| 2020-05-22 11:06:00 | PLAN REVIEW - BUILDING |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER BUILDING - PX3169 |
| | PLANS EXAMINER 1&2 FAMILY - SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. VALUATION |
| | |
| | CITY OF WPB CHPT. 1 ? VALUE |
| | 109.3 BUILDING PERMIT VALUATIONS. |
| | |
| | BASED ON THE INFORMATION PROVIDED, VALUE CANNOT BE |
| | DETERMINED AT THIS TIME. |
| | |
| | 1. THE STATED VALUE APPEARS LOW FOR THE PROPOSED SCOPE |
| | OF WORK. |
| | 2. THE PERMIT VALUATION AND PERMIT FEE MUST BE |
| | COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED |
| | CONTRACTOR WOULD PROVIDE. |
| | 3. YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE |
| | OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT |
| | RENTAL TO VERIFY VALUE. |
| | 4. FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE |
| | BUILDING OFFICIAL. |
| | PLEASE INCREASE THE VALUATION ACCORDINGLY. |
| | |
| | 2. DESIGNER SHALL PROVIDE INSULATION VALUES FOR CEILING |
| | AND WALLS. |
| | PROVIDE AN ENERGY SUBMITTAL. |
| | FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE. |
| | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402 |
| | SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO |
| | DEMONSTRATE CODE COMPLIANCE BY THIS METHOD. |
| | |
| | 3. PROVIDE FRAMING DETAILS FOR EXTERIOR WALLS. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 4. PROVIDE WINDOW SCHEDULE. INCLUDE ROUGH OPENINGS AND |
| | DESIGN PRESSURES. |
| | THESE MAY BE PLACED ON THE PLAN NEXT TO EACH OPENING. |
| | 1709.5 EXTERIOR WINDOW AND DOOR ASSEMBLIES. |
| | THE DESIGN PRESSURE RATING OF EXTERIOR WINDOWS AND |
| | DOORS IN BUILDINGS SHALL BE DETERMINED IN ACCORDANCE |
| | WITH SECTION 1709.5.1 OR 1709.5.2. FOR THE PURPOSES OF |
| | THIS SECTION, THE REQUIRED DESIGN PRESSURE SHALL BE |
| | DETERMINED USING THE ALLOWABLE STRESS DESIGN LOAD |
| | COMBINATIONS OF SECTION 1605.3. |
| | |
| | 5. PROVIDE PRODUCT APPROVALS FOR PROPOSED WINDOWS. |
| | FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | SPECIFICALLY, PROVIDE WINDOW SUBMITTALS. |
| | |
| | 6. IDENTIFY MEANS OF EGRESS FROM PROPOSED BEDROOM. |
| | |
| | R311.1MEANS OF EGRESS. |
| | DWELLINGS SHALL BE PROVIDED WITH A MEANS OF EGRESS IN |
| | ACCORDANCE WITH THIS SECTION. THE MEANS OF EGRESS SHALL |
| | PROVIDE A CONTINUOUS AND UNOBSTRUCTED PATH OF VERTICAL |
| | AND HORIZONTAL EGRESS TRAVEL FROM ALL PORTIONS OF THE |
| | DWELLING TO THE REQUIRED EGRESS DOOR WITHOUT REQUIRING |
| | TRAVEL THROUGH A GARAGE. THE REQUIRED EGRESS DOOR SHALL |
| | OPEN DIRECTLY INTO A PUBLIC WAY OR TO A YARD OR COURT |
| | THAT OPENS TO A PUBLIC WAY. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED. |
| | |
| | |