| 2020-08-24 11:08:06 | THIRD BUILDING REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK |
| | SHALL COMPLY WITH THE MATERIALS AND METHODS |
| | REQUIREMENTS IN THE FLORIDA BUILDING CODE. |
| | |
| | SECOND REVIEW ORIGINAL COMMENTS: |
| | 1(A) PROPOSED STOREFRONT PLAN ON SHEET A1 SHOWS THAT |
| | EXISTING EGRESS DOORS ON THE ROOM ADJACENT TO THE |
| | "EXISTING GATHERING HALL WERE REDUCED. DEMO PLAN ON THE |
| | SAME SHEET SHOWS DOUBLE DOORS, WHILE PROPOSED PLAN |
| | SHOWS ONLY ONE DOOR. PLEASE IDENTIFY THE USE OF THIS |
| | ROOM AND SHOW THAT THE PROPOSED SINGLE DOOR IS ADEQUATE |
| | TO COMPLY WITH THE EGRESS REQUIREMENTS OF THIS ROOM. |
| | SEC. 702.6 FBC-EXISTING BUILDING. SEC. 1004.1 |
| | FBC-BUILDING. |
| | |
| | RESPONSE: |
| | ARCHITECT'S RESPONSE LETTER STATES "EXISTING CONDITIONS |
| | PLAN WAS SHOWN IN ERROR. ONLY A SINGLE DOOR EXISTS ON |
| | EAST SIDE. REVISED PAGE A1 AND PROVIDED PHOTO.". |
| | THIS STATEMENT IS INCORRECT. PHOTO PROVIDED WAS NOT |
| | TAKEN FROM THE BEST ANGLE TO SHOW IF THE EXISTING DOOR |
| | IS SINGLE OR DOUBLE. LOOKING AT THE PHOTO IT APPEARS TO |
| | SHOW TWO VERTICAL DOOR HANDLES AT THE END OF THE |
| | STOREFRONT ON THE EAST SIDE. TO AVOID MAKING A |
| | STATEMENT WITHOUT VERIFYING, I VISITED THE JOBSITE AND |
| | VERIFIED THAT THE EXISTING STOREFRONT HAS DOUBLE DOOR |
| | ON ALL THREE BAYS. PLANS WERE DRAWN CORRECTLY THE FIRST |
| | TIME. REVISE PLANS AS REQUIRED AND IDENTIFY THE USE OF |
| | THIS ROOM AND SHOW THAT THE PROPOSED SINGLE DOOR IS |
| | ADEQUATE TO COMPLY WITH THE EGRESS REQUIREMENTS OF THIS |
| | ROOM. SPECIFY THE USE AND OCCUPANT LOAD AND SHOW THE |
| | ROOM LAYOUT AND DIMENSIONS. SEC. 702.6 FBC-EXISTING |
| | BUILDING. SEC. 1004.1 FBC-BUILDING. |
| | |
| | 2- OK |
| | 3- OK |
| | 4- OK |
| | |
| | 5- NOTE: ADDITIONAL INFORMATION ADDED TO HELP EXPEDITE |
| | THE REVIEW AND PERMITTING PROCESS. |
| | PROPOSED SLIDING GLASS DOORS NEED TO COMPLY WITH SEC. |
| | 1010.1.4.3 FBC-BUILDING. AND ELECTRICAL PERMIT WILL BE |
| | REQUIRED. |
| | SEE COPY OF SEC. 1010.1.4.3 FBC-BUILDING BELOW: |
| | |
| | 1010.1.4.3 SPECIAL PURPOSE HORIZONTAL SLIDING, |
| | ACCORDION OR FOLDING DOORS. |
| | IN OTHER THAN GROUP H OCCUPANCIES, SPECIAL PURPOSE |
| | HORIZONTAL SLIDING, ACCORDION OR FOLDING DOOR |
| | ASSEMBLIES PERMITTED TO BE A COMPONENT OF A MEANS OF |
| | EGRESS IN ACCORDANCE WITH EXCEPTION 6 TO SECTION |
| | 1010.1.2 SHALL COMPLY WITH ALL OF THE FOLLOWING |
| | CRITERIA: |
| | |
| | 1.THE DOORS SHALL BE POWER OPERATED AND SHALL BE |
| | CAPABLE OF BEING OPERATED MANUALLY IN THE EVENT OF |
| | POWER FAILURE. |
| | |
| | 2.THE DOORS SHALL BE OPENABLE BY A SIMPLE METHOD FROM |
| | BOTH SIDES WITHOUT SPECIAL KNOWLEDGE OR EFFORT. |
| | |
| | 3.THE FORCE REQUIRED TO OPERATE THE DOOR SHALL NOT |
| | EXCEED 30 POUNDS (133 N) TO SET THE DOOR IN MOTION AND |
| | 15 POUNDS (67 N) TO CLOSE THE DOOR OR OPEN IT TO THE |
| | MINIMUM REQUIRED WIDTH. |
| | |
| | 4.THE DOOR SHALL BE OPENABLE WITH A FORCE NOT TO EXCEED |
| | 15 POUNDS (67 N) WHEN A FORCE OF 250 POUNDS (1100 N) IS |
| | APPLIED PERPENDICULAR TO THE DOOR ADJACENT TO THE |
| | OPERATING DEVICE. |
| | |
| | 5.THE DOOR ASSEMBLY SHALL COMPLY WITH THE APPLICABLE |
| | FIRE PROTECTION RATING AND, WHERE RATED, SHALL BE |
| | SELF-CLOSING OR AUTOMATIC CLOSING BY SMOKE DETECTION IN |
| | ACCORDANCE WITH SECTION 716.5.9.3, SHALL BE INSTALLED |
| | IN ACCORDANCE WITH NFPA 80 AND SHALL COMPLY WITH |
| | SECTION 716. |
| | |
| | 6.THE DOOR ASSEMBLY SHALL HAVE AN INTEGRATED STANDBY |
| | POWER SUPPLY. |
| | |
| | 7.THE DOOR ASSEMBLY POWER SUPPLY SHALL BE ELECTRICALLY |
| | SUPERVISED. |
| | |
| | 8.THE DOOR SHALL OPEN TO THE MINIMUM REQUIRED WIDTH |
| | WITHIN 10 SECONDS AFTER ACTIVATION OF THE OPERATING |
| | DEVICE. |
| | |
| | |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |