Plan Review Details - Permit 20041048
Plan Review Stops For Permit 20041048
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-12-06 Cont ID  
Sent By jwitmer Date 2020-12-06 Time 16:04 Rev Time 0.00
Received By jwitmer Date 2020-12-06 Time 15:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-11-14 Cont ID  
Sent By jwitmer Date 2020-11-14 Time 15:14 Rev Time 0.00
Received By jwitmer Date 2020-11-14 Time 14:28 Sent To  
Notes
2020-11-14 15:16:03PLANS WILLBE STAMPED APPROVED ONCE ROOFING PASSES.
  
 PLEASE NOTE WE ARE WORKING FROM HOME IF YOU WOULD LIKE
 TO CONTACT ME, MY CELL NUMBER IS 561-718-9724.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-05-13 Cont ID  
Sent By jwitmer Date 2020-05-13 Time 10:27 Rev Time 0.00
Received By jwitmer Date 2020-05-13 Time 08:59 Sent To  
Notes
2020-05-13 10:20:102017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20041048
 ADD: 6411 PARKER
 CONT: TBD/ TO BE DETERMINED
 TEL: 305-725-5401
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. MAY 13TH/ 2020
 ACTION: DENIED
  
 1) SHEET A-1 INDICATES THE CODES THIS STRUCTURE WAS
 DESIGNED TO IS THE 2017 FBC-COMMERCIAL (BUILDING) AND
 THE 2017 FBC-RESIDENTIAL CODE.
 PLEASE NOTE THE RESIDENTIAL CODE IS TO BE USED STRICTLY
 FOR ONE AND TWO FAMILY DWELLING UNITS. PLEASE UPDATE
 THE PLANS.
  
 2) SHEET A-5 THE ROOF FRAMING PLAN SHOWS THE ROOF
 DRAINAGE BROKEN INTO 2 SECTIONS WITH ROOF DRAINS. NOTES
 TO THE RIGHT OF THE ROOF FRAMING PLAN INDICATES THE
 ROOF THICKNESS TO BE FROM 13 ? INCHES TO 6 INCHES AT
 EACH OF THE ROOF DRAINS. THAT IS A DIFFERENCE OF 7 ?
 INCHES IN HEIGHT. THE PLAN DOES NOT SHOW A SECONDARY
 ROOF DRAINAGE SYSTEM NOR A SECONDARY (EMERGENCY
 OVERFLOW) DRAINS OR SCUPPERS IN ACCORDANCE WITH SECTION
 1503.4.1 OF THE 2017 FBC-B. ALSO REVIEW 1503.4.2.1.
 OVERFLOW SCUPPERS.
  
 3A) SHEET A-4 SHOWS THE ROOFING PRODUCT TO BE A SINGLE
 PLY 60 MIL. TPO ROOFING MEMBRANE (20 YEAR). THIS REVIEW
 NO ROOFING PRODUCT APPROVAL WAS SUBMITTED. SINCE THERE
 IS NO CONTRACTOR SIGNED ONTO THIS PERMIT THE DESIGNER
 OF RECORD MAY WANT TO CONSIDER THE PRODUCT APPROVAL TO
 BE A DEFERRED SUBMITTAL.
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 3B) COMPONENTS & CLADDING. 2017 FBC-B 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES,
  
 3C) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 3D) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF
 ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR
 THE BASE SHEET AS CALCULATED IN COMPLIANCE WITH ROOFING
 APPLICATION STANDARDS RAS 117. CALCULATION PREPARED,
 SIGNED AND SEALED BY A FLORIDA REGISTERED PROFESSIONAL
 ENGINEER OR REGISTERED ARCHITECT. 1609.6.4.4.1
 COMPONENTS & CLADDING.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WE ARE WORKING FROM HOME IF YOU WOULD LIKE
 TO CONTACT ME, MY CELL NUMBER IS 561-718-9724.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2020-06-05 Cont ID  
Sent By jleahy Date 2020-06-05 Time 13:26 Rev Time 0.00
Received By jleahy Date 2020-06-05 Time 13:22 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2020-09-14 Cont ID  
Sent By shill Date 2020-06-24 Time 16:31 Rev Time 0.00
Received By mgonzale Date 2020-09-14 Time 15:10 Sent To  
Notes
2020-06-24 16:32:13CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT
 APPLICATION IF REQUIRED
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE
  
 MAIN PHONE: (561) 822-1200
  
 IF YOU HAVE AN ISSUED ENGINEERING PERMIT, OR A PENDING
 APPLICATION, PLEASE ADVISE VIA EMAIL ([email protected])
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-11-16 Cont ID  
Sent By pleduc Date 2020-11-16 Time   Rev Time 0.00
Received By pleduc Date 2020-11-16 Time 15:57 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-05-06 Cont ID  
Sent By pleduc Date 2020-05-06 Time   Rev Time 0.00
Received By pleduc Date 2020-05-06 Time 10:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-01-08 Cont ID  
Sent By lmarchan Date 2021-01-08 Time 09:07 Rev Time 0.00
Received By lmarchan Date 2021-01-07 Time 08:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-12-06 Cont ID  
Sent By jwitmer Date 2020-12-06 Time 16:14 Rev Time 0.00
Received By jwitmer Date 2020-12-03 Time 16:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-11-19 Cont ID  
Sent By lcrespo Date 2020-11-19 Time 16:10 Rev Time 0.00
Received By lcrespo Date 2020-11-10 Time 13:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-06-24 Cont ID  
Sent By shill Date 2020-06-24 Time 16:32 Rev Time 0.00
Received By shill Date 2020-05-04 Time 13:41 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2021-03-29 Cont ID  
Sent By lmarchan Date 2021-03-29 Time 17:11 Rev Time 0.00
Received By lmarchan Date 2021-01-08 Time 08:16 Sent To  
Notes
2021-03-29 15:32:59RECEIPT MU-2021-000894 - $33.40 - PAID
2021-01-08 08:15:5501/07/21 EMAILED IMPACT FEE OFFICE. QUESTIONNAIRE
 UPLOADED. CC

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-05-13 Cont ID  
Sent By jwitmer Date 2020-05-13 Time 10:27 Rev Time 0.00
Received By jwitmer Date 2020-05-13 Time 08:59 Sent To  
Notes
2020-05-13 10:21:49PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
 PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300
 N. JOG RD. ROOM?S 2W01-2W14 WEST PALM BEACH, FL.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2021-06-18 Cont ID  
Sent By medwards Date 2020-05-06 Time 14:57 Rev Time 0.00
Received By medwards Date 2020-05-06 Time 14:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-11-19 Cont ID  
Sent By lcrespo Date 2020-11-19 Time 16:10 Rev Time 0.00
Received By lcrespo Date 2020-11-19 Time 16:10 Sent To  
Notes
2020-11-19 16:11:0611/19/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-06-16 Cont ID  
Sent By tklarge Date 2020-06-16 Time 11:01 Rev Time 0.00
Received By tklarge Date 2020-06-15 Time 12:25 Sent To  
Notes
2020-06-16 10:42:52 
 1) SHEET A-1 REFERENCES THE 2017 FBC-RESIDENTIAL CODE.
 PLEASE NOTE THE RESIDENTIAL CODE IS TO BE USED STRICTLY
 FOR ONE AND TWO FAMILY DWELLING UNITS. PLEASE UPDATE
 THE PLANS.
 2) SHEET A-5 THE ROOF FRAMING PLAN SHOWS THE ROOF
 DRAINAGE BROKEN INTO 2 SECTIONS WITH ROOF DRAINS. NOTES
 TO THE RIGHT OF THE ROOF FRAMING PLAN INDICATES THE
 ROOF THICKNESS TO BE FROM 13 INCHES TO 6 INCHES AT EACH
 OF THE ROOF DRAINS. THAT IS A DIFFERENCE OF 7 INCHES IN
 HEIGHT. THE PLAN DOES NOT SHOW A SECONDARY ROOF
 DRAINAGE SYSTEM NOR A SECONDARY (EMERGENCY OVERFLOW)
 DRAINS OR SCUPPERS IN ACCORDANCE WITH SECTION 1503.4.1
 OF THE 2017 FBC-B. ALSO REVIEW 1503.4.2.1. OVERFLOW
 SCUPPERS.
 3) INDICATE ON THE PLANS WHERE THE CRYPT VENT DRAINS
 TERMINATE. ARE THEY PIPED UNDER THE SLAB TO A POINT OF
 DISCHARGE? CLARIFY.
 4) SHT. A-4 DETAIL B SHOWS THE THE CRYPT VENTS AS 1
 INCH AND SHEETS A-6 & P-2 SHOW THE VENTS AS 1 1/4 INCH.
 CLARIFY.
 5) SHTS. A-5 & P-1 & P-2 SHOW A 3 INCH ROOF DRAIN PIPE
 BUT THE ROOF DRAIN DETAIL ON P-1 ALSO SHOWS A 4 INCH
 DRAIN PIPE. CLARIFY.
 6) THE STORM PIPING SHALL BE SIZED BASED ON THE
 PUBLISHED ROOF DRAIN FLOW RATE, FBC-PLUMBING SEC. 1106.
 SUBMIT CALCULATIONS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2020-12-06 Cont ID  
Sent By jwitmer Date 2020-12-06 Time 16:03 Rev Time 0.00
Received By jwitmer Date 2020-12-06 Time 15:31 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2020-11-14 Cont ID  
Sent By jwitmer Date 2020-11-14 Time 15:13 Rev Time 0.00
Received By jwitmer Date 2020-11-14 Time 14:28 Sent To  
Notes
2020-11-14 15:14:342017 FBC- ROOFING PLAN REVIEW
 W. P. B. PERMIT: 20041048
 ADD: 6411 PARKER
 CONT: TBD/ TO BE DETERMINED
 TEL: 305-725-5401
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: SAT. NOV.14TH/ 2020
 ACTION: DENIED
  
 1A & B) SEMI- COMPLIED. ROOFING PRODUCT APPROVAL NOA
 16.0615.05WAS SUBMITTED.
  
 1C) 2ND REQUEST. W. P. B. 107.3.4. PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY FLORIDA
 ADMINISTRATIVE CODE RULE 61G20 SHALL BE REVIEWED AND
 APPROVED IN WRITING (SHOP DRAWING STAMP OF APPROVAL) BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 1D ) 2ND REQUEST. ROOFING: FOR ALL ROOFING PRODUCTS
 PLEASE IDENTIFY ALL ROOFING SUB-SYSTEMS AND THEIR
 ASSOCIATED PRESSURES FOR ROOF ZONE # 1. WITHIN THE
 SUBMITTED ROOFING PRODUCT APPROVAL THERE ARE SEVERAL
 ROOFING SUB-SYSTEMS. PAGES 11-42 ARE FOR INSULATED
 CONCRETE ROOF SYSTEMS.
 PAGES 43-50 ARE ROOFING SYSTEMS FOR NON-INSULATED
 ROOFS. WITHIN THESE SUB-SYSTEMS THERE ARE SUB-SYSTEMS
 THAT WOULD NOT MEET THE PRESSURES FOR ROOF ZONES 2 & 3
 PLEASE IDENTIFY WHICH SUB-SYSTEM IS GOING TO BE APPLIED
 TO THIS STRUCTURE. 107.2.1.2 FOR ROOF ASSEMBLIES
 REQUIRED BY THE CODE, THE CONSTRUCTION DOCUMENTS SHALL
 ILLUSTRATE, DESCRIBE AND DELINEATE THE TYPE OF ROOFING
 SYSTEM, MATERIALS, VENTING, FASTENING REQUIREMENTS,
 FLASHING REQUIREMENTS AND WIND RESISTANCE RATING THAT
 ARE REQUIRED TO BE INSTALLED. PRODUCT EVALUATION AND
 INSTALLATION SHALL INDICATE COMPLIANCE WITH THE WIND
 CRITERIA REQUIRED FOR THE SPECIFIC SITE.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WE ARE WORKING FROM HOME IF YOU WOULD LIKE
 TO CONTACT ME, MY CELL NUMBER IS 561-718-9724.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2020-05-13 Cont ID  
Sent By jwitmer Date 2020-05-13 Time 10:28 Rev Time 0.00
Received By jwitmer Date 2020-05-13 Time 08:59 Sent To  
Notes
2020-05-13 10:25:242017 FBC-ROOFING PLAN REVIEW
 W. P. B. PERMIT: 20041048
 ADD: 6411 PARKER
 CONT: TBD/ TO BE DETERMINED
 TEL: 305-725-5401
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: WED. MAY 13TH/ 2020
 ACTION: DENIED
  
 1A) SHEET A-4 SHOWS THE ROOFING PRODUCT TO BE A SINGLE
 PLY 60 MIL. TPO ROOFING MEMBRANE (20 YEAR). THIS REVIEW
 NO ROOFING PRODUCT APPROVAL WAS SUBMITTED. SINCE THERE
 IS NO CONTRACTOR SIGNED ONTO THIS PERMIT THE DESIGNER
 OF RECORD MAY WANT TO CONSIDER THE PRODUCT APPROVAL TO
 BE A DEFERRED SUBMITTAL.
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 1B) COMPONENTS & CLADDING. 2017 FBC-B 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES,
  
 1C) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 1D) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF
 ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR
 THE BASE SHEET AS CALCULATED IN COMPLIANCE WITH ROOFING
 APPLICATION STANDARDS RAS 117. CALCULATION PREPARED,
 SIGNED AND SEALED BY A FLORIDA REGISTERED PROFESSIONAL
 ENGINEER OR REGISTERED ARCHITECT. 1609.6.4.4.1
 COMPONENTS & CLADDING.
  
 2) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WE ARE WORKING FROM HOME IF YOU WOULD LIKE
 TO CONTACT ME, MY CELL NUMBER IS 561-718-9724.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-12-06 Cont ID  
Sent By jwitmer Date 2020-12-06 Time 16:13 Rev Time 0.00
Received By jwitmer Date 2020-12-06 Time 15:30 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-11-14 Cont ID  
Sent By jwitmer Date 2020-11-14 Time 15:15 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-05-06 Cont ID  
Sent By medwards Date 2020-05-06 Time 15:04 Rev Time 0.00
Received By medwards Date 2020-05-06 Time 15:04 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2020-05-21 Cont ID  
Sent By awooten Date 2020-05-21 Time   Rev Time  
Received By awooten Date 2020-05-21 Time   Sent To  
Notes
***NONE***