Plan Review Details - Permit 20040933
Plan Review Stops For Permit 20040933
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2021-08-23 Cont ID  
Sent By jwitmer Date 2021-08-23 Time 14:04 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2020-09-03 Cont ID  
Sent By jwitmer Date 2020-09-03 Time 07:20 Rev Time 0.00
Received By jwitmer Date 2020-09-03 Time 07:19 Sent To  
Notes
2020-09-03 07:20:12ASBESTOS COMMERCIAL. PLEASE PROVIDE A SIGNED
 ACKNOWLEDGEMENT FROM THE CONTRACTOR, ON LETTERHEAD,
 STATING THAT THE INSTRUCTIONS ON THE WEBSITE OF
 ASBESTOS PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF
 HEALTH PALM BEACH COUNTY WILL BE FOLLOWED AND THAT
 NOTIFICATION WILL BE GIVEN TIMELY. ADDITIONAL
 INFORMATION REGARDING ASBESTOS REQUIREMENTS CAN BE
 FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
 19120504
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-05-05 Cont ID  
Sent By jwitmer Date 2020-05-05 Time 08:55 Rev Time 0.00
Received By jwitmer Date 2020-05-05 Time 08:51 Sent To  
Notes
2020-05-05 08:54:56ASBESTOS COMMERCIAL. PLEASE PROVIDE A SIGNED
 ACKNOWLEDGEMENT FROM THE CONTRACTOR, ON LETTERHEAD,
 STATING THAT THE INSTRUCTIONS ON THE WEBSITE OF
 ASBESTOS PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF
 HEALTH PALM BEACH COUNTY WILL BE FOLLOWED AND THAT
 NOTIFICATION WILL BE GIVEN TIMELY. ADDITIONAL
 INFORMATION REGARDING ASBESTOS REQUIREMENTS CAN BE
 FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
 19120504
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-08-10 Cont ID  
Sent By jwitmer Date 2020-08-10 Time 15:28 Rev Time 0.00
Received By jwitmer Date 2020-08-10 Time 15:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-05-05 Cont ID  
Sent By jwitmer Date 2020-05-05 Time 09:16 Rev Time 0.00
Received By jwitmer Date 2020-05-05 Time 08:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-08-20 Cont ID  
Sent By jleahy Date 2020-08-20 Time 07:48 Rev Time 0.00
Received By jleahy Date 2020-08-19 Time 08:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-05-13 Cont ID  
Sent By jleahy Date 2020-05-13 Time 13:11 Rev Time 0.00
Received By jleahy Date 2020-05-13 Time 12:56 Sent To  
Notes
2020-05-13 13:14:31FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 1) LIGHTING AND OUTLET CONTROL NOT SHOWN ON PLANS.
  
 PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1:
 8.4.2. FBC CE 405.7.1
 PROVIDE LIGHTING CONTROL PER FBC ENERGY CODE. FBC CE
 405.2.2.2
  
 2) AIC RATING CALCULATION REQUIRED FOR SERVICE AND
 PANELS
  
 PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
  
 3) SEPARATE PERMITS REQUIRED FOR LOW VOLTAGE, FIRE
 ALARM, CCTV, ACCESS CONTROL

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-04-29 Cont ID  
Sent By pleduc Date 2020-04-29 Time   Rev Time 0.00
Received By pleduc Date 2020-04-28 Time 16:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-08-23 Cont ID  
Sent By jwitmer Date 2021-08-23 Time 14:05 Rev Time 0.00
Received By jwitmer Date 2021-08-20 Time 11:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-09-03 Time 07:21 Rev Time 0.00
Received By lmarchan Date 2020-08-03 Time 11:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-05-19 Time   Rev Time 0.00
Received By lmarchan Date 2020-04-27 Time 16:08 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2020-05-05 Cont ID  
Sent By jwitmer Date 2020-05-05 Time 08:47 Rev Time 0.00
Received By jwitmer Date 2020-05-05 Time 08:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-08-07 Cont ID  
Sent By medwards Date 2020-08-07 Time 13:08 Rev Time 0.00
Received By medwards Date 2020-08-07 Time 12:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2020-04-28 Cont ID  
Sent By medwards Date 2020-04-28 Time 13:12 Rev Time 0.00
Received By medwards Date 2020-04-28 Time 13:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-05-19 Cont ID  
Sent By jpearson Date 2020-05-19 Time 10:25 Rev Time 0.00
Received By jpearson Date 2020-05-19 Time 09:45 Sent To  
Notes
2020-05-19 09:45:05REVIEWED BY JERRY SMITH.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-08-20 Cont ID  
Sent By jleahy Date 2020-08-20 Time 07:48 Rev Time 0.00
Received By jleahy Date 2020-08-20 Time 07:48 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-05-19 Cont ID  
Sent By jpearson Date 2020-05-19 Time 10:36 Rev Time 0.00
Received By jpearson Date 2020-05-19 Time 10:36 Sent To  
Notes
2020-05-19 10:33:31MECHANICAL SHEETS ARE SELF-CERTIFIED BY ENGINEER. ALL
 OTHER SHEETS OK. PER THE WPB AMENDMENTS TO THE FBC,
 EACH SHEET OF PLAN IS REQUIRED TO BE SIGNED AND SEALED
 BY THE PERSON RESPONSIBLE FOR THE DESIGN. A DIGITAL
 PLAN REQUIRES A DIGITAL SIGNATURE WITH THE PROPER THIRD
 PARTY VERIFICATION. SELF-CERTIFICATION IS NOT
 ACCEPTABLE FOR ENGINEERS. PROVIDE CORRECTION.
 ALTERNATIVELY, A SIGNED/SEALED PAPER SET MAY BE
 SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL TRADES ARE
 APPROVED. WPB FBC 107.1; FS 471/481