Plan Review Details - Permit 20040924
Plan Review Stops For Permit 20040924
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-06-12 Cont ID  
Sent By pleduc Date 2020-06-12 Time   Rev Time 0.00
Received By pleduc Date 2020-06-12 Time 12:07 Sent To  
Notes
2020-06-12 12:18:16THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) COVER SHEET - THERE ARE INCORRECT EDITIONS OF NFPA
 INDICATED THAT ARE NOT THE CURRENT EDITIONS ADDOPTED BY
 THE STATE OF FLORIDA.
  
 NFPA 30 & 30 A ARE THE 2015 EDITIONS.
  
 NFPA 70 IS 2014.
  
 PLEASE REVIEW AND ANSURE COMPLIANCE.
  
  
  
 2) THERE ARE NO NEW PUMP SPECIFICATIONS PROVIDED.
  
 PLEASE ENSURE THAT THE NEW PUMP MANUFACTURES SPEC
 SHEETS ARE PROVIDED FOR FIRE INSPECTOR REVIEW AND
 VERIFICATION.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-07-06 Cont ID  
Sent By shill Date 2020-07-06 Time 14:02 Rev Time 0.00
Received By shill Date 2020-06-11 Time 10:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2020-07-06 Cont ID  
Sent By medwards Date 2020-07-06 Time 10:41 Rev Time 0.00
Received By medwards Date 2020-07-06 Time 10:41 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-07-06 Cont ID  
Sent By medwards Date 2020-07-06 Time 10:44 Rev Time 0.00
Received By medwards Date 2020-07-06 Time 10:41 Sent To  
Notes
***NONE***