLIANCE. | | | | | | 3) A1.3: PROVIDE A WATER RISER DRAWING FOR THE | | | RESTROOMS SHOWING PIPE SIZES, LOCATIONS OF SHUTOFF | | | VALVES, WATER HAMMER ARRESTORS, BACKFLOW PREVENTERS, | | | MIXING VALVES ETC.- SECTION 107.3.5.1.3 WPB AMENDMENTS | | | TO THE FBC. SHEETS A1.6: WATER HAMMER ARRESTORS ARE | | | REQUIRED FOR SUPPLY LINES TO THE WATER CLOSETS. | | | | | | 4) A1.0 & A1.3: PROVIDE A SANITARY ISOMETRIC AND WATER | | | RISER DRAWING FOR ALL PLUMBING ALTERATIONS IN THE | | | KITCHEN/FOOD AND BEVERAGE PREP AREAS. SEE COMMENT ABOVE | | | FOR WATER RISER REQUIREMENTS. SHEET A1.0, A1.6: THE MOP | | | SINK DETAIL 1/A.16 IS MISLABELED AS FLOOR DRAIN/SINK | | | PLAN. SHOW THE MOP SINK POINT OF CONNECTION TO THE | | | GREASE WASTE LINE. | | | | | | 5) A1.0 & A1.3: PROVIDE PLUMBING FLAT LINE DRAWINGS | | | SHOWING THE SANITARY AND GREASE WASTE LINE RUNS, THE | | | WATER DISTRIBUTION SYSTEM, AND POINTS OF CONNECTION. | | | SHOW IN THE RISER AND FLAT LINE DRAWING HOW HOT WATER | | | IS BEING SUPPLIED TO THE LAVATORIES, HAND SINK, AND ALL | | | OTHER FIXTURES REQUIRING HOT OR TEMPERED WATER- SECTION | | | 107.2.1 WPB AND SECTION 607.1 FBC P. PLEASE NOTE THAT | | | GREASE WASTE CALCULATIONS ARE REQUIRED IF ANY NEW | | | FIXTURES ARE TO BE DRAINED INTO THE EXISTING SYSTEM- | | | SECTION 1003.3.1. SHEETS A1.3 & A1.6: A REFER TO | | | SECTION AND TABLE C404.5.1 FBC ENERGY CONSERVATION. THE | | | MAXIMUM 2 FT. PIPING LENGTHS FROM THE SOURCE OF HOT | | | WATER TO THE PUBLIC LAVATORIES IS EXCEEDED. PLEASE | | | PROVIDE EITHER A RECIRCULATION LINE OR POINT OF USE | | | WATER HEATERS AT THE LAV SINKS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2020-09-15 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2020-09-15 |
Time |
11:06 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2020-09-15 |
Time |
06:50 |
Sent To |
|
|
| Notes |
| 2020-09-15 11:06:55 | 2ND REVIEW FBC-2017 PLUMBING | | | PERMIT- 20041058 | | | 9/15/2020 | | | | | | CODES IN EFFECT: | | | | | | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | COMMENTS FROM THE 1ST REVIEW LISTED BELOW HAVE NOT BEEN | | | COMPLETELY ADDRESSED. ADDITIONAL NOTES IN CAPS HAVE | | | BEEN ADDED TO THOSE COMMENTS- PLEASE COMPLY. | | | | | | 2) AR1 & A1.3: PROVIDE PLUMBING FIXTURE CALCULATIONS IN | | | ACCORDANCE WITH TABLE 403.3 FBC P. PROVIDE A SCHEDULE | | | INDICATING THE REQUIRED AND PROVIDED PLUMBING FIXTURES | | | FOR THE A2 OCCUPANCY. PLEASE NOTE THAT THE PLANS DO NOT | | | INDICATE DRINKING FOUNTAINS, OR A SERVICE SINK ARE | | | EITHER EXISTING OR PROPOSED. REFER TO SECTION 211.1- | | | 2113 FBC ACC FOR ACCESSIBLE DRINKING FOUNTAIN | | | REQUIREMENTS. SHEETS AR1 & A1.3: PLEASE INCLUDE THE | | | REQUIRED SERVICE SINK AND DRINKING FOUNTAIN IN THE | | | FIXTURE CALCULATION SCHEDULE. IF THE INTENTION IS TO | | | PROVIDE DRINKING WATER TO CUSTOMERS IN A CONTAINER FREE | | | OF CHARGE BY REQUEST PER SECTION 410.4 SUBSTITUTION, | | | PLEASE PROVIDE A NOTE IN THE SCHEDULE TO SHOW | | | COMPLIANCE. | | | | | | 3) A1.3: PROVIDE A WATER RISER DRAWING FOR THE | | | RESTROOMS SHOWING PIPE SIZES, LOCATIONS OF SHUTOFF | | | VALVES, WATER HAMMER ARRESTORS, BACKFLOW PREVENTERS, | | | MIXING VALVES ETC.- SECTION 107.3.5.1.3 WPB AMENDMENTS | | | TO THE FBC. SHEETS A1.6: WATER HAMMER ARRESTORS ARE | | | REQUIRED FOR SUPPLY LINES TO THE WATER CLOSET AUTO | | | FLUSH VALVES AND THE URINAL- SECTION 604.9 FBC P. | | | PLEASE SHOW THEIR LOCATIONS IN THE WATER DIAGRAMS. | | | | | | 4) A1.0 & A1.3: PROVIDE A SANITARY ISOMETRIC AND WATER | | | RISER DRAWING FOR ALL PLUMBING ALTERATIONS IN THE | | | KITCHEN/FOOD AND BEVERAGE PREP AREAS. SEE COMMENT ABOVE | | | FOR WATER RISER REQUIREMENTS. SHEET A1.0, A1.6: SHOW | | | THE BEFORE AND AFTER LOCATIONS OF THE RELOCATED | | | HANDSINK AND THE MOP SINK. SHOW A FLAT LINE DRAWING | | | THAT SHOWS THE POINT OF CONNECTIONS OF THE DRAINS TO | | | THE GREASE WASTE LINE. IT IS NOT CLEAR IF THE MOP SINK | | | IS A NEW INSTALLATION OR A REPLACEMENT. PLEASE NOTE | | | THAT REVISED GREASE WASTE CALULATIONS MUST PROVIDED FOR | | | NEW GREASE WASTE LOADS DRAINING INTO THE SYSTEM- | | | SECTION 1003.3 FBC P. PROVIDE A SLAB REPAIR DETAIL- | | | SECTION 107.2.1 WPB. | | | | | | 5) A1.0 & A1.3: PROVIDE PLUMBING FLAT LINE DRAWINGS | | | SHOWING THE SANITARY AND GREASE WASTE LINE RUNS, THE | | | WATER DISTRIBUTION SYSTEM, AND POINTS OF CONNECTION. | | | SHOW IN THE RISER AND FLAT LINE DRAWING HOW HOT WATER | | | IS BEING SUPPLIED TO THE LAVATORIES, HAND SINK, AND ALL | | | OTHER FIXTURES REQUIRING HOT OR TEMPERED WATER- SECTION | | | 107.2.1 WPB AND SECTION 607.1 FBC P. PLEASE NOTE THAT | | | GREASE WASTE CALCULATIONS ARE REQUIRED IF ANY NEW | | | FIXTURES ARE TO BE DRAINED INTO THE EXISTING SYSTEM- | | | SECTION 1003.3.1. SHEETS A1.3 & A1.6: THE PLANS DO NOT | | | SHOW HOW HOT WATER IS BEING SUPPLIED TO THE FIXTURES. | | | SHOW THE LOCATION OF THE EXISTING WATER HEATER AND | | | PROVIDE A SCOPE OF WORK FOR THE APPLIANCE- EXISTING OR | | | TO BE REPLACED? VERIFY THAT THE DISTANCE FROM THE WATER | | | HEATER TO THE MOST REMOTE FIXTURE REQUIRING HOT WATER | | | DOES NOT EXCEED 50 FT. OR PROVIDE A RECIRCULATION LINE- | | | SECTION 607.2 FBC P. | | | | | | 7) A1.3: PROVIDE A PLUMBING FIXTURE AND DEVICE SCHEDULE | | | THAT INCLUDES THE RESTROOMS AND KITCHEN AREA- SECTION | | | 107.2.1 WPB & SECTION 405.9 FBC P. SHEET A1.6: THE MOP | | | SINK AND FLOOR DRAIN WERE NOT INCLUDED IN THE SCHEDULE. | | | A DEVICE SCHEDULE WAS NOT PROVIDED. | | | | | | 8) A1.3: THE MEN'S TOILET ROOM DOOR SHALL NOT SWING | | | INTO THE CLEAR FLOOR SPACE OF THE URINAL PER SECTION- | | | 603.2.3 FBC ACC. SHEET A1.3: THE PLAN SHOWS NO CHANGE | | | TO THE DOOR SWINGING INTO THE CLEAR FLOOR SPACE OF THE | | | URINAL. | | | | | | 9) PLEASE PROVIDE A PLUMBING SUB-PERMIT APPLICATION- | | | SECTION 105.1 WPB AMENDMENTS TO THE FBC-17. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2020-07-13 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2020-07-13 |
Time |
10:16 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2020-07-13 |
Time |
08:33 |
Sent To |
|
|
| Notes |
| 2020-07-13 10:17:51 | 1ST REVIEW FBC-2017 PLUMBING | | | PERMIT- 20041058 | | | 7/13/2020 | | | | | | CODES IN EFFECT: | | | | | | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET AR1: PROVIDE A LIST OF CURRENT CODES AND | | | STANDARDS USED IN THE DESIGN OF THE PROJECT. PLEASE | | | NOTE THAT ALL PLANS SHALL BE DESIGNED IN ACCORDANCE | | | WITH THE 2017 FLORIDA BUILDING CODES SIXTH EDITION. | | | REFERENCES ARE MADE TO THE ADA ON SHEET A1.3. PLEASE | | | NOTE THAT THE PLANS SHALL BE IN COMPLIANCE WITH THE | | | FBC-17 ACCESSIBILITY CODE. PLEASE REVISE THE REFERENCES | | | TO AVOID CONFUSION- SECTION 107.2.1 WPB. | | | | | | 2) AR1 & A1.3: PROVIDE PLUMBING FIXTURE CALCULATIONS IN | | | ACCORDANCE WITH TABLE 403.3 FBC P. PROVIDE A SCHEDULE | | | INDICATING THE REQUIRED AND PROVIDED PLUMBING FIXTURES | | | FOR THE A2 OCCUPANCY. PLEASE NOTE THAT THE PLANS DO NOT | | | INDICATE DRINKING FOUNTAINS, OR A SERVICE SINK ARE | | | EITHER EXISTING OR PROPOSED. REFER TO SECTION 211.1- | | | 2113 FBC ACC FOR ACCESSIBLE DRINKING FOUNTAIN | | | REQUIREMENTS. | | | | | | 3) A1.3: PROVIDE A WATER RISER DRAWING FOR THE | | | RESTROOMS SHOWING PIPE SIZES, LOCATIONS OF SHUTOFF | | | VALVES, WATER HAMMER ARRESTORS, BACKFLOW PREVENTERS, | | | MIXING VALVES ETC.- SECTION 107.3.5.1.3 WPB AMENDMENTS | | | TO THE FBC. | | | | | | 4) A1.0 & A1.3: PROVIDE A SANITARY ISOMETRIC AND WATER | | | RISER DRAWING FOR ALL PLUMBING ALTERATIONS IN THE | | | KITCHEN/FOOD AND BEVERAGE PREP AREAS. SEE COMMENT ABOVE | | | FOR WATER RISER REQUIREMENTS. | | | | | | 5) A1.0 & A1.3: PROVIDE PLUMBING FLAT LINE DRAWINGS | | | SHOWING THE SANITARY AND GREASE WASTE LINE RUNS, THE | | | WATER DISTRIBUTION SYSTEM, AND POINTS OF CONNECTION. | | | SHOW IN THE RISER AND FLAT LINE DRAWING HOW HOT WATER | | | IS BEING SUPPLIED TO THE LAVATORIES, HAND SINK, AND ALL | | | OTHER FIXTURES REQUIRING HOT OR TEMPERED WATER- SECTION | | | 107.2.1 WPB AND SECTION 607.1 FBC P. PLEASE NOTE THAT | | | GREASE WASTE CALCULATIONS ARE REQUIRED IF ANY NEW | | | FIXTURES ARE TO BE DRAINED INTO THE EXISTING SYSTEM- | | | SECTION 1003.3.1. | | | | | | 6) A1.3: TEMPERED WATER SHALL BE PROVIDED TO THE | | | LAVATORY PER SECTION 416.5 FBC P. PLEASE NOTE THAT | | | TEMPERED SHALL BE SUPPLIED THROUGH A WATER TEMPERATURE | | | LIMITING DEVICE THAT CONFORMS TO ASSE 1070- SECTION | | | 607.1.2 FBC P. | | | | | | 7) A1.3: PROVIDE A PLUMBING FIXTURE AND DEVICE SCHEDULE | | | THAT INCLUDES THE RESTROOMS AND KITCHEN AREA- SECTION | | | 107.2.1 WPB & SECTION 405.9 FBC P. | | | | | | 8) A1.3: THE MEN'S TOILET ROOM DOOR SHALL NOT SWING | | | INTO THE CLEAR FLOOR SPACE OF THE URINAL PER SECTION- | | | 603.2.3 FBC ACC. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
P |
Date |
2021-03-18 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2021-03-18 |
Time |
12:33 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2021-03-18 |
Time |
12:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
F |
Date |
2021-03-16 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2021-03-16 |
Time |
10:55 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2021-03-16 |
Time |
10:55 |
Sent To |
|
|
| Notes |
| 2021-03-16 11:01:37 | DIGITAL SIGNATURE REVIEW | | | 3/16/2021 | | | | | | 1) SHEETS A1.6 & AR.1 ARE NOT DIGITALLY SIGNED AND | | | SEALED BY THE ARCHITECT- FL. STATUTE 481.221 AND | | | SECTION 61G1-16.005. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2020-09-28 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2020-09-28 |
Time |
21:59 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2020-09-28 |
Time |
21:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2020-07-16 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2020-07-16 |
Time |
20:23 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2020-07-16 |
Time |
20:21 |
Sent To |
|
|
| Notes |
| 2020-07-16 20:23:00 | DIGITAL SIGNATURE FROM PE MUST HAVE VERIFIED DIGITAL | | | CERTIFICATE. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2021-03-26 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2021-03-26 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2021-03-26 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2020-09-16 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2020-09-16 |
Time |
10:19 |
Sent To |
|
|
| Notes |
| 2020-09-16 10:19:51 | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | | APPLICABLE: | | | | | | 1.) FREEZER STORAGE CALCULATIONS ARE INCONSISTENT IN | | | THE SITE PLAN, FLOOR PLAN AND LANDSCAPE PLAN. PLEASE | | | ADDRESS FOR CONSISTENCY. | | | | | | | | | NOTES: | | | | | | * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS. | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE ANY | | | QUESTIONS. | | | | | | * Z = GC (OUTPARCEL; BELMONT PLAZA) | | | | | | * PROPOSED SEATING: 63 SEATS (REQUIRED PARKING: 21 | | | PARKING SPACES) | | | | | | * PHOTOMETRIC PLAN: USE OF EXISTING POLE FIXTURE | | | LOCATION | | | | | | * RELATED PERMITS: LANDSCAPING (#20070015) | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2020-06-10 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2020-06-10 |
Time |
|
Rev Time |
|
| Received By |
llouie |
Date |
2020-06-10 |
Time |
|
Sent To |
|
|
| Notes |
| 2020-06-10 10:55:59 | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | | APPLICABLE: | | | | | | 1.) PROVIDE AN UPDATED SIGNED AND SEALED SURVEY OF THE | | | PROPERTY. THE SURVEY PROVIDED IS FROM FEBRUARY 2017 AND | | | DOES NOT REFLECT THE LATEST CHANGES MADE TO THE SITE. | | | | | | 2.) THE OUTDATED SURVEY SHOWS THAT THE EXISTING | | | STRUCTURE IS 4,056 SQ. FT. THE SITE PLAN SHOWS THAT THE | | | EXISTING BUILDING IS 3,810 SQ. FT. WITH A PROPOSED 102 | | | SQ. FT. BUILDING ADDITION. PLEASE CLARIFY THE | | | DISCREPANCY. | | | | | | 3.) THE PROPOSED SITE MODIFICATIONS WILL ELIMINATE | | | EIGHT (8) EXISTING PARKING SPACES. PLEASE PROVIDE | | | ADDITIONAL INFORMATION ON THE RESTAURANT SEATING | | | CAPACITY SO THAT REQUIRED PARKING CAN BE CALCULATED. | | | | | | 4.) THE EXISTING PARKING STALL STRIPING IS INCONSISTENT | | | WITH THE MINIMUM STRIPING REQUIREMENTS OF THE ZONING | | | AND LAND DEVELOPMENT REGULATIONS (ZLDRS). STRIPING FOR | | | THE PROJECT SHALL BE UPDATED FOR CONSISTENCY WITH THE | | | CITY?S STANDARDS. A STRIPING DETAIL SHALL ALSO BE | | | PROVIDED IN THE DETAILS SHEET TO ENSURE CONSISTENCY | | | WITH THE ZONING CODE. [ZLDR S.94-485] | | | | | | 5.) TWO-WAY DRIVE AISLES SHALL BE A MINIMUM OF 24 FT. | | | WIDE. [ZLDR S.94-485] | | | | | | 6.) DETAIL OF THE LOCATION OF THE BICYCLE RACKS (WITH | | | DIMENSIONS) REQUIRED IN THE DETAILS. BICYCLE RACK | | | DIMENSIONS AND SPACING SHALL BE CONSISTENT WITH THE | | | CITY?S BICYCLE PARKING DESIGN STANDARDS. | | | | | | 7.) THE VALUE OF THE CONSTRUCTION FROM PERMITS | | | TABULATED FOR THE YEAR EXCEEDS 50% OF THE STRUCTURE'S | | | VALUE ($546,074.00) ACCORDING TO THE P.B.C. PROPERTY | | | APPRAISER'S OFFICE; THEREFORE, PURSUANT TO SECTION | | | 94-441(C)(2) OF THE ZONING AND LAND DEVELOPMENT | | | REGULATIONS (ZLDR), THE LANDSCAPE ON THE SITE SHALL BE | | | IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN | | | ARTICLE XIV OF THE ZLDR. IF THE SITE CONFORMS TO | | | ARTICLE XIV, THEN TWO (2) COPIES OF A LANDSCAPE PLAN | | | DEMONSTRATING COMPLIANCE SHALL BE INCLUDED WITH THE | | | PERMIT RE-SUBMITTAL. IF THE SITE DOES NOT CONFORM TO | | | ARTICLE XIV, THEN PRIOR TO THE ZONING APPROVAL OF THIS | | | PERMIT A SEPARATE LANDSCAPE PERMIT AND IRRIGATION | | | PERMIT SHALL BE SUBMITTED SHOWING MATERIAL TO BRING THE | | | SITE INTO CONFORMITY. | | | | | | NOTES: | | | | | | * ANY REVISIONS TO THE PLANS MAY RESULT IN ADDITIONAL | | | COMMENTS. | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | | QUESTIONS. | | | | | | SEPARATE PERMITS REQUIRED FOR: BUILDING | | | INTERIOR/EXTERIOR IMPROVEMENTS, LANDSCAPING, SIGNAGE, | | | PHOTOMETRICS. | | | | | | * ZONE: GC (OUTPARCEL; BELMONT PLAZA). | | | |
|
|
|