Plan Review Details - Permit 20040909
Plan Review Stops For Permit 20040909
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2020-07-17 Cont ID  
Sent By cpuell Date 2020-07-17 Time 14:51 Rev Time 0.00
Received By cpuell Date 2020-07-17 Time 14:51 Sent To  
Notes
2020-07-17 14:53:08SEPARATE REAR PROPERTY ROOF PERMIT APPLIED FOR
 (20070728) CHANGE PERMIT DESCRIPTION.

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2020-07-14 Cont ID  
Sent By cpuell Date 2020-07-14 Time 15:28 Rev Time 0.00
Received By cpuell Date 2020-07-14 Time 15:28 Sent To  
Notes
2020-07-14 15:28:39ROOF PERMIT FOR REAR PROPERTY OR FRONT PROPERTY? PLEASE
 EMAIL [email protected]

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2020-06-09 Cont ID  
Sent By cpuell Date 2020-06-09 Time 13:50 Rev Time 0.00
Received By cpuell Date 2020-06-09 Time 13:50 Sent To  
Notes
2020-06-09 13:51:18ROOF PERMIT FOR REAR PROPERTY OR FRONT PROPERTY? PLEASE
 EMAIL [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-07-23 Cont ID  
Sent By rmcdouga Date 2020-07-23 Time 10:58 Rev Time 0.00
Received By rmcdouga Date 2020-07-23 Time 10:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-06-29 Cont ID  
Sent By rmcdouga Date 2020-06-29 Time 08:37 Rev Time 0.00
Received By rmcdouga Date 2020-06-29 Time 08:37 Sent To  
Notes
2020-06-29 08:38:55PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW: THE COMMENT FROM
 THE FIRST REVIEW WAS NOT ADDRESSED.
  
 1) THE PROJECT IS LOCATED IN EXPOSURE C WITH A 170MPH
 VULT WINDSPEED. NO MEAN ROOF HEIGHT WAS PROVIDED. THE
 PROPERTY APPRAISER WEBSITE SHOWS THIS AS A TWO STORY
 STRUCTURE. ROOF ZONE 3 WITH A 20' ROOF HEIGHT HAS A
 -102 PSF UPLIFT PRESSURE. IF THE ROOF HEIGHT IS MORE
 THAN 20 FEET THE UPLIFT PRESSURE INCREASES. THE MAXIMUM
 DESIGN PRESSURE FOR THE W-207 SYSTEM THAT YOU SELECTED
 FROM FL1654 HAS A MAXIMUM DESIGN PRESSURE OF -90 PSF.
 SELECT A SYSTEM WITH AN ADEQUATE DESIGN PRESSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-05-28 Cont ID  
Sent By rmcdouga Date 2020-05-28 Time 07:50 Rev Time 0.00
Received By rmcdouga Date 2020-05-28 Time 07:50 Sent To  
Notes
2020-05-28 08:20:04PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PROJECT IS LOCATED IN EXPOSURE C WITH A 170MPH
 VULT WINDSPEED. NO MEAN ROOF HEIGHT WAS PROVIDED. THE
 PROPERTY APPRAISER WEBSITE SHOWS THIS AS A TWO STORY
 STRUCTURE. ROOF ZONE 3 WITH A 20' ROOF HEIGHT HAS A
 -102 PSF UPLIFT PRESSURE. IF THE ROOF HEIGHT IS MORE
 THAN 20 FEET THE UPLIFT PRESSURE INCREASES. THE MAXIMUM
 DESIGN PRESSURE FOR THE W-207 SYSTEM THAT YOU SELECTED
 FROM FL1654 HAS A MAXIMUM DESIGN PRESSURE OF -90 PSF.
 SELECT A SYSTEM WITH AN ADEQUATE DESIGN PRESSURE.

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2020-06-01 Cont ID  
Sent By fmittner Date 2020-06-01 Time 13:19 Rev Time 0.00
Received By fmittner Date 2020-06-01 Time 13:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status P Date 2020-07-23 Cont ID  
Sent By rmcdouga Date 2020-07-23 Time 11:04 Rev Time 0.00
Received By rmcdouga Date 2020-07-16 Time 16:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-07-14 Cont ID  
Sent By cpuell Date 2020-07-14 Time 15:28 Rev Time 0.00
Received By cpuell Date 2020-06-25 Time 14:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-06-09 Cont ID  
Sent By cpuell Date 2020-06-09 Time 13:50 Rev Time 0.00
Received By cpuell Date 2020-05-27 Time 08:29 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2020-05-28 Cont ID  
Sent By rmcdouga Date 2020-05-28 Time 07:50 Rev Time 0.00
Received By rmcdouga Date 2020-05-28 Time 07:50 Sent To  
Notes
***NONE***