Plan Review Details - Permit 20040996
Plan Review Stops For Permit 20040996
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2020-07-02 Cont ID  
Sent By tklarge Date 2020-07-02 Time 10:08 Rev Time 0.00
Received By tklarge Date 2020-07-02 Time 09:24 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2020-06-15 Cont ID  
Sent By medwards Date 2020-06-15 Time 15:38 Rev Time 0.00
Received By medwards Date 2020-06-15 Time 14:44 Sent To  
Notes
2020-06-15 15:39:301ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20040996
  
 CODES IN EFFECT:
  
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE RESPOND TO THE 1ST CYCLE REVIEWER?S COMMENTS.
  
 2) PLEASE SHOW THE CALCULATION OF WHERE THE 3000 CFM
 COMBUSTION AIR IS GOING TO BE TAKEN FOR THE RANGE. FBC
 FS 107.2.1
  
 3) PLEASE PROVIDE A DRAWING SHOWING THE ROOMS AND THE
 GAS LINES RUNNING THRU THE HOUSE. I CAN NOT TELL IF
 SOME OF THE PE IS BURIED UNDER THE HOME. FBC FS 107.2.1
  
 4) PLEASE REFINE THE DRAWING. I CAN NOT DISTINGUISH
 FROM THE ?SQUARE? HOW THIS GAS LINE IS RUNNING. WHERE
 IS THE REGULATOR LOCATION FOR THE RANGE? PLEASE SHOW
 THE REGULATOR FOR THE WATER HEATER. THE DRAWING NEEDS
 TO BE CLEAR AS TO THE DIRECTION OF THE GAS LINE. FBC FS
 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-05-14 Cont ID  
Sent By jpearson Date 2020-05-14 Time 13:29 Rev Time 0.00
Received By jpearson Date 2020-05-14 Time 13:29 Sent To  
Notes
2020-05-14 13:29:30REVIEWED BY JERRY SMITH.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 NFPA 99 = HEALTH CARE FACILITIES CODE
 NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20040996 237 EDGEWOOD DR
  
  
 GAS COMMENTS:DENIED
 1.SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE RANGE
 PER FBC FG 304.1
 2.SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR) TO THE MOST REMOTE OUTLET IN THE
 BUILDING AND / OR SYSTEM FBC FG 402.4.1, 402.4.2
 3.INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM(S)
 ON THE PLAN PER FBC FG 402.1, 402.4.3 THRU 402.6
 4.PER WPB FBC 107.2.1, SHOW PE TO GALVANIZED RIGID
 PIPING TRANSITION ON RISER DIAGRAM.
 5.PER WPB FBC 107.2.1, PROVIDE THE TABLE USED IN SIZING
 SCHEDULE 40 GALVANIZED PIPE
 (A) BETWEEN THE PE TRANSITION AND THE MP REGULATOR;
 NOTE THAT THE 70? DEVELOPED LENGTH FOR THE 2 PSI SYSTEM
 SHALL INCLUDE THE GALVANIZED PIPING. IF 70? IS NOT
 SUFFICIENT THEN PROVIDE UPDATED DEVELOPED LENGTH.
 (B) DOWNSTREAM OF MP REGULATOR(S). INDICATE ON THE PLAN
 THE DISTANCE FROM REGULATOR TO APPLIANCE.
 6.PER WPB FBC 107.2.1, PROVIDE DETAIL OF MP REGULATOR
 WITH SHUTOFF VALVE, UNION AND OTHER REQUIRED
 ACCESSORIES. COMPLY WITH FBC FG 410.2.
 7.SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND FBC FG
 402.2, AND 301.3. GAS APPLIANCES SHALL BE LISTED AND
 LABELED. PLEASE NOTE, THE INSTALLATION MANUALS FOR ALL
 GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME
 OF INSPECTION PER FBC FG 305.1.
 8.IS THE TANKLESS WATER HEATER LOCATED INDOORS OR
 OUTDOORS. PER WPB FBC 107.2.1, CLARIFY.
 10.PER WPB FBC 107.2.1, PROVIDE A DIMENSIONED PLAN VIEW
 DRAWING SHOWING BUILDING LAYOUT INCLUSIVE OF ROOMS,
 DOORS AND WINDOWS, LOCATIONS OF GAS APPLIANCES, PIPE
 ROUTING AND METER. INDICATE ON THE PLAN IF THE TANKLESS
 WATER HEATER IS REPLACING AN EXISTING TANKLESS WATER
 HEATER OR IS IT REPLACING A STORAGE TANK TYPE WATER
 HEATER OR IS IT BEING ADDED TO THE EXISTING HOT WATER
 SYSTEM? INDICATE ON THE APPLICATION IN THE DESCRIPTION
 OF WORK. IF REPLACING OR SUPPLEMENTING, IDENTIFY AND
 SHOW LOCATION OF THE EXISTING WATER HEATER. SHOW
 HORIZONTAL DISTANCE FROM ANY OUTSIDE APPLIANCE EXHAUST
 TO NEAREST WINDOW OR OPERATING DOOR. THE HOUSE PLAN CAN
 BE HAND DRAWN. A PLAN OF RECORD IS AVAILABLE FROM THE
 WPB BUILDING DEPARTMENT BY CONTACTING CRAIG MCPHERSON
 AT 561-805-6684; EMAIL [email protected].
 11.PER WPB FBC 107.2.1, SHOW LOCATION OF MP REGULATOR
 AND SHUT OFF VALVE FOR THE RANGE. ADDITIONALLY, SHOW
 APPLIANCE SHUTOFF VALVE FOR THE RANGE AS REQUIRED BY
 FBC FG 409.5.1.
 12.PROVIDE SHUTOFF VALVE ON THE SUPPLY SIDE OF THE
 METER PER FBC FG 409.2.
 13.PROVIDE DOCUMENTATION THAT REGULATORS INSTALLED ON
 THE EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR
 OUTDOOR INSTALLATION TO COMPLY WITH FBC FG 410.1.
  
 A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS TIME
 AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED
 UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 END OF COMMENTS.
  
 PLUMBING PERMIT REQUIRED
 A PLUMBING PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A PLUMBING PLAN REVIEW HAS NOT BEEN PERFORMED
 AT THIS TIME. A SEPARATE PLUMBING PERMIT AND PLANS WILL
 BE REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED
 WORK. PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND RISER DIAGRAMS THAT REFLECT THE
 ENTIRE SCOPE OF PLUMBING WORK TO BE DONE. WPB AMEND. TO
 FBC SEC. 107.2.1.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE SIGNED AND SEALED BY THE DESIGNER AS
 REQUIRED BY FAC AND FS.
 ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE
 DESIGNER IN ACCORDANCE WITH FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20040996 237 EDGEWOOD DR
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-07-02 Cont ID  
Sent By tklarge Date 2020-07-02 Time 10:09 Rev Time 0.00
Received By tklarge Date 2020-06-30 Time 15:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-06-16 Time   Rev Time 0.00
Received By lmarchan Date 2020-06-10 Time 14:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-05-14 Time   Rev Time 0.00
Received By lmarchan Date 2020-04-28 Time 14:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2020-07-02 Cont ID  
Sent By tklarge Date 2020-07-02 Time 10:09 Rev Time 0.00
Received By tklarge Date 2020-07-02 Time 10:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-06-16 Cont ID  
Sent By jpearson Date 2020-06-16 Time 11:20 Rev Time 0.00
Received By jpearson Date 2020-06-16 Time 10:10 Sent To  
Notes
2020-06-16 10:10:01REVIEWED BY JERRY SMITH.

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-05-14 Cont ID  
Sent By jpearson Date 2020-05-14 Time 13:30 Rev Time 0.00
Received By jpearson Date 2020-05-14 Time 13:30 Sent To  
Notes
2020-05-14 10:27:51REVIEWED BY JERRY SMITH.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20040996 237 EDGEWOOD DR
  
  
 PLUMBING COMMENTS: PLUMBING PERMIT REQUIRED
  
 A PLUMBING PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A PLUMBING PLAN REVIEW HAS NOT BEEN PERFORMED
 AT THIS TIME. A SEPARATE PLUMBING PERMIT AND PLANS WILL
 BE REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED
 WORK. PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND RISER DIAGRAMS THAT REFLECT THE
 ENTIRE SCOPE OF PLUMBING WORK TO BE DONE. WPB AMEND. TO
 FBC SEC. 107.2.1.
  
 SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR TANKLESS WATER HEATER.
  
 PER WPB FBC 107.2.1, PROVIDE A DIMENSIONED PLAN VIEW
 DRAWING SHOWING BUILDING LAYOUT. INDICATE ON THE PLAN
 IF THE TANKLESS WATER HEATER IS REPLACING AN EXISTING
 TANKLESS WATER HEATER OR IS IT REPLACING A STORAGE TANK
 TYPE WATER HEATER OR IS IT BEING ADDED TO THE EXISTING
 HOT WATER SYSTEM? INDICATE ON THE APPLICATION IN THE
 DESCRIPTION OF WORK. IF REPLACING OR SUPPLEMENTING,
 IDENTIFY AND SHOW LOCATION OF THE EXISTING WATER
 HEATER. PROVIDE A WATER RISER DIAGRAM. THE HOUSE PLAN
 CAN BE HAND DRAWN. A PLAN OF RECORD IS AVAILABLE FROM
 THE WPB BUILDING DEPARTMENT BY CONTACTING CRAIG
 MCPHERSON AT 561-805-6684; EMAIL [email protected].
  
 PER WPB FBC 107.2.1, ALL PLANS SHALL BE BEAR THE
 PRINTED NAME AND SIGNATURE OF THE DESIGNER.
  
 A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS TIME
 AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED
 UPON THE REVIEW OF SUBMITTED CORRECTIONS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20040996 237 EDGEWOOD DR
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-07-02 Cont ID  
Sent By tklarge Date 2020-07-02 Time 10:09 Rev Time 0.00
Received By tklarge Date 2020-07-02 Time 10:09 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-06-16 Cont ID  
Sent By jpearson Date 2020-06-16 Time 11:24 Rev Time 0.00
Received By jpearson Date 2020-06-16 Time 11:23 Sent To  
Notes
2020-06-16 11:23:55PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A
 DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY
 VERIFICATION. PROVIDE CORRECTION. ALTERNATIVELY, A
 SIGNED/SEALED PAPER SET MAY BE SUPPLIED TO THE BUILDING
 DEPARTMENT WHEN ALL TRADES ARE APPROVED. WPB FBC 107.1;
 FS 471/481

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-05-14 Cont ID  
Sent By jpearson Date 2020-05-14 Time 13:32 Rev Time 0.00
Received By jpearson Date 2020-05-14 Time 13:32 Sent To  
Notes
2020-05-14 13:32:01PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A
 DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY
 VERIFICATION. PROVIDE CORRECTION. ALTERNATIVELY, A
 SIGNED/SEALED PAPER SET MAY BE SUPPLIED TO THE BUILDING
 DEPARTMENT WHEN ALL TRADES ARE APPROVED. WPB FBC 107.1;
 FS 471/481